7. Collection of Temperate
7-3
(2) Content of temperature conversion data [range : -20 to +40
°
C] (Pt100)
The meaning of the each bit( b0 to b15) of temperature conversion data (in WX**) is as shown
below.
The sum of the bit “1” is the measured temperature.
<For example>
(1) HE000 =
1110 0000 0000 0000"
(HE) (H0) (H0) (H0)
-800 + 40 + 20 = - 20
°
C
(2) H0600 = 0000 0110 0000 0000"
(H0) (H6) (H0) (H0)
2.5 + 1.25 = 3.75
℃
When an input error occurs( below -25
°
C and over 45
°
C), the temperature conversion data is
H7FFF.
The following relation exits between temperature conversion data and actual temperature.
Temperature (
°
C) =
Note) “b0” is always “0” in normal time.
Relation between the temperature and temperature conversion data
Figure 7.4
b15 b14 b13 b12 b11 b10 b9 b8 b7
b5
b6
b4
b3
b2
b1 b0
(
°
C)
-80
40
20
10
5
2.5
1.25
0.625
0.3125
0.15625
0.78125
0.390625
0.1953125
0.0976562
0.0488281
0.024414
Note)
H4000
H3000
H2000
H1000
H0800
-20
0
5
10
20
30
40
HE000
Temperate (
°
C)
b)Temperature conversion data(hexadecimal) -20 to +40
°
C
Temperature conversion data(signed decimal data)
409.6