Water pump configuration
Operation mode:
•
ΔT:
To control the pump speed to guarantee
the ΔT between Two and Twi.
•
Fix:
The water pump works at the specified
speed % at the space speed menu.
Space speed:
Selection of the % for the pump speed when fix
mode is selected.
DHW speed:
Selection of the % for the pump speed when
using DHW.
Swimming pool speed:
Selection of the % for the pump speed when
using Swimming pool.
Minimum OFF Time:
Minimum time of the water pump OFF.
•
Only when Economic mode is active (DSW)
Minimum ON Time:
Minimum time of the water pump ON.
•
Only when Economic mode is active (DSW)
Pumps during DHW:
This option allows to stop Water Pumps during
DHW operation. Water pumps that are allowed
to stop are the ones that are not directly involved
to DHW heating-up procedure. This is WP2 and
WP3 depending on the hydraulic configuration.
Overrun Time:
Added operation time of water pump
after Demand OFF.
Stop conditions:
•
Standard
•
Thermo OFF:
The water pump stops
after Thermo OFF. (DSW5 pin 4 ON).
Pump Setup:
This option allows user to select hydraulic
configuration of the system when hydraulic
separator is used.
•
Standard:
WP2 is connected after
WP3 by means an hydraulic separator
or directly by means Hitachi mixing kit
accessory. Whenever WP2 is switched
ON, WP3 is also switched ON in order to
transfer heat to C2.
•
Parallel:
WP2 is directly connected to
the buffer tank in parallel with WP3.
Operation of WP3 is independent
of the operation of WP2. When this
configuration is used, Hitachi mixing kit
accessory cannot be used.
Option available only when there is
Hydraulic separator configured.
2 / 2
1 / 2
Night Shift
Starting time of Nigh Shift operation
Ratio of reduction in heat pump capacity
Status of activation of Night Shift (reduction of compressor load in
order to reduce operation noise during the night hours).
Ending time of Night Shift operation