Hirschmann OWL LTE M12 Quick Installation Manual Download Page 3

OWL LTE M12 (Industrial Cellular Router) 

     Page 

3

 of 

4

 

Quick Installation Guide     

 Rel. 01 / Sept. 2016

 

First use 

Power cable connection

 

The router requires an external DC power supply. The DC voltage required is 

b12 to +48 V DC. The router has built-in protection against reverse polarity without 
signaling.  

Connect the power cable to the Power connector on the front panel of the router and 

tighten the locking screws (see the figure below). 

Grounding the device (functional earth)

 

The device is grounded via the separate ground screw. 

– Terminate the ground conductor using a M4 ring cable lug between the screw head and

the toothed lock washer.

– The wire diameter of the ground conductor is at least 0.5 mm² (North America: AWG20).
– Tighten the grounding screw with a tightening torque of 3 Nm ± 0.5 Nm
 (26.55 lb-in ± 4.43 lb-in). 

Ethernet cable connection

 

The Ethernet cable is connected to the ETH connector (see the figure below). 

The  Ethernet cable is used to configure and communicate with the router. 