Connection block diagram

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

PC, 

PLC, 

Touch Panel,

etc. 

+24V=

 

Tx

Rx

RS232

M-Bus meter

(1,5 mA load)

M+

M-

M-Bus meter

(1,5 mA load)

M+

M-

M-Bus meter 

(1,5 mA load) 

M+

M- 

GND

< 3 A

Up to 8 separate M-Bus meters 1,5 mA each can be connected per HIQUEL-MBUS-

MODBUS Converter  

Summary of Contents for SLS-500-MBUS-MODBUS Series

Page 1: ...HIQUEL HIQUEL MBUS Konverter HIQUEL MBUS Converter Hardware user manual ...

Page 2: ...y not be copied in part or whole in any form including electronic media without the written consent of HIQUEL Neither may it be transferred in any other language suitable for machines or data processing facilities Also rights for reproduction through lecture radio or television transmission are reserved This documentation and the accompanying software are copyrighted by HIQUEL Copyright 2005 2007 ...

Page 3: ...tum Author Description 30 06 06 O Reisky First version 27 09 06 H Weiß Add on of the function query pause 15 12 06 H Weiß Add on of the tested counters 05 03 07 M Niederl Add on of the tested counters 16 01 08 M Niederl Discription of the system registers ...

Page 4: ...must be routed so that no inductive or capacitive interference or any other severe electrical noise disturbance may interfere with the device Supply voltage variation must not exceed the specifications in the technical details If so proper performance of the device cannot be guaranteed Emergency installations according to EN60204 IEC204 VDE0113 must remain active in all modes of the automated inst...

Page 5: ...cribed steps in the following chapters Please observe the country specific rules and standards for the mini module installation Do not perform any electrical work while the device is connected to power Please pay attention to the following rules Activate the automated installation Disable any automatic restart system Electrically isolate the installation Cover any non isolated areas ...

Page 6: ...on 21 Content HISTORY 3 CONTENT 6 INTRODUCTION 7 BLOCK CONNECTION DIAGRAM 9 DESCRIPTION 9 CONNECTION BLOCK DIAGRAM 10 DESCRIPTION OF THE FUNCTIONS 12 TECHNICAL DATA 18 DIMENSIONS 18 ELECTRICAL DATA 19 APPENDIX 20 TESTED METERS 20 CONTACT 21 ...

Page 7: ...be seen from the respective data sheet The data to be read are freely configurable and are automatically actualised in selectable periods of time meter Bus ports for max 8 unit loads 1 5 mA meter Bus interface 300 to 38400 bps 8 data bits even parity 1 stop bit meter Bus and Modbus interfaces are galvanically isolated Modbus interface RS232 or RS485 9600 to 57600 bps 8 data bits no parity 1 stop b...

Page 8: ...RTU type RS232 or RS485 block connection diagram Figure 4 1 9600 to 57600 8 N 1 dimensions graphic Figure 6 1 dimensions B x H x T 22 5 x 85 x 70 Meter Bus interface max unit loads 8 300 to 38400 8 E 1 factory settings Modbus Address 255 Modbus baud rate 19200 ternimals M Bus baud rate 300 max terminal cross section 2 5 mm rigid 1 5 mm flexible CE conformity YES Accessories SLS 500 MBUS Configurat...

Page 9: ...85 interface A positive data link B negative data link C Meter Bus interface MBus MBus Meter Bus interface MBus MBus D indication of the status of the converter indication of the status of the converter E indication for supply voltage of the M Bus interface indication for supply voltage of the M Bus interface F Indication for sending data on the M Bus interface Indication for sending data on the M...

Page 10: ...Connection block diagram PC PLC Touch Panel etc 24V Tx Rx RS232 M Bus meter 1 5 mA load M M M Bus meter 1 5 mA load M M M Bus meter 1 5 mA load M M GND 3 A Up to 8 separate M Bus meters 1 5 mA each can be connected per HIQUEL MBUS MODBUS Converter ...

Page 11: ...te 11 von 21 PC PLC Touch Panel etc 24 V GND A B M Bus meter 1 5 mA load M M RS485 M Bus meter 1 5 mA load M M M Bus meter 1 5 mA load M M 3 A Up to 8 separate M Bus meters 1 5 mA each can be connected per HIQUEL MBUS MODBUS Converter ...

Page 12: ...ing on the configuration written into the respective Modbus registers From now on the selectable pause time between two query cycles is activated If no answer is received from an initialised MBUS device within three consecutively reading attempts this device is reinitialised within the following working cycle After three failed initialising attempts another attempt follows every 5 cycles After suc...

Page 13: ...dbus address 4x00001 Modbus baud rate 4x00001 Meter Bus baud rate pause between queries 4x00004 4x00005 4x00207 configuration Data points list 4x00204 store configuration 4x00205 4x00208 restart converter 4x00206 4x00300 unused Software version 4x00301 4x00301 Error code device status 4x00328 system device 1 8 4x00260 Identification number device 1 8 4x00328 4x00500 unused 4x00501 4x00700 value s ...

Page 14: ... SLAVESTATE3 read 4x00305 status device 4 SLAVESTATE4 read 4x00306 status device 5 SLAVESTATE5 read 4x00307 status device 6 SLAVESTATE6 read 4x00308 status device 7 SLAVESTATE7 read 4x00309 status device 8 SLAVESTATE8 read 4x00310 4x00311 4x00312 0 ID device 1 SLAVEID1 read 4x00313 1 ID device 2 SLAVEID2 read 4x00315 1 ID device 3 SLAVEID3 read 4x00317 1 ID device 4 SLAVEID4 read 4x00319 1 ID devi...

Page 15: ... RELEASE bit description MAJOR main version range 0 to 15 MINOR secondary version range 0 to 15 RELEASE issue range 0 to 255 Error code ERRCODE Holding Register 4x00302 factory setting 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 ERROR CODE bit description ERROR CODE Error code 0 no error 1 no valid configuration 2 error in configuration 3 system error ...

Page 16: ...y setting 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SLAVEADR SLAVESTATE bit description SLAVEADR Meter Bus address of the device range 0 to 255 SLAVESTATE device state 0 not configured 1 ready for initialisation 2 send the initialisation 3 wait for answer 4 ready for data exchange 5 send the query 6 wait for answer ...

Page 17: ...eader and is stored as a signed 32 bit binary number in 2 Modbus registers SLAVEIDx 1 Register Holding Register 4x00313 4x00315 4x00327 factory setting 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SLAVEID LOW WORD SLAVEIDx 2 Register Holding Register 4x00314 4x00316 4x00328 factory setting 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SLAVEID HIGH WORD ...

Page 18: ...6 1 Housing type dimensions in mm dimensions installation dimensions B x H x T mm 22 5 x 85 x 70 weight 85 g colour grey RAL 7012 material Noryl housing Wellamid terminals Lexan 940A cover plate protection class IP20 after DIN 40050 EN 60529 Table 6 1 Specification of the housing ...

Page 19: ...al data terminals clamp acquirement 1 screw tightening torque 0 4 0 8 Nm screws pozidrive 1 slot 3 5 0 6mm Table 6 3 Specification of the terminals Modbus interface physics RS232 RS485 carrying out terminals electrical isolation no power supply for external devices no status indication no settings 9600 to 57600 baud 8 data bits no parity 1 stop bit protocol Modbus RTU Table 6 4 Specification of th...

Page 20: ...d YSLY J n x 2 x 0 8 mm max cable length 350 m max cable capacity 180 nF Table 6 5 Specification of the Meter bus interface Appendix Tested meters The following meters were tested in house for proper function in combination with our converter manufacturer meter from software version Kamstrup Multical 401 1 0 0 Zenner Zähler multidata S1 2 0 0 Engelmann ista viterra Energy Services sensonic Sensost...

Page 21: ...HIQUEL HIQUEL MBUS Konverter Contact HIQUEL GmbH Bairisch Koelldorf Gewerbepark 266 A 8344 Bad Gleichenberg Tel 43 0 3159 3001 Fax 43 0 3159 3001 4 www hiquel com e mail hiquel hiquel com ...