4.7 Quick setup
69
Chapt
er
4 Configuring the
Instrument
before Me
asuremen
t (SYS-
TEM - SYSTEM screen) and W
iring
4
Type of measurement lines
Set before proceeding to the next step.
Current sensor used
Set before proceeding to the next step.
*: Set the range switch of the sensor to
500 A
when the
current range
of this instrument is set to
500 A
or
50 A
.
External VT Ratio, External CT Ratio
Set when attaching an external VT or CT. Set to 1 if not attaching an external VT or CT.
TIME PLOT Interval
Sets the TIME PLOT interval.
If the event icon (
) is orange after performing quick setup (indicating that the event is being
detected continuously), it is recommended to check and reconfigure the event's threshold.
"5.6Changing Event Settings" (p.87)
Setting Contents:
CH1,2,3:
1P2W/1P3W/3P3W2M/3P3W3M/3P4W/3P4W2.5E
CH4:
ACDC/DC/OFF
Current sensor
Current range
Optional
Other than the optional
AC flexible current sensor
CT7044
CT9667-01*
5000 A, 500 A, 50 A
CT7045
CT9667-02*
CT7046
CT9667-03*
AC leakage current sensor
CT7116
9657-10
5 A, 500 mA
9675
AC current sensor
CT7126
9694, 9695-02
50 A, 5 A
CT7131
9660, 9695-03
100 A, 50 A
CT7136
9661
500 A, 50 A
AC/DC auto-zero current sensor
CT7731
-
100 A, 50 A
CT7736
-
500 A, 50 A
CT7742
-
5000 A, 500 A
Clamp on sensor
9669
9669
1000 A, 100 A
Setting Contents:
0.01
to
9999.99
Setting Contents:(
∗
: Default setting)
1
/
3
/
15
/
30 second(s), 1
∗
/
5
/
10
/
15
/
30 minute(s), 1
/
2 hour(s), 150
/
180cycle
The 150 (50 Hz) and 180 (60 Hz) cycle settings provide the TIME PLOT intervals
required for IEC61000-4-30-compliant measurement. When using a measurement fre-
quency of 400 Hz, selecting 150/180 cycle will result in a 1200 cycle interval.
HIOKI PQ3198A961-03
Summary of Contents for PQ3198
Page 2: ...HIOKI PQ3198A961 03...
Page 6: ...Contents iv HIOKI PQ3198A961 03...
Page 20: ...Usage Notes 14 HIOKI PQ3198A961 03...
Page 44: ...2 3 Display Items and Screen Types 38 HIOKI PQ3198A961 03...
Page 58: ...3 8 Turning the Power On and Off Setting the Default Language 52 HIOKI PQ3198A961 03...
Page 102: ...5 8 Factory Settings 96 HIOKI PQ3198A961 03...
Page 198: ...12 4 Downloading Recorded Data to Computer 192 HIOKI PQ3198A961 03...
Page 264: ...14 4 Disposing of the Instrument 258 HIOKI PQ3198A961 03...
Page 296: ...A32 HIOKI PQ3198A961 03...
Page 299: ...Index Index 3 Index Wiring 73 Z Zero adjustment 53 Zero phase A28 HIOKI PQ3198A961 03...
Page 300: ...Index Index 4 HIOKI PQ3198A961 03...
Page 301: ...HIOKI PQ3198A961 03...
Page 302: ...HIOKI PQ3198A961 03...
Page 303: ...HIOKI PQ3198A961 03...
Page 304: ...www hioki com HIOKI PQ3198A961 03...