4 Start-up
X-DO 24 02
Page 28 of 54
HI 801 095 E Rev. 4.00
4 Start-up
This chapter describes how to install, configure and connect the module. For more
information, refer to the Safety Manual (HI 801 003 E).
i
The safety-related application (SIL 3 in accordance with IEC 61508) of the outputs and the
actuators connected must comply with the safety requirements. For more information, refer
to the HIMax Safety Manual.
4.1 Mounting
Observe the following points when mounting the module:
Only operate the module with the appropriate fan components. For more information,
see the System Manual (HI 801 001 E).
Only operate the module with the suitable connector board. For more information, see
Chapter 3.6.
Connection to the field zone with twisted pair wire
The module and its connected components must be mounted to provide protection of at
least IP20 in accordance with EN 60529: 1991 + A1: 2000.
The outputs may be wired redundantly using the corresponding connector boards. For
more information, see Chapters 3.6 and 4.5.
4.1.1
Wiring Outputs not in Use
Outputs that are not being used may stay open and need not be terminated. To prevent
short-circuits and sparks in the field zone, never connect a wire to a connector board if it is
open on the field side.