4 Start-up
X-AI 32 51
Page 38 of 58
HI 801 181 E Rev. 4.00
Name
Data
Type
R/W Description
SP HIGH
DINT
W
Lower limit of high level
SP HIGH
(switching point HIGH) is the limit value: if this limit
is exceeded, the module detects a HIGH and switches the
Channel
LED on.
Restriction:
SP LOW
≤
SP HIGH
Default setting: 40 500 (4.05 mA)
-> Ch. value [BOOL]
[BOOL]
R
Boolean channel value in accordance with the limits
SP LOW
and
SP HIGH
.
T on [µs]
UDINT
W
Time on delay
The module only indicates a level change from LOW to HIGH
if the HIGH level is present for longer than the configured
time t
on
.
Important: The maximum reaction time T
R
(worst case) for
this channel is extended by the delay time, since a signal
change is not detected until the delay time has expired.
Range of values: 0…(2
32
-1)
Default setting: 0
T off [µs]
UDINT
W
Time off delay
The module only indicates a level change from HIGH to LOW
if the LOW level is present for longer than the configured time
t
off
.
Important: The maximum reaction time T
R
(worst case) for
this channel is extended by the delay time, since a signal
change is not detected until the delay time has expired.
Range of values: 0…(2
32
-1)
Default setting: 0
-> State LL
BOOL
R
TRUE: Value associated with the LL event state
FALSE: Value out of the range associated with the LL event
state
-> State L
BOOL
R
TRUE: Value associated with the L event state
FALSE: Value out of the range associated with the L event
state
-> State N
BOOL
R
TRUE: Value associated with the N (normal) event state
FALSE: Value out of the range associated with the N (normal)
event state
-> State H
BOOL
R
TRUE: Value associated with the H event state
FALSE: Value out of the range associated with the H event
state
-> State HH
BOOL
R
TRUE: Value associated with the HH event state
FALSE: Value out of the range associated with the HH event
state
Redund.
BOOL
W
Requirement: A redundant module must exist.
Activated: Activate the channel redundancy for this channel
Deactivated: Deactivate the channel redundancy for this
channel
Default setting: Deactivated.
Redundancy value
BYTE
W
Setting for determining the redundancy value.
Min
Max
Average
Default setting: Max
It is only displayed in the redundancy group tab!
Table 23: Tab: I/O Submodule CI32_01:Channels in the Hardware Editor