4 Start-up
HI 801 111 E Rev. 4.00
Page 41 of 52
4.4.4
Connection via Field Termination Assembly
The connection via the X-FTA 002 01 is performed as described in Figure 15:. For further
information, refer to the manuals specific to the X-FTA 002 01 and X-FTA 009 02L.
Connector Board
AO-
X-AO 16 01
3
1
AO+
2
Field Termination
Assembly
Analog Output
System Cable
Actuator
Figure 15:
Connection via Field Termination Assembly
4.4.5
Characteristics of HART Communication
To ensure HART communication, a HART handheld can be connected in parallel to the
actuator. The current fluctuation caused by the HART communications is extensively
compensated by the analog output so that the maximum residual error of the preset current
is 2 % of the final value.
i
Higher residual error with HART communication. Remove the HART terminal directly after
the diagnosis!
Connector Board
X-AO 16 01
AO+
AO-
HART
2
1
Analog Output
Actuator
Figure 16: HART Handheld in Parallel to the Transmitter and Output Module