X-AO 16 01
4 Start-up
HI 801 111 E Rev. 4.00
Page 39 of 52
4.4 Connection
Variants
This chapter describes the correct wiring of the module in safety-related applications. The
connection variants specified here are permitted.
The outputs are wired via connector boards.
4.4.1 Single-Channel
Wiring
Connector boards X-CB 014 01 (with screw terminals) or X-CB 014 03 (with cable plug) can
be used to perform the wiring such as described in Figure 12.
Connector Board
AO-
X-AO 16 01
2
1
AO+
Analog Output
Load
Figure 12: Single-Channel Wiring
4.4.2
Redundant Wiring (Serial Connection)
When redundantly wired as specified in Figure 13, the modules are inserted in the base
plate next to each other and on a common connector board. The X-CB 014 02 or
X-CB 014 04 connector board can be used. Use the
Create Redundant Connection
function
to configure the redundancy in the SILworX Hardware Editor.
Connector Board
AO-
X-AO 16 01
2
1
AO+
AO-
X-AO 16 01
1
AO+
Analog Output
Actuator
Figure 13: Redundant Wiring (Serial Connection)