AI 8 01
4 Start-up
HI 800 195 E Rev. 2.00
Page 23 of 38
4.3.2
Analog Inputs
The following tables present the statuses and parameters for the input module in the same
order as given in the Hardware Editor.
4.3.2.1
Tab
Module
The
Module
tab contains the following system parameters:
System parameter
Data
type
R/W
Description
AI.Error Code
WORD
R
Error codes for all analog inputs
Coding
Description
0x0001 Module
fault
0x0008
FTT test: Walking bit of data bus faulty
0x0010
FTT test: Error while checking coefficients
0x0020
FTT test: Operating voltages faulty
0x0040
A/D conversion faulty (DRDY_LOW)
0x0080
Cross links of MUX faulty
0x0100
Walking bit of data bus faulty
0x0200
Multiplexer addresses faulty
0x0400
Faulty operating voltages
0x0800
Measuring system (characteristic) faulty
(unipolar)
0x1000
Measuring system (final values, zero point)
faulty (unipolar)
0x2000
Measuring system (characteristic) faulty
(bipolar)
0x4000
Measuring system (final values, zero point)
faulty (bipolar)
0x8000
A/D conversion faulty (DRDY_HIGH)
AI.Mode
BOOL
W
All channels unipolar or bipolar:
0 = unipolar measurement
1 = bipolar measurement
Module Error Code
WORD
R
Module error code
Coding
Description
0x0000
I/O processing, if required with errors, see
other error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: invalid configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS
UDINT
R
Slot number (System.Rack.Slot)
Module Type
UINT
R
Type of module, target value: 0xFD02 [64 770
dec
]
Table 13: SILworX - System Parameters for Analog Inputs,
Module
Tab