CIO 2/4 01
3 Product Description
HI 800 199 E Rev. 1.00
Page 15 of 40
3.4.3 Module
Indicators
LED
Color
Status
Description
On
Operating voltage present
RUN
Green
Off
No operating voltage
On
Module faulty or external faults
Reaction as dictated by the diagnosis
ERR
Red
Off
No module faults and / or no channel faults
Table 5:
Module Indicators
3.4.4 I/O
LEDs
LED
Color
Status
Description
On
The related output is active (energized).
1...4
Yellow
Off
The related output is inactive (de-energized).
Table 6:
I/O LEDs
3.4.5
Mode of Operation of the Counters
Both counters of the CIO 2/4 01 must be configured using system parameters, see Chapter
4.3.1 and Chapter 4.4.1.
The following modes of operation can be implemented:
Counter function 1 (depending on the count direction input signal)
Counter function 2 (irrespective of the count direction input signal)
Decoder operation with attached absolute rotary transducer
3.4.5.1
Counter Function 1 (Depending on the Count Direction Input Signal)
Counter[0x].Auto. Advance Sense
system parameter set to TRUE,
counting with falling edge on input A1 (A2).
Low level on count direction input B1 (B2) increments (increases) the counter value,
High level on count direction input B1 (B2) decrements (decreases) the counter value.
For this mode of operation, the Z1 (Z2) input must be set to low level. The counter can be
reset with a short-time high level.
Input C1 (C2) has no function.
The counter can be reset within the programming tool using the
Counter[0x].Reset
system
parameter.
Configuration of counter function 1:
System parameter
Description
Value
Counter[0x].5/24V Mode
Inputs 2
4 V
5 V
TRUE
FALSE
Counter[0x].Auto.
Advance Sense
Counter function 1 active
TRUE
Counter[0x].Direction No
function
FALSE
Counter[0x].Gray Code
Pulse operation active
FALSE
Counter[0x].Reset
Standard
Reset
short-time
TRUE
FALSE
Table 7:
Configuration of Counter Function 1