Hardware description
14/166
4.2
Interfaces
4.2.1
Supply voltage
X21
(see position
(17)
page 12]) is the
connector for the +24 V DC standard supply voltage (U
1L
) load circuit 1L.
U
1L
/ 1L supplies the power for the device itself (logic) and for the connected
IO-Link devices.
Note:
The sensorEDGE does not need or use auxiliary supply voltage
(U
2L
), even though the pins for the 2L auxiliary load circuit are
implemented on the device. The 1L and 2L load circuits are
galvanically isolated from each other.
Supply voltage
Pin
Signal Description
1
2
3
4
FE
M12, L-coded,
male
5-pin (4 + FE)
1
1L+
+24 V DC power supply for system and sensors (U
1L
)
2
2L-
Not used (device does not use U
2L
)
3
1L-
Ground for U
1L
4
2L+
Not used (device does not use U
2L
)
FE
FE
Functional earth
Table 7: Supply voltage
For a description of the LEDs belonging to this interface, see section
Accessories
Use cables featuring an M12 L-coded female connector for mating; e.g. one
of the following products (other brands are also available).
Cable assemblies:
·
·
https://www.ifm.com/de/en/product/E12641
·
https://www.phoenixcontact.com/online/portal/pi/?uri=pxc-oc-
itemdetail:pid=1414772
Connector only:
·
https://b2b.harting.com/ebusiness/en/M12-Power-IDC-female-L-code-
d/21032962505
·
https://b2b.harting.com/ebusiness/de/M12-Power-IDC-female-L-coded-
w-o-FE/21032962506
·
https://catalog.belden.com/index.cfm?event=pd&p=PF_RKCCS5L
netFIELD sensorEDGE | User manual
DOC200601UM01EN | Revision 1 | English | 2021-09 | Released | Public
© Hilscher 2021