LEDs
54/64
COM-C | Communication Module
DOC021001DG12EN | Revision 12 | English | 2011-06 | Released | Public
© Hilscher, 2002-2011
4.1.9 InterBus
Slave
LED
Color
State
Meaning
On
Protocol chip is supplied with power.
UL green
Off
Reset. Protocol chip is not supplied with power.
On
Communication to the IBS Master is possible.
RC green
Off
Communication to the IBS Master is not possible.
On
Master active, user data is exchanged
Flashing irregular
Communication is not possible,
system operation is being monitored.
BA green
Off
No user data is exchanged.
On
The outgoing interface is disabled.
RD yellow
Off
The outgoing interface is not disabled.
On
PCP communication, send or receive
TR green
Off
No PCP data is exchanged.
Table 34: LED InterBus Slave (COM)