Hillstone HLB480-375 Operating Manual Download Page 3

OMHLB480-375 M36548

INTRODUCTION

The load bank HLB480-375 is designed for battery discharge testing of lead acid at various power 
levels upto 174KW. Eleven switched steps are available to achieve the required load profile .
 The unit comprises of pre-set, high powered resistors channels of various rating, with each 
individual channels selectable via panel mounted switches and internal contactors.
A 3.5 metre DC cable set is provided plus a 5 metre auxiliary cable set.
The load bank is force cooled using a mains powered 240V single phase fan. 
Failure of the auxiliary mains supply will automatically de-energise the load contactors thereby 
preventing damage to resistor elements.
Test sockets are provided to allow measurement of DC volts and amps using external digital 
multimeters.

SAFETY CONSIDERATIONS

1. The equipment is designed for use in a clean, dry, indoor environment and should only be 

operated by competent electrical engineers who are completely familiar with the operation and 
specification of the load bank.

2. As with any electrical equipment the load bank should not be used in close proximity to recently 

charged batteries where a build up of explosive gases may have occurred.

3. Operators must ensure that interconnecting cables are correctly rated to carry the required load 

current and adequately insulated to prevent the possibility of electric shock when operating at 
high voltages..

4. All resistors are rated for operation when force cooled and therefore can only be used when the 

fans are running

5. Do not attempt to insert or remove the battery power plug with the load circuit energised.
6. When in use the load bank should be cordon off using safety barriers.
7. The load bank should only be operated in an area with adequate ventilation.
8. During operation the care should be taken as to the exhaust air outlet will be hot.
9. Do not smoke in the proximity of batteries.
10.Operators working with batteries should not wear rings, jewellery or metal watch straps.
11.Only insulated tools should be used when working on battery connections.
12.Refer to battery charger or the battery manufacturers operating instructions for additional safety 

precautions.

13.Ensure all personnel are familiar with the location of the nearest safety kit and eye wash facility.
14.During operation the load bank should not be covered or positioned to restrict air flow.
15.Caution metal surfaces will be hot during operation
16.Always run the fans for several minutes after a test, with the load switched off to cool the 

resistor elements.

3