DOMESTIC HOT SANITARY WATER VERSION (WDH/SW5) – 5 WATER PIPE CONNECTIONS
This version is suitable to produce domestic hot water: the unit is supplied with an ON/OFF 3 way valve to deviate the water flow in
a water accumulator; the activation of the 3 way valve is done automatically by the microprocessor control when the domestic hot
water temperature is lower than the required set point.
VSH
MC
BTI
EXV
SFW
BTO
IV
ØSC
ØSS1
MC
SLP
ØDS2
ØDS1
SHP
FL
CH
SV
ØDC
ØSS2
EV
IO
SHP
YL
CND
BTI
BTO
TA
LI
MI
T
E
D
I FO
RN
IT
UR
A
V3W
SUP
P
L
Y
LI
M
IT
VR
VR
AAS
MP
During winter operation, if domestic hot water is required, it is temporarily stopped the water flow into the
heating system. The unit microprocessor gives always priority to the domestic hot water.
WARNING: The WDH/SW5 is not available in the reversible version (RV).
The WDH/SW5 can also be combined with the free cooling version (WDH/FC/SW5).