USER'S GUIDE R18 AXIAL FAN , Iss: 6.05.2021

NFC / RFID WIRELESS COMMUNICATION

Fan has integrated NFC/RFID tag, based on ISO/IEC 15693, that can be used for advanced custom fan functionality configuration. NFC/RFID tag is
located as shown in the figure below. Before using NFC/RFID, the aluminium cover must be removed. Please see Hidria Fan App manual for more
information.

08

PROTECTIVE FEATURES

Short-circuit protection:

The motor and electronic controller are protected against short-circuit by built-in fuse.

Locked-rotor protection:

As soon the rotor is blocked, the motor is switched off electronically. After de-blocking, the motor will restart automatically. 

Mains under voltage:

If mains voltage falls below the nominal value the motor will keep running with degraded performance. Below 320V, the motor will be switched off
electronically in stand-by mode. When mains voltage returns to correct value, the motor will restart automatically. 
In the specific case, the undervoltage protection may switch off the fan to stand-by mode, for example, fan running or testing at high pressure drop and
low voltage.

Over temperature protection:

Internally connected thermal protector to protect electronic and motor against over temperature.

06

PUTTING INTO OPERATION

Before first start you should check:

a. Appropriate installation and electrical connection, especially resistance of the protective-earth (PE) circuit (max. 100m

).

b. If safety equipment is in place and motor protection device is in function.

c. If the impeller can rotate freely once the unit is mounted and the right direction of rotation is assured.

Only if all dangerous situations are excluded, the fan may be put into operation!

Switch ON the power supply.

Switch ON the device via the control signal and apply the speed setting voltage/signal and check the direction of the rotation and the smoothness of
running.

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

8 / 10

Summary of Contents for 0318-4-1006

Page 1: ...ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL DATA This document contains instructions and information for the operation installation connection use and maintenance of the product Be sur...

Page 2: ...rm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance is not intended to be built as a part...

Page 3: ...not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be permanently co...

Page 4: ...ensing Max pressure 250 Pa ErP DATA Overall Efficiency Effes 54 3 Installation category A Efficiency category static Efficiency grade N 57 7 Variable speed drive INTEGRATED Power Input Pelec 2917 9 W...

Page 5: ...juries the height and the diameter of inlet cone must be appropriate dimensions To lift the device with lifting devices use the hangers provided for this purpose as shown on figure below Always use su...

Page 6: ...ng plug must remain in the gland Connection box screws have to be tightened with torque of 2 0Nm 2 5Nm Secure connection cable to the fan guard grill or to the motor holder with cable fasteners so tha...

Page 7: ...but the highest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In o...

Page 8: ...correct value the motor will restart automatically In the specific case the undervoltage protection may switch off the fan to stand by mode for example fan running or testing at high pressure drop an...

Page 9: ...in circuit of electronics windings never try to repair the fan but replace it with new one or and return defected fan to the manufacturer for repair or replacement ALARM RELAY DIAGNOSTICS Alarm relay...

Page 10: ...protection grill Do not apply any force for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transp...

Reviews: