2.7 Reader wiring

Each reader port supports a reader with TTL (D1/D0, Clock/Data), F/2F (standard or supervised) or 2-wire 
RS-485 signaling (OSDP reader for example).  Power to the readers is selectable: 12 V DC (VIN must be 
greater than 20 V DC), or power is passed-through (PASS) from the input voltage of the LP1502 (TB1-VIN), 
300 mA maximum per reader port.  Readers that require different voltage or have high current requirements 
must be powered separately.  Refer to the reader manufacture specifications for cabling requirements.  In the 
2-wire LED mode the buzzer output is used to drive the second LED.  Reader port configuration is set via the 
host software.

To fully utilize each reader port:

 

n

TTL signaling requires a 6-conductor cable (18 AWG).

 

n

F/2F signaling requires a 4-conductor cable.

 

n

RS-485 signaling requires two 2-conductor cables.  Use one cable for power (18 AWG) and one cable for 
communication (24 AWG, with drain wire and shield).

Note:

  For OSDP cable lengths greater than 200 ft (61 m) or EMF interference, install 120

Ω

 +/- 2

Ω

 resistor 

across RS-485 termination ends.

Note:

  Data 0 and Data 1 wires for Wiegand may be reused for OSDP. However, standard Wiegand cable may 

not meet RS-485 twisted pair recommendations. The reuse of cable works best on shorter cable 
lengths at lower data rates.

J7 – Reader power select

12V PASS

Reader power

12 V DC is available on reader ports (VIN > 20 V DC)

VIN power is "passed through" to reader ports

Caution:

  If the input voltage to the LP1502 is 12 V DC, jumper J7 

MUST

 be in the 

PASS

 position.

Input power

Reader power select

Reader output

Notes

24 V DC

Pass-through

24 V DC

 

24 V DC

12 V DC

12 V DC

 

12 V DC

Pass-through

12 V DC

 

12 V DC

12 V DC

0 V DC

Caution:

 Do not use

PLT-05244, A.3

12

June 2021

Powering

Trusted Identities

HID Mercury™ LP1502 Controller

Installation and Specifications

Summary of Contents for Mercury LP1502

Page 1: ...HID Mercury LP1502 Controller Installation and Specifications PLT 05244 A 3 June 2021 HID Mercury LP1502 Controller Installation and Specifications Powering Trusted Identities...

Page 2: ...chnical Support www hidglobal com support Americas and Corporate Asia Pacific 611 Center Ridge Drive Austin TX 78753 USA Phone 1 866 607 7339 19 F 625 King s Road North Point Island East Hong Kong Pho...

Page 3: ...Section 01 Powering Trusted Identities Overview...

Page 4: ...eader that uses TTL D1 D0 Clock Data F 2F standard or supervised or 2 wire RS 485 device signaling OSDP reader for example and also provides tri state LED control and buzzer control one wire LED mode...

Page 5: ...Section 02 Powering Trusted Identities LP1502 wiring and setup...

Page 6: ...t 2 wire RS 485 TB3 2 TR B 1 TB3 3 TR A 1 TB4 1 IN2 Input 2 TB4 2 IN2 TB4 3 IN1 Input 1 TB4 4 IN1 TB5 1 IN4 Input 4 TB5 2 IN4 TB5 3 IN3 Input 3 TB5 4 IN3 TB6 1 IN6 Input 6 TB6 2 IN6 TB6 3 IN5 Input 5...

Page 7: ...Normally open contact TB10 2 C Out 1 Common contact TB10 3 NC Out 1 Normally closed contact TB10 4 NO Out 2 Normally open contact TB10 5 C Out 2 Common contact TB10 6 NC Out 2 Normally closed contact...

Page 8: ...eader ports PASS VIN Pass Through to reader ports J8 N A microSD card J10 1 N A Remote Status LED 1 1 J10 2 N A Remote Status LED 2 1 J10 3 N A Remote Status LED 3 1 J10 4 N A Remote Status LED 4 1 J1...

Page 9: ...FF Bulk Erase prompt mode at power up See Bulk erase configuration memory X X X ON Makes the LP1502 report and function like an EP1502 To be used in situations where the host software has not been upd...

Page 10: ...D 1 is on for about 15 seconds while LP1502 boots up 3 Change DIP switches 1 or 2 to OFF Within 10 seconds after LEDs 1 and 2 and LEDs 3 and 4 start flashing alternately at a rate of 0 5 seconds If th...

Page 11: ...g The LP1502 controller communicates with the host via the on board Ethernet 10 BaseT 100Base TX port and or the USB port 2 0 with an optional USB to Ethernet adapter The serial I O device communicati...

Page 12: ...uires two 2 conductor cables Use one cable for power 18 AWG and one cable for communication 24 AWG with drain wire and shield Note For OSDP cable lengths greater than 200 ft 61 m or EMF interference i...

Page 13: ...al reader 2 Wiegand or Clock Data installation Typical unsupervised F 2F reader Typical supervised F 2F reader Jumper D1 to LED on supervised F 2F reader Inputs on supervised F 2F readers may be unsup...

Page 14: ...voltage A supervised input circuit requires two resistors be added to the circuit to facilitate proper reporting The standard supervised circuit requires 1k 1 resistors and should be located as close...

Page 15: ...a diode is used to protect the relay Wire should be of sufficient gauge to avoid voltage loss Diode selection n Diode current rating 1x strike current n Diode breakdown voltage 4x strike voltage n Fo...

Page 16: ...battery status Off line 20 ON On line 80 ON Double flash if battery is low 2 Host communication activity Ethernet or Micro USB port 3 Internal SIO communication activity 4 External SIO communication...

Page 17: ...is shipped from the factory with a default login account which is enabled when DIP 1 is moved from OFF to ON See DIP switches The default login user name admin and password password will be available...

Page 18: ...Section 03 Powering Trusted Identities Specifications...

Page 19: ...rm C with dry contacts Normally open contact NO contact 5 A 30 V DC resistive Normally closed contact NC contact 3 A 30 V DC resistive Reader interface Power jumper selectable 12 V DC 10 regulated 300...

Page 20: ...anties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returns must be accompanied by a Return Material Authori...

Page 21: ...Added reader power select table in 2 7 Reader wiring A 2 January 2021 Add J19 Battery backup call out to the hardware diagram A 1 October 2020 Initial release A 0 PLT 05244 A 3 21 June 2021 Powering...

Page 22: ...a Pacific 19 F 625 King s Road North Point Island East Hong Kong Europe Middle East Africa 3 Cae Gwyrdd Green Meadow Springs Cardiff CF15 7AB United Kingdom Brazil Condom nio Business Center Av Ermano...

Reviews: