OPERATION

 

 On/Off : Press “

” to turn on, press “ ” again to turn off thermostat and its output. 

  Setting  temperature:  press  “

”  to  reduce  temperature,  press  “

”  to  raise  temperature  (0.5

  changed  each 

press) 

 

Mode Selection: Press “ ” to change system working in cooling “ ”, heating “ ” or ventilation “ ”mode.(The 

 Fan speed Selection (not for 

H7

990

 

Y/YE): Press 

 

”to select  (Hi),  (Med),  (Low), AUTO(Auto).

In mode “AUTO”(Auto)”, the fan-speed changed automatically. Auto LOW-speed When the differential temperature 

between  room-temperature  and  setting-temperature  exceed  1

,  Auto  MED-speed  When  exceed  2

,  Auto  HI-speed 

When exceed 3

 Control Damper (

H7

990

 

Y/YE): The damper will be open when room temperature is higher than set-point in

cooling; room temperature is lower than set-point in heating, Otherwise the damper will be closed. 

 

Control Motorized Valve under 2-pipe configuration (not for 

H7

990 

Y/YE): If the differential temperature between

 

room

temperature and set-point exceed 1

, FCU valve will be open; if room temperature and set-point are equal, 

H

7990

 

DA/

DAE/DA2/DA2E will close the FCU valve with the fan still running, H

7990

 

DB/DBE/DB2/DB2E will close both of valve

 

and

Fan. 

 Control FCU Valve under 4-pipe configuration (

H

7990

 

FCV2/FCV2E): In cooling, when the room temperature

is

 

higher than set-point, the cooling Valve will be opened. Otherwise it will be closed. Heating valve is always closed. 

In heating, When the room temperature is lower than set-point, the heating valve will be opened. Otherwise it will be 

closed. Cooling valve is always closed. 

CLOCK CALIBRATION ( -T, -T74 ) 

 

Press “M” with four seconds till to display “hh:mm” and “hh” flash, press “

” or “

” to adjust hour, press “M”, 

“mm” flash, press “

” or “

” to adjust minute; Press “M”, “week” flash, press “

” or “

” to adjust Mon to Sun. 

TIMER FUNCTION SETTING ( -T ) 

 Timer on/off function: Turn on or Turn off the thermostat according to customers setting

 

 

Timer on: Press “M”, till to display “ON” and “hh” all flash, press “

” or “

” to adjust hour. Press “M”, “mm” flash, 

press “

” or “

” to adjust minute. 

 

Timer off: Press “M”, till to display “OFF” and “hh” which all flash, press “

” or “

” to adjust hour. Press “M”, 

“mm” flash, press “

” or “

” to adjust minute. 

 

Canceling timer on: Press “M”, till to display “ON” and “hh” which all flash, press “

” or “

” to adjust hour to 

“--:--”. Press “M”, “mm” flash, press “

” or “

” to adjust minute to “--:--”. 

 

Canceling timer off: Press “M”, till to display “OFF” and “hh” which all flash, press “

” or “

” to adjust hour to 

“--:--”. Press “M”, “mm” flash, press “

” or “

” to adjust minute to “--:--”.   

7 DAYS PROGRAMMING (-T74) 

 Divide each day of one week (7 days) into four events, set the temperature respectively to satisfy different room 

temperature requirements in different time. 

 

Power On: Press “ ” and “ ” at same time for 3 seconds till displaying “SET”, ”1” and “MON”, to set the 7days 

4periods programs based on the following table. When 

“hh” of “hh:mm” is flashing, ”▲”or ”▼” button to set the hours of 

programming time; Press 

“ ”, “mm” of “hh:mm” is flashing, “▲” or ”▼” button to set the minutes of programming time; 

HERZ Armaturen Gws.m.b.H

Richard-Strauss-Strasse 22,1230 Vienna, Austria.

2

Summary of Contents for H7990 Series

Page 1: ...uto Restart Option STATUS DISPLAY Working Status Cooling Heating or Ventilation Fan Speeds low Mid High or Auto FCU valve status Room temperature display Temperature setting display Clock week display SPECIFICATIONS Sensing element NTC Control Accuracy 1 Set point range 5 to 35 Display range 0 55 Operation environment 0 45 Operating Humidity 5 90 RH non condensing Key Touch screen key soft touch k...

Page 2: ...When the room temperature is lower than set point the heating valve will be opened Otherwise it will be closed Cooling valve is always closed CLOCK CALIBRATION T T74 Press M with four seconds till to display hh mm and hh flash press or to adjust hour press M mm flash press or to adjust minute Press M week flash press or to adjust Mon to Sun TIMER FUNCTION SETTING T Timer on off function Turn on or...

Page 3: ...tion Turn off When the room temperature is lower than 5 the thermostat would automatically turn on the fan and valve with showing When the room temperature reaches to 7 the thermostat will automatically close the output Low Temperature Protection Setting Turn off press and hold for 3 seconds it will display OF or ON press or button to adjust the parameter OF indicates low temperature protection in...

Page 4: ...o the back panel in the wall then fix it with the two screws in the packing box 5 Put the cover with 30 degree angle then fix the up two clips 6 Push the places of the two down clips fix the cover and finish the installation Med Low H7990 25 L N Val Fan Valve AC85 260V 50 60Hz N L Hi Low H7990 27 L N VO Med Fan Valve VC AC85 260V 50 60Hz N L Hi Val2 Low H7990 26 L Cooling N Med Fan Val1 4 pipe L C...

Reviews: