The Herz 3 F800 16 transceiver 

The Herz 3 F800 16 is a 16-channel receiver of signals from TP-1xx 

wireless thermostats working on a frequency of 868.1 MHz. It can also 
be  used  with  Herz  thermostats  3  F800  50  or  3  F800  55  digital  bus 
thermostats.  The  Herz  3  F800  16  can  efficiently  control  multi-zone 
heating 

(including 

thermoelectric 

valve-actuators 

to 

replace 

thermostats  on  radiators)  or  cooling  systems.  The  receiver  has  a 
special  „ON  indicator”  channel  which  turns  the  heating  to  Stand-by 
economy  mode.  It  is  designed  for  heating  system  control  and  is  not 
suitable for extending hardwired alarm systems via wireless detectors. 

Due  to  the  maximum  current  limits  of the outputs, pulses switching 

the outputs off for short moments are used (when more than 8 outputs 
are  used).  Therefore  the  Herz  3  F800  16  should  only  be  used  with 
thermoelectric  valve-actuators.  It  should  not  be  used  to  control  any 
relays, semiconductor switches etc. LEDs on the receiver’s front cover 
indicate the status of each output channel.  

The  built-in  power  relay  modules  can  be  used  for  pump  and  boiler 

control. Both relays work with OR logic: they are switched if any of the 
1

–16 outputs is activated. 

Output no. 16 can be used with a wired temperature sensor for DHW 

control (Domestic Hot Water). 

Installation 

Attach the unit to the desired location with two screws. Route all the 

cables to the unit before you tighten the case. 

Fix  the  output  terminal  cables  (4)  firmly  inside  the  box  by  the 

mechanical grips if using flat cables. If you use round cables from the 
actuators remove the hole covers on the box bottom first. 

Note:  Only  a  qualified  technician  should  provide  installation  and 

servicing. The user is not allowed to open the cover and/or make any 
modifications.  The  mains  cable  must  also  be  fixed  outside  the 
receiver’s case. Replace the mains plug if necessary for your country. 

 

The output/input terminals: 

–  the  input  terminal  for  the  digital  bus  connection  (for 

thermostats of the relevant type). 

–   the input  terminal  for  cooling/heating  mode: 

Disconnect  =  Heating  (default  setting)  ;  Connect  = 
cooling.

 

–   the STAND-BY  input.  This  terminal  can  be  used  for 

remotely  controlling  the  mode  in  which  all the output 
channels  (4)  will  work,  switching  between  two 
possibilities:   A)  Terminal  disconnected:  The  outputs 
may 

be 

controlled 

by 

thermostat 

signals 

demanding/stopping 

heating 

   B) 

Terminal 

connected:  All  outputs  respond  to  the  Stand-by 
temperature  demanding  heating.  The  status  of  this 
channel is shown by the „ON indicator”. 

–   the input  terminal  for  the  high-temperature-cut-off 

wired sensor. It is designed for the TS-80 sensor. 

–   the input  terminal  for  DHW  control.  Once  it  is 

connected  output  no.  16’s  reaction  is  related  to  the 
domestic hot water tank. It is designed for the TS-80 
sensor. 

 

 

–   the output terminal for the alarm signal. There is a 10s 

pulse    in  events  concerning  freezing  alert  signals  or 
reaching  the  hi-temperature.  It  is  possible  to  set 
parameters for the freezing and the hi-temperature on 
the  LCD  module  or  on  thermostats.  This  output  is 
prepared for the GD-04 only .   

Power terminals of the power module: 

1

–16 

–   24VDC  channel  outputs.  The  Herz  3  F800  16  has 

pulsed switching. 

–   RJ-45  connector  for  an  LCD  module  or  additional 

Herz 3 F800 16 transceiver.  

Mains Power Terminals of the power module: 

 

–   mains  power  supply  output  for  the  circulatory 

pump (use an external fuse for its protection). 

 

–   mains power supply output for the heat exchanger 

(use  an  external  fuse  for  its  protection).  Can  be 
used  as  a  spare  relay.  It  is  recommended  to 
check  the  correct  connection  of  the relay with the 
manual of the connected device.  

 

–   power terminals for the power cord. 

 

The buttons: 

 

–  

 

or 

>

 

(left,  right  arrow)  for  the 

enrollment of wireless devices 

–  

RESET

 button, to delete enrolled devices for a 

channel 

The buttons are disabled if the LCD module is connected 

 

The  transceiver  is  protected  against  shorts  on  the  outputs.  If  an 

output is overloaded (the current is greater than 0.4A), then the output 
is automatically disconnected. A fault is indicated by rapid red flashing 
of  the  corresponding  LED  indicator.  The  output  is  under  constant 
monitoring  and  when  the  output  current  decreases  below  0.4A  the 
output will be switched on again. 

It is possible to connect an AC-100LCD module via the RJ connector 

(7).  The  LCD  module  provides  you  with  features  allowing  advanced 
programming and saving energy. 

If  it  is  necessary  to  have  more  channels,  then  it  is  possible  to 

connect  another  unit  via  the  RJ-45  connector.  In  this  case  the 
minimum distance between the units is 2m. If there is more then one 
unit  in  the  installation it is obligatory to use an LCD module. The unit 
with an LCD module works as a master unit, the other as a slave unit. 
Do NOT connect another LCD module to the slave unit. 

There is a connector for an external antenna (3) (e.g. AN-80 or AN-

81) and a covered hole for the cable on the bottom left of the housing. 
If  the  external  antenna  is  used  no  further  modifications  to  settings  or 
connections are necessary. 

 

 

Picture: 

1

 - Output/input terminals; 

2

 

– “ON indicator”; 

3

 - Antenna connector; 

4

 - Channels 1-16, Output terminals; 

5

 - Reset and 

enrollment buttons; 

6

 - DHW output; 

7

 

– 2 x RJ-45 connectors; 

8

 - Output relays; 

9

 - Power terminals; 

10

 - Fuse 3.15A 