HEROSE 0681 Series Operating Instructions Manual Download Page 9

Operating instructions 

herose.com 

 

4.3 

Intended use 

Safety valves protect vessels and pipework systems against impermissible excess pressure. Safety 
valves represent the last line of safety for a vessel or pipework system. They should be capable of 
preventing impermissible excess pressure when all other upstream regulating, control and monitoring 
devices have failed. In order to ensure this operability, safety valves require special attention during their 
mounting and maintenance. 
A safety valve is a piece of equipment with a safety function for protecting pressure equipment when the 
permissible limits are exceeded and is thus subject to Directive 2014/68/EU (Pressure equipment 
directive) of the European Parliament and of the Council, article 2, section 4. 

4.4 

Operational data 

Type 

d

[mm] 

Pressure 
range* 
[bar] 

Max. back 
pressure 
[%] 

Temperature 
[°C]** 

Medium 

0681x 

30 to 550 

10 

-270 to 
+400 

See section 
"4.5 Media" 

10 

0.5 to 180 

15 

06820 

30 to 550 

10 

0685x 

10 

0.5 to 250 

15 

14 

0.2 to 200 

18 

0.5 to 110 

*When the valve disc is implemented with a sealing plate, the sealing plate material (soft 
material seal) must be considered in relation to the pressure and temperature (see details on 
the technical data sheet). Further details are to be taken from the VdTÜV bulletin. 
**When the safety valve 06820 is made of material 1.4462, the temperature range is from -40 
to +250 °C. 

4.5 

Media 

Gases, cryogenic liquefied gases and their gas mixtures, such as: 

Name  

Argon, 
Nitrous oxide,  
Ethane,  
Ethylene,  
Helium, 
Carbon dioxide, 
Krypton,  
LNG 
LPG, 
Air,  
Methane, 
Neon, 
Oxygen, 
Nitrogen,  
Trifluoromethane,  
Hydrogen,  
Xenon,  

 

Summary of Contents for 0681 Series

Page 1: ...HEROSE GMBH ARMATUREN UND METALLE Operating instructions Angle type safety valve Type 0681X 06820 0685X...

Page 2: ......

Page 3: ...ermany Phone 49 4531 509 0 Fax 49 4531 509 120 E mail info herose com Web www herose com 2nd issue 10 2019 The transmission or duplication of this document and the use or communication of its content...

Page 4: ...Phone 49 4531 509 0 Table of contents 1 About these instructions 1 2 Safety 1 3 Transport and storage 4 4 Description of the safety valve 4 5 Assembly 7 6 Operation 8 7 Maintenance and service 9 8 Di...

Page 5: ...erating instructions see section 4 5 Media Operating conditions and applications deviating from these require the approval of the manufacturer Only media may be employed to which the materials used fo...

Page 6: ...for all work on the safety valve 2 5 Additional equipment and spare parts Additional equipment and spare parts not conforming to the manufacturer s requirements can negatively affect the operational...

Page 7: ...njury due to thermal influences Insulate the safety valve Attach warning signs Medium escaping at high speed and high low temperature Risk of injury Wear the prescribed protective equipment NOTICE Imp...

Page 8: ...n damp storerooms to prevent the formation of condensation Adhere to a storage temperature range of 20 C to 65 C 4 Description of the safety valve Refer to the respective catalogue page for further de...

Page 9: ...irective of the European Parliament and of the Council article 2 section 4 4 4 Operational data Type d0 mm Pressure range bar Max back pressure Temperature C Medium 0681x 6 30 to 550 10 270 to 400 See...

Page 10: ...rose products only for their intended purpose In this case a technical service life may be assumed in accordance with the underlying product standards e g EN1626 for shut off valves and EN ISO 4126 1...

Page 11: ...n Remove protective caps or covers before mounting Check the safety valve for dirt and damage DO NOT install damaged or dirty safety valves Remove any dirt and residues from the pipeline in order to a...

Page 12: ...tion position with the layout plan for the pipework system Dirt and residues have been removed from the pipeline and safety valve in order to prevent leaks 6 1 Liftability manual actuation for testing...

Page 13: ...s 7 2 1 Inspection and maintenance intervals Recommended intervals Inspection Interval Scope Inspection During start up Visual inspection of the angle valve for damage of the valving marking for legib...

Page 14: ...rectly or at all Attach water drain according to regulations Constantly blowing off Spring corroded by impermissible medium and broken Replace the safety valve System pressure too high Replace the saf...

Page 15: ...l service herose com Fax 49 4531 509 9285 8 Disassembly and disposal 8 1 Notices regarding the disassembly Take note of all national and local safety requirements The pipework system must be depressur...

Page 16: ...Operating instructions 12 Phone 49 4531 509 0...

Reviews: