![HEROSE 0651X Operating Instructions Manual Download Page 9](http://html1.mh-extra.com/html/herose/0651x/0651x_operating-instructions-manual_2126797009.webp)
Operating instructions
herose.com
5
4.3
Intended use
Div erter v alve for the installation of two or more saf ety valves in a possible combination with bursting discs
f or protecting gas storage tanks. The requirements of the pressure equipment directive for redundant or
dif f erent types of safety devices are f ulfilled with this diverter valve and in combination with safety valves
with the same setting pressure. Additional connections are av ailable on each side for suitable means of
testing.
In the case of serv icing the safety valves or replacement of the bursting discs, the side to be serviced is
isolated f rom the tank.
In the end position one outlet is open and the other is closed. It is not possible to shut off both outlets at
the same time.
4.4
Operating data
Valv e
Nominal
pressure
Temperature
Max. operating
pressure
06510
06511
PN50
-196 °C to +120 °C
50 bar
06512
06513
PN50
-196 °C to +120 °C
50 bar
06520
06521
PN50
-196 °C to +120 °C
50 bar
06530
06531
PN50
-196 °C to +120 °C
50 bar
4.5
Media
Gases, cry ogenic liquefied gases and their gas mixtures, such as:
Name
Argon
Chlorotrif luoromethane
Nitrous oxide
Ethane
Ethy lene
Carbon dioxide
Carbon monoxide
Kry pton
LPG
LNG
Methane
Oxy gen
Nitrogen
Trif luoromethane