HENRY A1584 Installation, Operation And Maintenance Manual Download Page 7

 
7. Installation Procedure 
 
WARNING:

 

Please read this section completely before commencing installation. 

 
Prior to commencing installation of the power supply, ensure that adequate precautions are taken 
against static damage to the sensitive electronic components on the A1584 board. You should 
discharge any static electricity that you may have accumulated by touching a convenient earthed 
object. 
 
The power supply unit should be located in a clean, dry position which is not subject to shock or 
vibration and at least 2 metres away from Pager systems or other radio transmitting equipment. The 
maximum temperature range is –10°C to +50°C @ 20%-90% humidity. Ensure that adequate 
ventilation is provided for the p.s.u at all times over the temperature range stated.  
 

Enclosure/Housing 
 
This type of power supply can be housed within an R3 rack enclosure (forming part of a system) or a 
standalone enclosure which can incorporate 2 x 12V rechargeable Lead Acid Batteries. When batteries 
are included the enclosure must provide adequate ventilation (see battery manufacturer’s 
recommendations). 
   
The power supply should be mounted on to a metal chassis or back plane using the 4 off M4 x 20mm 
bolts provided. Each of the four bolts should be spaced with the M5 x 6mm spacers provided. Figure1 
provides information relating to the dimensions and locations of the four fixing holes. 
 
Earthing Arrangement. 
 
It is recommended that the incoming Mains primary earth conductor is connected to a Stud or similar 
permanent fixed earth point on the intended p.s.u enclosure. The power supply must also be earthed. 
Additional earth connections must be made to the power supply chassis from the enclosure earth stud. 
There is an earth point connection on the Mains Terminal Block and also an M3 tapped hole (8mm 
depth) is available to allow for a ring terminated earth strap to be attached to the p.s.u chassis. It is 
recommended that the primary earth is connected to the enclosure earth stud. An earth strap should 
then be connected between enclosure earth stud and the psu chassis.  
 

FIGURE 2. Recommended Earthing arrangement 

 
 
 

Document Ref: O&M15845T.DOC/Rev 0    22.11.99      Page 7 of 8    Originator KP    Checked By        Approved By

 

 

Summary of Contents for A1584

Page 1: ...cations 6 7 Installation Procedure 7 8 Commissioning 8 1 Introduction Thank you for purchasing this 5A Power Supply Unit This power supply is designed to the requirements of EN54 4 This power supply will provide the user with many years of reliable service NOTE It is important to read this manual before commencing installation Document Ref O M15845T DOC Rev 0 16 11 99 Page 1 of 8 Originator KP Che...

Page 2: ...and other materials can substantially weaken the case WARNING Avoid charging the batteries in float standby applications outside of the range quoted by the battery manufacturer WARNING Do not incinerate batteries If placed in a fire the batteries may rupture with the potential to release hazardous gases and electrolyte VRLA batteries contain substances harmful to the environment Exhausted batterie...

Page 3: ...de power supply whilst the 5VDC output is derived via a regulator on the A1584 controller board In the event of Mains failure the power supply will automatically change over to the standby batteries The power supply has 9 LED status indicators to indicate what type of fault has occurred on the power supply The power supply consists of a steel mounting chassis with the A1584 a switchmode power supp...

Page 4: ...Document Ref O M15845T DOC Rev 0 22 11 99 Page 4 of 8 Originator KP Checked By Approved By ...

Page 5: ...etected by the A1584 a delay of 2 seconds is initiated and if the fault still exists after this delay period the Mains Fault output MF is activated 5 Termination List BATT Battery charger terminal 27 5volts 2 amps max two terminals 2 5mm2 cable max BATT Common 0 volt terminal two terminals 2 5mm2 cable max THERM Thermistor input two terminals 2 5mm2 cable max Mains LNE 2 5mm2 cable max 29VDC INPUT...

Page 6: ...AIN Mains input fault Amber Flashes whenever the DC input from the switchmode unit falls below 28V DC or above 30VDC THERM Thermistor Fault Amber Flashes whenever Thermistor input resistance falls outside its resistance range 800 Ohms to 52kOhms PSU OK PSU Healthy Green Illuminates whenever unit is not displaying any detected faults Turns off whenever charger is checking the presence of the batter...

Page 7: ...nclosure must provide adequate ventilation see battery manufacturer s recommendations The power supply should be mounted on to a metal chassis or back plane using the 4 off M4 x 20mm bolts provided Each of the four bolts should be spaced with the M5 x 6mm spacers provided Figure1 provides information relating to the dimensions and locations of the four fixing holes Earthing Arrangement It is recom...

Page 8: ...not permitted to be used while connected to the power pack otherwise will cause serious damage to internal components 5 As the equipment relies primarily on natural convection for cooling purposes it is important that the enclosure is checked sited in a position with a free flow of air This also applies to equipment fitted with cooling fans 6 Connect the A C mains supply to the mains terminal maki...

Reviews: