4.2 Display of the absolute data

 of the absolute shaft encoders

Function

Procedure

• Entering level 2

Press E and F2 simultaneously, light diode DATA is illuminated

• Select absolute data

Press 

 to switch either to single turn or to multi turn data.

Editing of the value is not possible.
For differentation of the data, the values are displayed:
Singleturn: f.e.  _4321
Multiturn: f.e.     8765_

4.3 Changing system parameters

Function

Procedure

• Entering level 3

Press keys E and 

-key (arrow up) key in de-energized state, then switch

on power

• Selection of changeable

parameter

Press key E shortly, until the desired indication " " in display is flashing (see
table chapter 4.4)

• Changing parameter

Selection of the various alternatives for each parameter by pressing 

-key

(arrow up) (see table chapter 4.4)

• Storage of parameter value

Press key E shortly to switch to the next parameter or press Key E for at
least 2 sec to exit operation level and return to the display mode

• Exit level 3 without storage

by the time criterion: the return to the display mode is done automatically 15
sec after a key has been pressed last, without the changed parameter being
stored

4.4 Survey on the system parameters and alternatives

Parameter

Display

Alternatives / Signification

total encoder
resolution / bit

'F1'

'1' to
'24'*

total encoder resolution in bits

encoder resolution single
turn / bit

'F2'

'0' to
'12''

*

resolution of the singleturn part in bits

Data coding

'F3'

'bin':*
'Gray':

binary code
gray code

Data transfer format

'F4'

'Std':*
'tan':

standard format, MSB-flush
pine-tree format

Signal OUT 1

'F5'

'off':
'bi':*

no output signal
output signal

Signal OUT 2

'F6'

'off':
'bi':*

no output signal
output signal

Special bits

'F7'

'0':*
'1':
'2':

no special bits
alarm
parity

Display per revolution

'F8'

'0'-
'4096' *
-'9999'

value, added to or subtracted from the display per revolution

Display divisor

'F9'

'1':*
'10':
'100':
'1000':

value by which the display is divided
(f.e. display per revolution = 35, display divisor = 10, display
per revolution = 3,5; i.e. first revolution = 3, second revolution
= 7).

Drive direction

'F10'

'0':*
'1':

adding in clockwise sense
adding in anti-clockwise sense

Multiple transfer

'F11'

'0':*
'1':

single transfer
double transfer in comparison

Decimal point

'F12'

'0':*
'1':
'2':
'3':

no decimal point
-.- decimal point at first digit
-.-- decimal point at 2nd digit
-.--- decimal point at 3rd digit

Function of first limit
value 1

'F20'

'0':

*

'1':

limit value 1 is absolute
limit value 1 is relative to limit value 2

Summary of Contents for signo 727 SSI

Page 1: ...function of position indicator 3 3 Operation of the position indicator 3 3 1 Display and keyboard 3 3 2 Setting the reference value and resset of the chain value 3 3 3 Changing limit value 1and 2 and set value 4 4 Programming 4 4 1 Survey 4 4 2 Display of the absolute data of the absolute shaft encoders 5 4 3 Changing system parameters 5 4 4 Survey on the system parameters and alternatives 5 5 Loc...

Page 2: ...place 4 Fix the position indicator with the screws against the panel 2 2 Terminal connections Attention Take care that all parts of system are deenergized during the installation of position indicator and that current is not switched on during assembly Safety conditions are to be observed during installation which shall be effected by trained personnel only Caution The operation and or switched vo...

Page 3: ...ter 4 3 Application input Terminal 25 set value refernce point display hold or chain reset can be programmed see chapter 4 3 2 3 Description of function of position indicator The position indicator is working in range mode i e the output signals Out 1 and Out 2 are set when reaching the respective limit value The bistable signal is active until the count value falls below the limit value or the co...

Page 4: ...de Exit without storage by time criterion the return to the display mode is automatically done 15 sec after the last pressing of a key without storing the changed parameter 4 Programming 4 1 Survey level 1 SET Setvalue long 2s Power ON and simultaneous P1 limit value 1 P2 limit value 2 short key to switch to the remarks next parameter DISPLAYMODE Normal Count Mode simultaneous simultaneous short l...

Page 5: ...ec after a key has been pressed last without the changed parameter being stored 4 4 Survey on the system parameters and alternatives Parameter Display Alternatives Signification total encoder resolution bit F1 1 to 24 total encoder resolution in bits encoder resolution single turn bit F2 0 to 12 resolution of the singleturn part in bits Data coding F3 bin Gray binary code gray code Data transfer f...

Page 6: ...it value 2 plus limit value 1 Example limit value 1 20 limit value 2 100 absolute OUT1 at 20 OUT2 at 100 relative OUT1 at 80 100 20 OUT2 at 100 5 Locking keyboard functions In level 3 the following keyboard functions can be locked Calibration function entry to level 1 entry to level 2 buttons F1 and F2 The setting of those keylocks is explained in chapter 4 3 6 failures and error messages failure ...

Page 7: ...put Values Relay Output Terminals 6 8 and 10 12 OUT 1 OUT 2 Contact Type changeover relay Contact Guard Circuit no externally recommended for capacitive and or inductive loads Switching Voltage max 30 VDC 250 VAC min 5 V AC DC Switching Current max 1 A min 10 mA Relay Response Delay 15 ms Transistor Output terminals 14 15 Switching voltage PNP 24VDC at AC supply VDC 2V at DC supply Switching curre...

Reviews: