HELVAR Digidim 313 Installation Manual Download Page 3

3

Helvar

 | Data is subject to change without notice.

www.helvar.com   

You can use a Helvar infrared remote handset, 
such as the 303 DIGIDIM Infrared Remote Control, 
to send signals to the 313 Detector to:
– Recall lighting scenes 1–4.
– Adjust light levels.
– Store current level.
– Install preset levels for scenes 1–4.

Remote Control

Other Functions

Sensitivity

Adjust the sensitivity using Designer, or Toolbox (Helvar’s lighting system design and control software).

Note:

  On maximum sensitivity, the detector unit is 

extremely sensitive

 to movement and may detect through glass, thin walls or 

partitions. If this causes a problem, reduce its sensitivity.

Adjusting On, Exit and Transition Time-Outs

The default time-outs for On, Exit and Transition can be altered using Designer, or Toolbox.

Check Connection to DALI Network

To make sure that the sensor is correctly connected the DALI network, use the 

Identify

 function in Designer, or Toolbox.

Using Designer and Toolbox Software

When using Designer, connect the PC to the lighting network via a Helvar router.
When using Toolbox, connect the PC to the lighting network via a Helvar serial or USB interface. 

For information about Designer and Toolbox, visit www.helvar.com.

303 DIGIDIM Infrared Remote Control

For details, see the 303 

Installation and 

User Guide.

External Power Supply (Optional)

The following table gives the various 12 V to 24 V external power supply units that can be used, 
as well as the sensor hardware revision needed for each of them. With some models, you must 
make a wire link between the DALI negative terminal and the negative terminal of the external 
power supply, as shown in the figure.

EPS

Current 
limited

Link from 
DA– to EPS–

Sensor hardware 
revision

Helvar 401

Yes

No

Any

Helvar 402

Yes

Yes

Any

Helvar 403

Yes

No

Any

Helvar 

LL1x30-E-CV24 Slow

No

4 or later

Generic 

12 V to 24 V

No

No*

4 or later

* Except in some cases where the generic EPS output is referenced to earth.

+

-

+

-