3.4. Connection of the sauna heater to the mains 

 
The sauna heater must be connected to the mains by a qualified electrician and in compliance with current regulations. The 
sauna heater is connected with a semi-permanent connection. Use H07RN-F (60245 IEC 66) cables or a corresponding type. 
Other output cables (signal lamp, electric heating toggle) must also adhere to these recommendations. Do not use PVC 
insulated cable as a connection cable for the sauna heater. 

A multipolar (e.g. 7-pole) cable is allowed, if the voltage is the same. In the absence of a separate control current fuse, the 
diameter of all cables must be the same, i.e. in accordance with the front fuse.  

The connecting box on the sauna wall should be located within the minimum safety clearance specified for the sauna heater. 
The maximum height for the connection box is 500 mm from the floor. See page 9 Image 2 Location for the connection box 

If the connection box is located at over 500mm distance from the heater, the maximum height is 1000mm from the floor. 

Sauna heater insulation resistance:

  

The sauna heater heating elements may absorb moisture from air, e.g. during storage. This may cause leakage currents. The 
moisture will be gone after a few heating sessions. Do not connect the heater power supply through a ground fault interrupter. 

However, adhere to the effective electrical safety regulation when installing the sauna heater. 

 

 

Power 

 
 
 
 
 

kW 

Sauna heater’s 

connection cable 

H07RN-F / 

60245 IEC 66 

mm

2

 

400 – 415V 3N~ 

Fuse 

 
 
 
 
 

Sauna heater’s 

connection cable 

H07RN-F / 

60245 IEC 66 

mm

2

 

230V 3~ 

Fuse  

 
 
 
 
 

Sauna heater’s 

connection cable 

H07RN-F / 

60245 IEC 66 

mm

2

 

230-240V 1N~/2~ 

Fuse

 
 
 
 
 

6,0 
8,0 

5 x 1,5 
5 x 2,5 

3 x 10 
3 x 16 

4 x 2,5 

4 x 6 

3 x 16 
3 x 25 

3 x 6 
3 x 6 

35 
35 

 

Table 2  Connection cable and fuses 

 

 

 

3.5. Electric heating toggle 

 

The electric heating toggle applies to homes with an electric heating system. 
Sauna heater has a connection (marked 55) for controlling the electric heating toggle. Connector 55 and the heating elements 
are simultaneously live (230V). 

 

 

 

 

 

 

Installation and User Manual Helo Ring 

Summary of Contents for Ring1118-600-0405

Page 1: ...ELECTRIC SAUNA HEATER 1118 600 0405 1118 900 0405 CONTROL PANELS 1601 12 RA 12 Digi II 1601 13 RA 13 Digi I 1601 16 RA 16 Easy 1601 18 RA 18 Midi 314 SKLT A Installation and User Manual Helo Ring...

Page 2: ...lation 6 3 3 Sauna heater safety clearances 7 3 4 Connection of the sauna heater to the mains 8 3 5 Electric heating toggle 8 3 6 Locating the connecting box for the connection cable in the sauna room...

Page 3: ...ocated on the side of the sign at the bottom of the sauna heater The sign shows the position of the switch 0 I Refer to the specific control panel operating instructions 2 Information for users Person...

Page 4: ...lve DO NOT ISTALL INLET VALVE WITHIN ZONE C IF THE SAUNA HEATER S CONTROL THERMOSTAT IS LOCATED IN THE SAME ZONE 2 3 Heating the sauna Before turning the sauna heater on make sure the sauna room is su...

Page 5: ...east once a year and replace small and broken stones with new larger stones Stones are piled so that they cover the heating elements Do not however pile a large heap of stones on the heating elements...

Page 6: ...an be considered as a maintenance area 3 2 Installation Follow the safety clearance specifications on page 7 when installing the sauna heater The sauna heater is a floor standing model The base must b...

Page 7: ...al Helo Ring 7 Absolute measurement 1900 60 mm mm 60 770 60 60 40 OLET 19 425 mm 800 OLET 19 Heater s leg Metal fastener Adjustable leg Floor fastener Corner and wall installation The sensor is placed...

Page 8: ...x is located at over 500mm distance from the heater the maximum height is 1000mm from the floor Sauna heater insulation resistance The sauna heater heating elements may absorb moisture from air e g du...

Page 9: ...cation for the connecting box 2 Silumin box recommended in this area 3 This area should be avoided Always use a silumin box In other areas use a heat resisting box T 125 C and heat resisting cables T...

Page 10: ...ul Yellow Gelb A5 Harm Gr Grey Grau B1 Rosa Ljusr d Pink Rose B2 Sin Bl Blue Blau B3 Pun R d Red Rot B4 Musta Svart Black Schwarz B5 Violetti Violett Violet Violett OLET 19 1 Blue 2 White 3 Red 4 Yell...

Page 11: ...chting Luz de sauna 3 Tuuletin Fl kt Ventilator Fan Ventilation Ventilator Ventilaci n 4 S hk l mmityksen vuorottelu Alternering med elv rme Signal kontakt Signal contact Contact du signal Signaalcont...

Page 12: ...v nda utsliten utrustning bidrar du till att skydda v r milj Produkten returneras till tervinningscentralen utan bastusten och eventuell t ljstensmantel V nligen kontakta de kommunala myndigheterna f...

Reviews: