SR250HL Series - 250 W Power Supply/Float Charger for Lead Acid Ba$eries 

The user is responsible for ensuring that input and output wiring segregation complies with local standards and that in the use of the equipment, 
access is confined to operators and service personnel.   A low resistance earth connection is essential to ensure safety and additionally, satisfactory 
EMI suppression (see below).

 

 

HAZARDOUS VOLTAGES EXIST WITHIN A POWER SUPPLY ENCLOSURE AND ANY REPAIRS MUST BE CARRIED OUT BY A 

QUALIFIED SERVICEPERSON.

 

  

 

Electrical Strength Tests

 

Components within the power supply responsible for providing the safety barrier between input and output are constructed to provide electrical 
isolation as required by the relevant standard. However EMI filtering components could be damaged as result of excessively long high voltage tests 
between input, output and ground. Please contact our technicians for advice regarding electric strength tests. 
  

Earth Leakage

 

Where fitted, EMC suppression circuits cause earth leakage currents which may be to a maximum of 3.5mA.  
  

Ventilation 

 

High operating temperature is a major cause of power supply failures, for example, a 10

o

C rise in the operating temperature of a component will 

halve its expected life.   Therefore always ensure that there is adequate ventilation for the equipment.   Batteries in particular suffer shortened 
lifetimes if subjected to high ambient temperatures. 
  

Water / Dust 

 

Every effort must be made in the installation to minimise the risk of ingress of water or dust. Water will almost always cause instant failure.   The 
effects of dust are slower in causing failure of electronic equipment but all electrical equipment should be cleaned free of any dust accumulation at 
regular intervals. 
  

Electromagnetic Interference (EMI)

 

Switching power supplies and converters inherently generate electrical noise.  All wiring should be as short as practicable and segregated from all 
equipment wiring which is sensitive to EMI.   Residual noise can be reduced by looping DC wiring through ferrite cores (sleeves). These are most 
effective as close to the power supply as possible and as many turns of the wire taken through the core (+ and - in the same direction) as the core 
will accommodate.  
  

External fuse protection 

Fuses or circuit breakers must be used in all battery circuits to protect against short circuits.   External fuses should  be used for power supplies/ 
chargers even though they are usually internally protected. 
  

Connection polarity 

It is critical to check the polarity carefully when connecting DC devices even with models which have non-destructive reverse polarity protection

1. SAFETY 

PSU 

= power supply unit 

BCT

 = baDery condiEon test 

ECB

 = electronic circuit breaker 

ELVD

 = electronic low voltage disconnect 

RPP

 = reverse polarity protecEon 

EMI

 = electromagneEc interference 

Glossary of terms used in our user manuals 

SNMP

 = Simple Network Management  

Protocol   

EMC

 = ElectromagneEc compaEbility 

DOD

 = depth of discharge 

Summary of Contents for SR250HL

Page 1: ...TURES STANDARD FEATURES 3 Relay Alarms Form C Float Charger Lead Acid Ba eries Temperature Sensor on 1 7m lead with adhesive pad 4mV C cell 10 Comms RS232 RS485 Modbus SNMP Webpages Customizable Digit...

Page 2: ...2 www heliosps com...

Page 3: ...ENCE Table of Contents 1 SAFETY 4 2 INTRODUCTION 5 3 FRONT PANEL LAYOUT 5 4 FG Frame Ground 5 5 N 1 REDUNDANCY 6 6 MODEL CODING OPTIONS 6 7 CONNECTION NOTES 6 8 TECHNICAL SPECIFICATIONS 7 9 PHYSICAL 7...

Page 4: ...imes if subjected to high ambient temperatures Water Dust Every effort must be made in the installation to minimise the risk of ingress of water or dust Water will almost always cause instant failure...

Page 5: ...on mains failure PSU fails DC Low DC Output Low or BaDery voltage low if used as a charger 4 DC CONNECTIONS 5 LED indicaEons Code DC OK Power OK and Standby 6 COOMS PORT RS232 ASCII RS485 ASCII Modbus...

Page 6: ...uts connected in parallel internally are provided If used as a baDery charger ensure that the baDery polarity matches the power supply output Alarms can be tested by using an external variable voltage...

Page 7: ...tural convecEon except for 12V LED IndicaEon Green DC OK Green Power OK Red Standby Alarm Relays Form C contacts changeover rated 30VDC 2A 110VDC 0 3A 125VAC 0 5A DC High POWER mains fail PSU fail DC...

Page 8: ...8 www heliosps com SR250HL Series 250 W Power Supply Float Charger for Lead Acid Ba eries 11 MOUNTING DETAILS...

Page 9: ...9 www heliosps com SR250HL Series 250 W Power Supply Float Charger for Lead Acid Ba eries...

Page 10: ...ow temp compensation output voltage reduction at over temperature Helios Power SoluEons warrants this product for 24 months from date of shipment against material and workmanship defects Liabil ity un...

Reviews: