background image

8

 

 

www.heliosps.com

 

SR100Hi Series 

-

 100 W DC UPS

 

8. SR100Hi–

  

DC SETTINGS 

 

Parameter

 

Default Settings

 

Actual settings if different from default

 

V nominal

 

12

 

24

 

30

 

36

 

48

 

 

 

 

 

V output (20°C)

 

13.8

 

27.6

 

34.5

 

41.4

 

55.2

 

 

 

 

 

BatDetect (mins)

 

60

 

60

 

60

 

60

 

60

 

 

 

 

 

Vpres:

 

12.2

 

24.4

 

30.5

 

36.6

 

48.8

 

 

 

 

 

Vbatl:

 

11

 

22

 

27.5

 

33

 

44

 

 

 

 

 

Vshutd:

 

11.5

 

23

 

28.7

 

34.5

 

46

 

 

 

 

 

Vdisco:

 

10

 

20

 

25

 

30

 

40

 

 

 

 

 

Bccl (%)

 

100

 

100

 

100

 

100

 

100

 

 

 

 

 

Comms

 

M

 

M

 

M

 

M

 

M

 

 

 

 

 

BCTim (mins)

 

20

 

20

 

20

 

20

 

20

 

 

 

 

 

CC Mins:

 

40

 

40

 

40

 

40

 

40

 

 

 

 

 

CC Hrs:

 

23

 

23

 

23

 

23

 

23

 

 

 

 

 

CC Days:

 

27

 

27

 

27

 

27

 

27

 

 

 

 

 

MfiBCT:

 

30

 

30

 

30

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BatDetect: 

 

Time between battery detections

 

Vpres: 

 

Voltage threshold for battery detection and BCT. Note that if the voltage drops to this level dur-
ing a BCT the test is aborted and the 

BAT LOW

 alarm shows.

 

Vshutd: 

 

Internal voltage level of the power supply during battery detection and battery condition tests. 

 

Vbatl:

 

BAT LOW

 alarm voltage level

 

Vdisco:

 

Voltage at which the load is disconnected from the battery during mains fail

 

Bccl:

 

Battery charge current limit as percentage of the rated power supply current

 

Comms

 

Communication mode of PSU:  F = continuous data stream of status

 

BCTim:

 

Length of battery condition test

 

CC Mins:

 

Time in minutes between  automatically scheduled BCTs

 

CC Hrs:

 

Time in hours between  automatically scheduled BCTs

 

CC Days:

 

Time in days between  automatically scheduled BCTs

 

Note: 

The total time interval between battery condition tests (BCTs) is the sum total of the three 'CC' settings

 

MFiBCT:

 

Time in minutes before the mains fail check during the BCT (only applicable to SR100)

 

Scheduled BCT

 

disabled

   

 

 

 

 

 

 

 

SNMP VERSIONS ONLY:

 

Alarm mask

 

1048187

   

 

 

 

 

 

 

 

DHCP

 

enabled

   

 

 

 

 

 

 

 

Summary of Contents for SR100Hi Series

Page 1: ...rm C Float Charger Lead Acid Batteries ELVD Electronic low voltage disconnect Temperature Sensor on 1 7m lead with adhesive pad 4mV C cell 10 N 1 Redundancy Comms RS232 RS485 Modbus SNMP Webpages Cust...

Page 2: ...2 www heliosps com...

Page 3: ...BLOCK DIAGRAM 5 4 OPERATION OF ELECTRONIC CIRCUIT BREAKER ECB FOR PROTECTION OF BATTERY CIRCUIT BATTERY 5 5 FRONT PANEL LAYOUT 6 6 CONNECTION AND INITIAL TESTING 7 7 LED INDICATION 7 8 SR100Hi DC SET...

Page 4: ...h ambient temperatures Water Dust Every effort must be made in the installation to minimise the risk of ingress of water or dust Water will almost always cause instant failure The effects of dust are...

Page 5: ...together when there is no input power Max allowable load amps x I rated 8 7 2 5 2ms 300ms Time ECB automatically resets IPSU 1x I rated 7x I rated for 300ms max 2 5 x I rated until battery fully dis...

Page 6: ...r present Battery Missing or fault in battery circuit wiring alarm does not activate for up to battery detection interval time BCT fail 4 LOAD BATTERY CONNECTION 5 LED indications Batt OK and Power OK...

Page 7: ...the B and B terminals 8 Turn on ac power 9 After the batteries are fully charged check that the battery continues to power up the load when the input power is turned off Power OK LED Battery OK LED P...

Page 8: ...AT LOW alarm shows Vshutd Internal voltage level of the power supply during battery detection and battery condition tests Vbatl BAT LOW alarm voltage level Vdisco Voltage at which the load is disconne...

Page 9: ...B is one stud labelled COMMON Alarms Available Input Fail YES Battery Missing YES Battery Low YES Battery Condition Test Fail YES ALARMS ECB LVD INPUT L B L SRxxx Hi B LOAD Peak load connection using...

Page 10: ...B BATT2 1 interlock circuit required for automated BCT use SR100 Hi chargers 10 MODEL CODING AND OPTIONS T Yes Blank No Temperature Compensation 12 24 30 36 48V DC output nominal battery voltage Funct...

Page 11: ...esive pad 4mV C cell 10 Battery Charge Current Limit Customizable on request Reverse Polarity Battery reverse connection will open internal fuse and produce alarm Battery Monitoring Detects for presen...

Page 12: ...arrants this product for 24 months from date of shipment against material and workmanship defects Liabil ity under this warranty is limited to the replacement or repair of the defective product as lon...

Reviews: