8
www.heliosps.com
SR100Hi Series
-
100 W DC UPS
8. SR100Hi–
DC SETTINGS
Parameter
Default Settings
Actual settings if different from default
V nominal
12
24
30
36
48
V output (20°C)
13.8
27.6
34.5
41.4
55.2
BatDetect (mins)
60
60
60
60
60
Vpres:
12.2
24.4
30.5
36.6
48.8
Vbatl:
11
22
27.5
33
44
Vshutd:
11.5
23
28.7
34.5
46
Vdisco:
10
20
25
30
40
Bccl (%)
100
100
100
100
100
Comms
M
M
M
M
M
BCTim (mins)
20
20
20
20
20
CC Mins:
40
40
40
40
40
CC Hrs:
23
23
23
23
23
CC Days:
27
27
27
27
27
MfiBCT:
30
30
30
30
30
BatDetect:
Time between battery detections
Vpres:
Voltage threshold for battery detection and BCT. Note that if the voltage drops to this level dur-
ing a BCT the test is aborted and the
BAT LOW
alarm shows.
Vshutd:
Internal voltage level of the power supply during battery detection and battery condition tests.
Vbatl:
BAT LOW
alarm voltage level
Vdisco:
Voltage at which the load is disconnected from the battery during mains fail
Bccl:
Battery charge current limit as percentage of the rated power supply current
Comms
Communication mode of PSU: F = continuous data stream of status
BCTim:
Length of battery condition test
CC Mins:
Time in minutes between automatically scheduled BCTs
CC Hrs:
Time in hours between automatically scheduled BCTs
CC Days:
Time in days between automatically scheduled BCTs
Note:
The total time interval between battery condition tests (BCTs) is the sum total of the three 'CC' settings
MFiBCT:
Time in minutes before the mains fail check during the BCT (only applicable to SR100)
Scheduled BCT
disabled
SNMP VERSIONS ONLY:
Alarm mask
1048187
DHCP
enabled