Slide switch controller
KWL-BE
Operating instructions
3
EN
2.2 Evaluation of faults
A fault indicator (information or error message) from the unit is displayed through the
integrated LED on the controller (see Fig.1,
ä
). The fault indicators >
Info
< and >
Error
<
are displayed by differently coloured LEDs:
LED >>
Info
= Green
LED >>
Error
= Yellow
Information and error messages can be evaluated via the flash code and the fault over-
view (see section 2.3. fault overview).
The following information and error messages are defined:
In relation to flash code, the LED flashes 32 times in quick succession (approx. 100
msec). There is a 4 second pause after each cycle (32 flashes). A total of 32 possible
errors can be represented. The error to be displayed is represented in the cycle by longer
flashes (approx. 500 msec).
Fault example for >Error< 2 and 9:
Reset function
(error messages, information messages, warnings)
The controller can be RESET via the slide switch. For this purpose, quickly switch
through the 3 operating stages via the slide switch settings 1-2-3-2-1, starting with
operating stage 1, in one sequence within one second.
100 msec
1 no error
100 msec
Pause
500 msec
2 error
100 msec
Pause
100 msec
3 no error
100 msec
Pause
100 msec
4 no error
100 msec
Pause
100 msec
5 no error
100 msec
Pause
100 msec
6 no error
100 msec
Pause
100 msec
7 no error
100 msec
Pause
100 msec
t
8 no error
100 msec
Pause
500 msec
9 error
100 msec
Pause
100 msec
10 no error
100 msec
Pause
100 msec
11 no error
100 msec
Pause
100 msec
12 no error
100 msec
Pause
100 msec
13 no error
100 msec
Pause
100 msec
14 no error
100 msec
Pause
100 msec
100 msec
100 msec
32 no error
100 msec
Pause
.....