Soffit element installation package –
KWL 45-160 LE-RP
Installation and Operating Instructions
5
4 .1 Installation preparation
– WALL INSTALLATION SLEEVE
ò
Length of wall installation sleeve
Min.: 300 mm
Max.: 500 mm
The length of the wall installation sleeve
ò
comprises the thickness of the unco-
vered wall with internal finished plaster
and the insertion depth in the soffit chan-
nel
ù
(see Fig. 4).
The length of the wall installation sleeve
should be adjusted so that there are no
collisions in the area of the shutter rail.
Observe installation instructions for
shutters and blinds! The shutter rail,
or the like, must pass by the soffit
grille .
It may be necessary to underlay
the soffit channel on site, if required .
ù
Insertion depth of the wall installa-
tion sleeve in the soffit channel
Length: 20 mm
The wall installation sleeve must have
an overhang of 20 mm to the unfinished
wall. This serves as a connection for the
soffit channel.
The wall installation sleeve must not be
cut flush with the wall on the external
side of the wall!
Wall thickness of unfinished wall:
Min.: 280 mm
Max.: 480 mm
– SOFFIT CHANNEL
ä
Clearance from core hole (centre)
to soffit channel connection
Min.: 200 mm
Max.: 480 mm
The shortenable areas of the soffit
channel
ä
and the plaster frame
ë
are
shown in Fig. 4.
ë
Height of plaster frame
Min.: 15 mm
Max.: 35 mm
The plaster frame height bridges the
clearance between the soffit channel
and soffit grille. The height should be
selected depending on the thickness of
the insulation of the window soffit and
finished plaster. The plaster frame allows
tolerance compensation.
A minimum height of 20 mm is recom-
mended for the plaster frame.
ö
Insulation thickness
The soffit channel must be over-insu-
lated . It is not suitable for insulation
thicknesses
≤
100 mm and must not
be installed in this case .
EN
A
A
Dämmstärke
15 - 35
(Kürzbarer Bereich Putzrahmen)
200 - 480
74
Rohb Fertigputz
min. 280
Wandeinbauhülse
( min. 300 )
Laibungskanal
100
120
18
200
0 - 280
(Kürzbarer Bereich Laibungskanal)
20
+
5
0
SCHNITT A-A
Dämmung
Überdämmung
Fertigputz
Laibungskanal
Putzrahmen
Laibungsgitter mit
Kondensatablaufblech
Dämmung
Fensterlaibung
Fertigputz
Fenster
Fertigputz
ä
ò
ù
ë
Fig .4
All dimensions in mm
ö
Uncovered wall + finished plaster
Insulation thickness
Finished plaster
Insulation
Finished plaster
Over
-insulation
Soffit channel
Wall installation sleeve
Soffit channel
W
indow
Finished plaster
Insulation
W
indow soffit
Plaster frame
Soffit grille with
condensate discharge plate
(Shortenable ar
ea of plaster frame)
(Shortenable ar
ea of soffit channel)