Central ventilation unit –
KWL 170 W/W ET
Installation and Operating Instructions
EN
EN
14
4.3 Install ball siphon
During heating periods, condensate may form in the heat exchanger due to the heat recovery process. The condensa-
te must be able to drain freely from the unit. The provided ball siphon (scope of delivery) must be installed in the base
tray of the unit for this purpose.
1. Open ball siphon. Turn the mounting part a 1/4 turn (see Fig. 16).
2. Plug the mounting part in the condensate outlet from below, until the claw fasteners snap to the sheet edge of the
3. Insert locking part and insert up to stop (see Fig. 18).
4. Then insert the condensate hose (DN 12 mm; not included in delivery) in the hose connector on the siphon casing
and tighten by hand (see Fig. 19).
5. Connect siphon casing and turn a 1/4 turn in the mounting part (see Fig. 20). Ensure that the float ball is loose in
the casing!
Water damage in the unit due to condensation.
A closed discharge can lead to pressure conditions which prevent controlled drainage from the unit. Furthermo-
re, gases may escape from the drainage line into the unit, which may create a breeding ground for microorga-
nisms in combination with moisture.
> The condensate hose must end 20 mm above the open drain or possible water level (see Fig. 21).
> The condensate hose from the ball siphon must have a downward gradient, openly dripping into a funnel
siphon and must not be discharged into a closed system (see Fig. 21).
Mounting part with
seal elements
Locking part
Float ball
Siphon casing
Hose connector
Fig. 16
View below
View above
Fig. 17
Fig. 18
Fig. 19
ATTENTION
Connect siphon
casing
Fig. 20
1/4 turn
20
Trichter-
siphon
ø12, Schlauch
max.1,5m lang,
Gefälle beachten
Fig. 21
Funnel
siphon
ø12, hose
max. 1.5m long
Note gradient
Summary of Contents for KWL 170 W
Page 33: ...Zentrales Lüftungsgerät KWL 170 W W ET Montage und Betriebsvorschrift DE 32 ...
Page 65: ...Central ventilation unit KWL 170 W W ET Installation and Operating Instructions EN 32 ...
Page 97: ...Unité de ventilation centrale KWL 170 W W ET Notice de montage et d utilisation FR 32 ...
Page 98: ...Unité de ventilation centrale KWL 170 W W ET Notice de montage et d utilisation FR 33 ...
Page 99: ...Unité de ventilation centrale KWL 170 W W ET Notice de montage et d utilisation FR 34 ...