5

Centrifugal fans – GigaBox GBW EC.. / GBD EC.. 

Installation and Operating Instructions 

 EN

2.3  Dimensions Connecting flange (outlet adapter)

  C 

 B 

  A 

 

 D 

 F 

 G 

Dimensions in mm

  GBW EC 250  

352  339  310 

6,5 

 -  

 GBW 

EC 

315 

355  452 439 410 330 6,5 439

  GBW EC 400 / 450   622  609  580  500  6,5       609     500
  GBW EC 500 / 560 

718  698  678  620 

8        698        -

 

Type 

A B 

C  D 

Ø E        F        G

  GBW EC 630 / 710   938  918  898  840 

8      918

  C 

  A 

 D 

 F 

 

 B 

GBW EC 250-450

GBW EC 500-710

Fig.6

Dimensions in mm

Fig.7

CHAPTER 3 

ASSEMBLY/
INSTALLATION

2.4  Functional description

 

The  GigaBox GB EC.. fans are steplessly speed-controllable by means of 0-10 V control voltage. Suitable  

 

potentiometers (Type PU/A 10), three-step switches (Type SU/A) are offered in the Helios accessories range.  

 

Stepless speed control is possible with the universal controller (Type EUR EC). Alternatively, the electronic differential  

 

pressure/temperature controller EDR / ETR can be used.

 

Activation / deactivation:

EC fans can be frequently activated and deactivated via the 0-10 V control input or the release input
depending on the type. This is gentle on the electronics and ensures a long service life. Control via the power 
supply (on/off) is not recommended. In general, there must be an interval of at least 120 seconds between 
activation and deactivation.

 

In case of strong vibrations and/or odours, maintenance must be carried out by a specialist according to

 

 

chapter 1.4.

3.0  – Assembly

The EC-GigaBox model range allows a flexible 
assembly (installation position horizontal or verti-
cal) by five possible axial and centrifugal dischar-
ge directions of the outlet adapter (see Fig.8).
Please pay attention to a secure, durable moun-
ting of the unit as well as a free access to the 
terminal box and the motor impeller unity on the 
rear of the unit. Easy positioning is made using 
integrated crane hooks. Removable panels allow 
an easy inspection access. 

To prevent vibration transmission to buildings 
and ducting systems use flexible connectors  
GB-FM..(included in delivery) between EC-fan box and connecting ducting.

- With regard to duct installation, it must be ensured that there is a sufficiently long straight section of ducting
   (2x duct diameter) before and after the unit, as otherwise there may be a loss of performance and higher  
   sound levels.
- The GigaBox must be assembled so that it is freely accessible for maintenance work.
- The installation must be carried out with condensation drainage showing downward (see Fig. 9)!
- The side panels can be removed for cleaning.

 

 

NOTE

 

Fig.8

Radial lateral discharge

Radial on both 

sides, 

free discharge

Axial discharge

Summary of Contents for GBD EC 450

Page 1: ...tilatoren MONTAGE UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS NOTICE DE MONTAGE ET D UTILISATION EC Radialventilatoren EC Centrifugal fans Caissons centrifuges EC GigaBox GBW EC GBD EC DE EN FR ...

Page 2: ...gsregelung Seite 2 1 17 Motorschutzeinrichtung Seite 3 KAPITEL 2 LIEFERUMFANG UND ZUBEHÖR Seite 4 2 0 Lieferumfang Seite 4 2 1 Zubehör Seite 4 2 2 Abmessungen Gerät Seite 4 2 3 Abmessungen Anschlussflansch Austritts Formstück Seite 5 2 4 Funktionsbeschreibung Seite 5 KAPITEL 3 AUFSTELLUNG MONTAGE Seite 5 3 0 Aufstellung Seite 5 3 1 Montage Seite 6 3 2 Demontage Seite 6 3 3 Elektrischer Anschluss S...

Page 3: ... und Feuch tigkeitsindikatoren Der Lagerort muss erschütterungsfrei wassergeschützt und frei von übermäßigen Temperatur schwankungen sein Bei mehrjähriger Lagerung bzw Motorstillstand muss vor Inbetriebnahme eine Inspektion der Lager und gegebenen falls ein Lageraustausch durchgeführt werden Zusätzlich ist eine elektrische Prüfung nach VDE 0701 bzw VDE 0530 durchzuführen Bei Weiterversand vor alle...

Page 4: ...men Der serienmäßige Klemmenkasten befindet sich auf der Motorträgerplatte bzw am Motor 1 14 Berührungsschutz m Bei Einbau sind die gültigen Arbeitsschutz und Un fall verhütungsvorschriften zu beachten Ein Be rüh rungs schutz gemäß DIN EN ISO 13857 ist sicherzustellen Kontakt mit rotierenden Teilen muss verhindert werden Es ist si cher zu stellen dass sich im Ansaug bereich keine Tex tilien oder a...

Page 5: ... des Betriebs sowie ein Kurzschluss im Motor kann es zu einem Über stromfehler kommen Der Motor wird abgeschaltet Der Fehler wird über das Störmelderelais nach 10 s angezeigt Der Wiederanlauf des Ventilators ist nur über das Abschalten der Netzspannung für min 30 s möglich Netzunterspannung Fällt die Netzeingangsspannung 20 unter die jeweils spezifizierte Netzspannung wird der Motor abgeschaltet D...

Page 6: ...EC 500 A B 800 800 500 250 GBD EC 560 800 800 560 250 GBD EC 630 1020 1020 630 250 Maße in mm Die Zubehörtteile sind in unterschiedlichen Größen und Ausführungen erhältlich Die entsprechende Bestell Nr kann den Helios Verkaufsunterlagen entnommen werden Die zu den EC Baureihen zugehörigen Drehzahl Po tentiometer und das Universal Regelsystem EUR EC können aus dem aktuellen EC Katalog EC greenVent ...

Page 7: ...Type c A B c C D Ø E F G GBW EC 630 710 938 918 898 840 8 918 C B A E D F G Maße in mm C A D F E B GBW EC 250 450 GBW EC 500 710 Abb 6 Maße in mm Abb 7 3 0 Aufstellung Die GigaBox EC Baureihen ermöglichen eine flexi ble Aufstellung Einbaulage horizontal oder vertikal durch fünf mögliche axiale und radiale Ausblas richtungen des Austrittsformstücks siehe Abb 8 Auf eine sichere dauerhafte Befestigun...

Page 8: ... Folgende Kontrollarbeiten sind auszuführen Bestimmungsgemäßen Einsatz des Ventilators über prüfen Die Baureihen dürfen nicht in explosionsgefährdeten Bereich betrieben werden Vor allen Wartungs und Installationsarbeiten oder vor Öffnen des Revisionsraumes ist das Gerät allpolig vom Netz zu trennen Der elektrische Anschluss darf nur von einer autorisierten Elektrofachkraft entspre chend den nachst...

Page 9: ...ngsentkopplung zu anderen Bauteilen Gebäudeteilen haben Vibrationen und Schwingungen können verursacht werden durch ein unwuchtiges u U mit Schmutz beaufschlag tes Laufrad mangelhafte Entkopplung zum Rohrsystem oder Gebäudeteilen Stark geminderte Luftleistung kann auftreten bei falscher Drehrichtung wenn die sich einstellenden Rohrleitungs und Bauteil wider stände Gitter Klappen Filter usw höher a...

Page 10: ... 8 Radialventilatoren GigaBox GBW EC GBD EC Montage und Betriebsvorschrift SS 976 GBD EC 450 500 A B 560 630 710 A B Drehstrom 3 400 V SS 973 GBW EC 250 GBW EC 315 GBW EC 355 GBW EC 400 A GBW EC 400 B GBW EC 450 Wechselstrom 1 230 V ...

Page 11: ...7 2 Anschlusspläne mit PU A und EUR EC 9 Radialventilatoren GigaBox GBW EC GBD EC Montage und Betriebsvorschrift SS 974 SS 975 DE ...

Page 12: ...10 Radialventilatoren GigaBox GBW EC GBD EC Montage und Betriebsvorschrift SS 977 SS 978 DE ...

Page 13: ...11 Radialventilatoren GigaBox GBW EC GBD EC Montage und Betriebsvorschrift SS 1035 DE ...

Page 14: ...ed control Page 2 1 17 Motor protection Page 3 CHAPTER 2 SCOPE OF DELIVERY AND ACCESSORIES Page 4 2 0 Scope of delivery Page 4 2 1 Accessories Page 4 2 2 Dimensions Unit Page 4 2 3 Dimensions Connecting flange outlet adapter Page 5 2 4 Functional description Page 5 CHAPTER 3 ASSEMBLY INSTALLATION Page 5 3 0 Assembly Page 5 3 1 Installation Page 6 3 2 Dismantling Page 6 3 3 Electrical connection Pa...

Page 15: ...ion of motor by dry air dustproof packing plastic bags with drying agent and moisture indicators The storage place must be water proof vibration free and free of temperature variations When storing for several years or non rotation of motor an inspection of the bearings with possible relubrication and an electrical inspection to VDE 0701 and VDE 0530 are absolutely necessary before starting operat...

Page 16: ... 1 is mandatory The rated voltage and frequency must be consistent with the information on the type plate The standard terminal box is located on the motor mounting plate or on the motor 1 14 Protection against accidental contact m When installing observe the valid regulations for labour protection and accident prevention A protection against accidental contact according to DIN EN ISO 13857 is to ...

Page 17: ...blocking of the impeller during the operation as well as a short circuit in the motor an overcurrent error may occur The motor is switched off The error is displayed over the fail safe relay after 10 seconds The restart of the fan is possible only over switching the mains voltage off for min 30 s Mains undervoltage If the mains input voltage falls 20 under the mains voltage specified in each case ...

Page 18: ...r louvres GB WSG accessories ö Outdoor cover hood GB WSD accessories ü Anti vibration mounts SDD U accessories Å Wall bracket GB WK accessories î Condensate collector with central outlet nozzle GB RA accessories Fig 4 GBD EC 710 A B 1020 1020 710 250 GBW EC 250 400 400 250 150 GBW EC 315 500 500 315 150 GBW EC 355 500 500 355 150 GBW EC 400 A B 670 670 400 250 Type c A A Ø B C GBW EC 450 670 670 4...

Page 19: ...must be an interval of at least 120 seconds between activation and deactivation m In case of strong vibrations and or odours maintenance must be carried out by a specialist according to chapter 1 4 3 0 Assembly The EC GigaBox model range allows a flexible assembly installation position horizontal or verti cal by five possible axial and centrifugal dischar ge directions of the outlet adapter see Fi...

Page 20: ...rear side 3 3 Electrical connection The following checks are to be carried out Check the intended purpose of the fan The series must not be operated in potentially hazardous atmospheres All maintenance and installation work must be carried out with the equipment fully isolated from the power supply The electrical connection is to be carried out in accordance with the relevant wiring diagram and is...

Page 21: ...o high Abnormal noises can be caused by incorrect direction of rotation worn out ball bearings lack of vibration decoupling to other buildings and ducting systems Vibrations and oscillation can be caused by unbalanced or dirty impellers lack of vibration decoupling to other buildings and ducting systems Extreme reductions in performance can occur in case of incorrect direction of rotation if resis...

Page 22: ...stallation and Operating Instructions 7 1 Standard wiring diagram SS 976 GBD EC 450 500 A B 560 630 710 A B rotary current 3 400 V SS 973 GBW EC 250 GBW EC 315 GBW EC 355 GBW EC 400 A GBW EC 400 B GBW EC 450 Alternating current 1 230 V Terminal box ...

Page 23: ...l fans GigaBox GBW EC GBD EC Installation and Operating Instructions EN 7 2 Wiring diagram with PU A and EUR EC SS 974 SS 975 Terminal box Example EUR EC control EC Motor SS 973 with modus 4 01 pressure controlled ...

Page 24: ...10 Centrifugal fans GigaBox GBW EC GBD EC Installation and Operating Instructions SS 977 SS 978 Example EUR EC control EC Motor SS 976 with modus 4 01 pressure controlled EN ...

Page 25: ...11 Centrifugal fans GigaBox GBW EC GBD EC Installation and Operating Instructions SS 1035 EN ...

Page 26: ...1 17 Protection moteur Page 3 CHAPITRE 2 CONTENU DE LA LIVRAISON ET ACCESSOIRES Page 4 2 0 Contenu de la livraison Page 4 2 1 Accessoires Page 4 2 2 Dimensions Page 4 2 3 Dimensions des pièces de raccordement Page 5 2 4 Description des fonctionnalités Page 5 CHAPITRE 3 INSTALLATION MONTAGE Page 5 3 0 Installation Page 5 3 1 Montage Page 6 3 2 Démontage Page 6 3 3 Raccordement électrique Page 6 CHA...

Page 27: ...à l air et la poussière sac en matière synthétique contenant des sachets deshydrateurs et un indicateur d humidité Le matériel est à stocker dans un endroit abrité de l eau exempt de variations de températures et de vibrations En cas de stockage sur plusieurs années entraînant une immobilisation du moteur il faut effectuer un contrôle des roulements et éventuellement les changer avant la mise en s...

Page 28: ...e aux indi cations de l étiquette La boîte à bornes livrée de série se trouve sur la plaque support moteur ou directement sur le moteur 1 14 Protections m Lors de l installation respecter les instructions en vigueur relatives au Code du Travail et à la prévention des accidents Il faut prévoir toutes les protections nécessaires conformément à la norme DIN EN ISO 13857 Toute possibilité de contact a...

Page 29: ...du rotor pendant son fonctionnement ou un court circuit dans le moteur peuvent entraîner une surintensité Le moteur se coupe La défaillance sera signalée au relais de signalement des défauts après 10 secondes Le redémarrage du ventilateur n est possible qu après une coupure de la tension du secteur d une durée minimum de 30 secondes Sous tension du réseau Si la tension du réseau tombe 20 en dessou...

Page 30: ... antivibratoires SDD U acc Å Console murale GB WK acc î Bac de récupération des condensats avec écoulement central GB RA acc Fig 4 GBD EC 710 A B 1020 1020 710 250 GBW EC 250 400 400 250 150 GBW EC 315 500 500 315 150 GBW EC 355 500 500 355 150 GBW EC 400 A B 670 670 400 250 Type c A A Ø B C GBW EC 450 670 670 450 250 GBD EC 450 670 670 450 250 GBD EC 500 A B 800 800 500 250 GBD EC 560 800 800 560...

Page 31: ...ores procéder à une maintenance selon les consignes de la section 1 4 3 0 Installation Les séries GigaBox EC permettent de nombreuses possibilités d installation et de montage horizon tale et verticale grâce aux cinq emplacements possibles de la pièce de transformation voir fig 8 Veiller à fixer l appareil de façon solide et durable et garantir un accès aisé à la boîte à bornes et à l unité moto t...

Page 32: ...res composants de l installation 3 3 Raccordement électrique Les vérifications suivantes sont à réaliser Vérifier que l utilisation du ventilateur est conforme à la prescription Cette gamme ne doit pas être utilisée dans des zones à risque d explosion Mettre impérativement l appareil hors tension avant tous travaux d entretien de réglages ou l ouverture de la trappe de visite Le branchement électr...

Page 33: ...Le ventilateur doit tourner de façon centrifuge à toutes les vitesses 5 0 Nettoyage et entretien Les travaux de maintenance et d entretien ne doivent être effectués que par des professionnels qualifiés et expérimentés et conformément aux dispositions et réglementations en vigueur m S assurer que l appareil est hors tension avant toute intervention et qu il est bloqué en position arrêt grâce à l in...

Page 34: ...nal 0 10 V SS 976 GBD EC 450 500 A B 560 630 710 A B Triphasé 3 400 V SS 973 GBW EC 250 GBW EC 315 GBW EC 355 GBW EC 400 A GBW EC 400 B GBW EC 450 Monophasé 1 230 V Code couleur selon CEI 757 BK noir BN marron RD rouge OG orange YE jaune GN vert BU bleu VI violet WH blanc Valable à partir des versions 5810 002 et 5811 002 Alimentation 1 6 mA max Alimentation 2 20 mA max Valeur de consigne ouvert q...

Page 35: ...uge OG orange YE jaune GN vert BU bleu VI violet WH blanc Exemple Régulateur EUR EC pour moteur EC SS 973 en mode 4 01 pression Signalisation Relais sonde Câbles de commande 30 m max à partir de 20 m blindés voir notice de montage et d utilisation Paramétrage EUR EC Entrée sonde E1 paramétrage usine mode 4 01 pression Sortie analogique A1 IO Setup Fonction A1 2A contrôle proportionnel Signalisatio...

Page 36: ...pour sélection sonde sonde Paramétrage EUR EC Entrée sonde E1 paramétrage usine mode 4 01 pression Sortie analogique A1 IO Setup Fonction A1 2A contrôle proportionnel Signalisation des défauts via entrée numérique D1 IO Setup Fonction D1 2D défaut externe D1 inversion enclenchée Autorisation via relais K1 IO Setup Fonction K1 1K message fonctionnement Sonde de pression N Réf 1322 Câbles de command...

Page 37: ...e charge potentiomètre charge tous les ventilateurs Principe de raccordement Commande de plusieurs ventilateurs EC avec PU PA sans LED Principe de raccordement Commande de plusieurs ventilateurs EC avec PU PA avec LED Ventilateur EC n 1 Ventilateur EC n 2 Ventilateur EC n 3 Ventilateur EC n 1 Ventilateur EC n 2 Ventilateur EC n 3 Attention Le branchement en parallèle de la tension 10 V DC n est pa...

Page 38: ...12 ...

Page 39: ...13 ...

Page 40: ...nstraße 4 8112 Otelfingen GB HELIOS Ventilation Systems Ltd 5 Crown Gate Wyncolls Road Severalls Industrial Park A HELIOS Ventilatoren Postfach 854 Siemensstraße 15 6023 Innsbruck Colchester Essex CO4 9HZ www heliosventilatoren de Als Referenz am Gerät griffbereit aufbewahren Druckschrift Nr Please keep this manual for reference with the unit Print No Conservez cette notice à proximité de l apapre...

Reviews: