Centrifugal fans – GigaBox GBW EC.. / GBD EC..
Installation and Operating Instructions
EN
2.3 Dimensions Connecting flange (outlet adapter)
C
B
A
E
D
F
G
Dimensions in mm
GBW EC 250
352 339 310
-
6,5
-
GBW
EC
315
/
355 452 439 410 330 6,5 439
GBW EC 400 / 450 622 609 580 500 6,5 609 500
GBW EC 500 / 560
718 698 678 620
8 698 -
Type
c
A B
c
C D
Ø E F G
GBW EC 630 / 710 938 918 898 840
8 918
C
A
D
F
E
B
GBW EC 250-450
GBW EC 500-710
Fig.6
Dimensions in mm
Fig.7
CHAPTER 3
ASSEMBLY/
INSTALLATION
2.4 Functional description
The GigaBox GB EC.. fans are steplessly speed-controllable by means of 0-10 V control voltage. Suitable
potentiometers (Type PU/A 10), three-step switches (Type SU/A) are offered in the Helios accessories range.
Stepless speed control is possible with the universal controller (Type EUR EC). Alternatively, the electronic differential
pressure/temperature controller EDR / ETR can be used.
m
Activation / deactivation:
EC fans can be frequently activated and deactivated via the 0-10 V control input or the release input
depending on the type. This is gentle on the electronics and ensures a long service life. Control via the power
supply (on/off) is not recommended. In general, there must be an interval of at least 120 seconds between
activation and deactivation.
m
In case of strong vibrations and/or odours, maintenance must be carried out by a specialist according to
chapter 1.4.
3.0 – Assembly
The EC-GigaBox model range allows a flexible
assembly (installation position horizontal or verti-
cal) by five possible axial and centrifugal dischar-
ge directions of the outlet adapter (see Fig.8).
Please pay attention to a secure, durable moun-
ting of the unit as well as a free access to the
terminal box and the motor impeller unity on the
rear of the unit. Easy positioning is made using
integrated crane hooks. Removable panels allow
an easy inspection access.
To prevent vibration transmission to buildings
and ducting systems use flexible connectors
GB-FM..(included in delivery) between EC-fan box and connecting ducting.
- With regard to duct installation, it must be ensured that there is a sufficiently long straight section of ducting
(2x duct diameter) before and after the unit, as otherwise there may be a loss of performance and higher
sound levels.
- The GigaBox must be assembled so that it is freely accessible for maintenance work.
- The installation must be carried out with condensation drainage showing downward (see Fig. 9)!
- The side panels can be removed for cleaning.
m
NOTE
Fig.8
Radial lateral discharge
Radial on both
sides,
free discharge
Axial discharge
Summary of Contents for GBD EC 450
Page 12: ...10 Radialventilatoren GigaBox GBW EC GBD EC Montage und Betriebsvorschrift SS 977 SS 978 DE ...
Page 13: ...11 Radialventilatoren GigaBox GBW EC GBD EC Montage und Betriebsvorschrift SS 1035 DE ...
Page 25: ...11 Centrifugal fans GigaBox GBW EC GBD EC Installation and Operating Instructions SS 1035 EN ...
Page 38: ...12 ...
Page 39: ...13 ...