Helios B AVD Series Installation And Operation Instructions Manual Download Page 32

2

B AVD.. and B VAR.. – Smoke Extraction Fans F300/F400/F600

Installation and Operating Instructions

Only transport smoke extraction fans using means of transport that are

appropriate for the weight, wear protective gloves during transport!

Observe attached transportation diagram!

Wear protective gloves/footwear when unpacking the unit.

Ensure the suitable load capacity and properties of the mounting surface

and use suitable mounting material.

The installation area must be designed so that people cannot be endange-

red by hot gases.

The outlet area of the fan and motor cooling system must be free of flamma

ble materials and it must not be accessible to persons.

It must be checked whether ear protection is necessary for the installation

situation.

The operator is responsible for observing all plant-related safety regulations!

Abnormally frequent activation/deactivation is not permissible.

Protection against contact for the impeller must be ensured pursuant to DIN

EN 13857.

It must be ensured that no water can get into the smoke extraction fan!

In order to maintain operational safety, a regular vibration check must be

carried out! Alternatively, the installation of an on-site vibration monitoring

system is recommended.

The information and permissible vibration limits according to ISO 14694

from the table on page 12, section 3.9 must be observed.

The planner and operator must ensure easy access for inspection and clea-

ning work!

A uniform inflow and free outlet must be ensured.

1.3

Area of application

– Normal use:

Operation within the characteristic curve of the respective unit (see catalogue). Vibrations and an increase in noise

generation indicate operation outside of the characteristic curve.

Ventilation mode:

Conveyance of normal or slightly dusty (particle size < 10 µm), less aggressive and humid air, in moderate climates at

temperatures in the range of -20 °C to +40 °C, with stationary installation of the fan.

Smoke extraction mode:

One-off conveyance of smoke type F300 - 300 °C, 2h; Type F400 - 400 °C, 2h; Type F600 - 600 °C, 2h tested ac-

cording to DIN EN 12101-3.

Type F600

with forced ventilation: For sufficient cooling air vent opening (max. 40 °C) and reliable discharging of out-

going air (max. 250 °C).

Installation:

In fire area, outside fire area, outdoors (protected from the elements) vertical and horizontal installation possible.

– Reasonably foreseeable misuse:

The fans are not suitable for operation under difficult conditions, such as high levels of humidity, aggressive media,

long standstill periods, heavy contamination, excessive loads due to climatic, technical or electronic influences. The

same applies for the mobile use of fans (vehicles, aircraft, ships, etc.).

– Improper, prohibited use:

Outdoor installation without effective weather protection or in direct contact with water. Conveyance of explosive gas

mixtures/media. Installation in an explosive area/atmosphere. Operation without standardised safety devices (e.g.

protective grille). Conveyance of solids or solid content > 10 µm in the conveyed medium and liquids. Conveyance

of abrasive and/or fan material-corrosive media. Conveyance of conveyed medium containing fat. Smoke extraction

with motor protection device or frequency converter.

EN 

Summary of Contents for B AVD Series

Page 1: ...Helios Brandgasventilatoren B AVD B VAR in Temperaturklassen F300 F400 F600 D Helios Ventilatoren MONTAGE UND BETRIEBSVORSCHRIFT NR 85573 B AVD...

Page 2: ...stigungsschrauben Seite 12 3 12 Elektrischer Anschluss Seite 13 3 13 Inbetriebnahme Seite 13 3 14 Betrieb Seite 13 KAPITEL 4 INSTANDHALTUNG UND WARTUNG Seite 14 4 0 Instandhaltung und Wartung Seite 14...

Page 3: ...etzungen sowie vor Ber hrung mit hei en Oberfl chen m Sicherheitsschuhe Sicherheitsschuhe dienen zum Schutz vor schweren herabfallenden Teilen und verhindern Ausrutschen auf rutschigem Untergrund Haar...

Page 4: ...z Betrieb innerhalb des Kennlinienfelds des jeweiligen Ger ts siehe Katalog Vibrationen und eine Zunahme der Ger uschentwicklung weisen auf einen Betrieb au erhalb des Kennlinienfeldes hin L ftungsbet...

Page 5: ...Textilien oder andere ansaugbare Stoffe wie z B auch Kleidung von Personen befinden In Abh ngigkeit der Einbauverh ltnisse kann ein Ber hrungsschutz erforderlich sein Entsprechende Schutzgitter sind a...

Page 6: ...tnehmen Ventilator nicht an Anschlussleitungen Klemmenkasten oder Laufrad transportieren Nicht unter der schwebenden Last aufhalten 2 3 Sendungsannahme Die Sendung ist sofort bei Anlieferung auf Besch...

Page 7: ...kapselt und zus tzliches Zuluft Gebl se erforderlich Baureihe B AVD 500 1250 F300 F400 Der Brandgas Axial Niederdruckventilator ist ein direktgetriebener Ventilator bei dem der Motor im Luftstrom sitz...

Page 8: ...er K hlluft in die Motorkapselung max 40 C Mindestk hlluft beachten Montagezubeh r Radial K hlluftgebl se Wetterschutzdach bauseitig Anschluss der Entrauchungsleitungen mit Montagezubeh r Segeltuchstu...

Page 9: ...s der Entrauchungsventilator mit ausreichend K hlluft versorgt wird Um Sch den am Entrauchungsventilator zu vermeiden muss dieser sofort abgeschaltet und eine St r meldung ausgegeben werden Entrauchun...

Page 10: ...raum IB ist der Klemmenkasten vom Geh use zu demontieren und au erhalb des Brandraums anzubringen siehe Abb 10 Hierbei ist die Anschlussleitung vom Klemmenkasten zum Antriebsmotor Leitungsl nge ist ba...

Page 11: ...n Type B KLG 500 Best Nr 2798 Schutzart IP44 Leistung 160 Watt Spannung 230 Volt max Umgebungstemperatur 40 C Frequenz 50 Hz Drehzahl 2400 1 min Strom 0 7 Amp Volumenstrom 500 m3 h Schaltplan SS 1018...

Page 12: ...rungsrohren verbun den Kein Montagering Vertikal m glich MRV Lieferumfang Verl ngerungsrohre 2 St inkl Montagesatz Sechskantschrauben muttern Federringe Parallel Einheit Montagepaket MP P Zwei paralle...

Page 13: ...0 3 0 B AVD 560 F300 4 6 B VAR 630 F300 3 0 B AVD 630 F300 5 2 B VAR 710 F300 3 5 B AVD 710 F300 5 7 B VAR 800 F300 4 0 B AVD 800 F300 5 8 B VAR 900 F300 4 5 B AVD 900 F300 6 9 B VAR 1000 F300 5 0 B A...

Page 14: ...inheit 1 Ermittlung der zu d mpfenden Masse B VAR 900 4 533 kg B VAR 900 4 533 kg MP Z 900 68 kg VR 900 34 kg MK 900 18 kg Gesamtgewicht 1186 kg 3 10 Schwerpunktlage Je nach Baugr e und Motorleistung...

Page 15: ...ung muss vor der Funktionspr fung entfernt werden Bestimmungsgem en Einsatz des Ventilators berpr fen Zul ssige F rdermitteltemperatur Netzspannung mit Leistungsschildangabe vergleichen Ventilator auf...

Page 16: ...en Typen F600 Nachschmiereinrichtung au en am Geh use Motoren mit Nachschmiereinrichtung nach Angaben auf dem Motortypenschild schmieren Nur vorgeschriebene Fette sind zul ssig Es wird empfohlen ein A...

Page 17: ...erwiesenes Personal Laufrad besch digt Laufrad ersetzen Hersteller Geh use besch digt Geh use ersetzen Hersteller Laufrad nicht mittig Helios Kundendienst kontaktieren Falsche F rder richtung falscher...

Page 18: ...CHE DATEN Type Temperaturklasse Gewicht bis max Type Temperaturklasse Gewicht bis max B VAR 280 F300 24 kg B VAR 315 F300 26 kg B VAR 355 F300 43 kg B VAR 400 F300 76 kg B VAR 450 F300 106 kg B VAR 50...

Page 19: ...or Baugr e Nenndurchmesser Ventilator Baureihe Axial Niederdruckventilator B Brandgas Ausf hrung Zeichenschl ssel Typenschild Ventilator q Herstelleradresse w CE Zeichen e Ausf hrung B AVD Typenbezeic...

Page 20: ...PE W2 U2 V2 KL U1 V1 W1 KL KL KL L1 L2 L3 PE Kaltleiter Thermistor PTC PTC Kaltleiter Thermistor M L1 L2 L3 L1 L2 L3 230 400 V 230 V 400 V 400 690 V 400 V 690 V Typenschild Netz Spannungs angabe auf M...

Page 21: ...s wei white PK rs rosa pink 12 12 11 Farbcode nach IEC 757 BK sw schwarz black BN br braun brown RD rt rot red OG or orange orange YE ge gelb yellow GN gn gr n green BU bl blau blue VT vi violett viol...

Page 22: ...Steuerung Principle layout Principe contr le Steuerkontakt Brandfall Alarm Control port contact emergency Contact de contr le alarme incendie Normal Betrieb Normal operation Fonctionn normal Ein On Ma...

Page 23: ...D 21 B AVD und B VAR Brandgasventilatoren F300 F400 F600 Montage und Betriebsvorschrift 6 2 Prinzipplan f r F600 Brandfall Schaltungsvorfall SS 1024...

Page 24: ...vorschrift INBETRIEBNAHMEPROTOKOLL KAPITEL 7 Einbaudatum Bemerkungen Anlagenbezeichnung Baureihe Typ Produktionscode Seriennummer Zulassungsnummer Nenndaten Nennwert Istwert Einheit Motortyp Motornumm...

Page 25: ...festen Sitz gepr ft JA Schutzgitter auf festen Sitz gepr ft JA Anlage Kanalsystem fachgerecht montiert JA Revisions ffung am Geh use frei zug ngig und geschlossen JA F rder und Drehrichtung gepr ft J...

Page 26: ...ente ggf f r Funktionserhalt reinigen x x x Unterwiesenes Personal j hrlich Kontrolle des Laufrads auf Verschmutzungen Korrosion Besch digungen sowie die korrekte Befestigung Komponente ggf f r Funkti...

Page 27: ...Motorlager austauschen x Hersteller oder vom Hersteller autorisierte Fachfirma Keine zeit liche Be grenzung erst nach Warnung der Zu standsan zeige von LZD Motorlager austauschen x Hersteller oder vom...

Page 28: ...8 78056 VS Schwenningen F HELIOS Ventilateurs Le Carr des Aviateurs 157 av Charles Floquet 93155 Le Blanc Mesnil Cedex CH HELIOS Ventilatoren AG Tannstrasse 4 8112 Otelfingen GB HELIOS Ventilation Sy...

Page 29: ...Helios Smoke Extraction Fans B AVD B VAR in temperature classes F300 F400 F600 EN Helios Ventilatoren INSTALLATION AND OPERATING INSTRUCTIONS B AVD...

Page 30: ...avity position Page 12 3 11 Recommended tightening torques for mounting screws Page 12 3 12 Electrical connection Page 13 3 13 Commissioning Page 13 3 14 Operation Page 13 CHAPTER 4 SERVICING AND MAIN...

Page 31: ...ns cuts or more profound injuries as well as contact with hot surfaces m Protective footwear Protective footwear serves to protect against heavy falling parts and from slip ping on slippery surfaces H...

Page 32: ...ea of application Normal use Operation within the characteristic curve of the respective unit see catalogue Vibrations and an increase in noise generation indicate operation outside of the characteris...

Page 33: ...als that could be sucked up such as clothing located in the intake area Protection against contact may be necessary on the suction side depending on the installation conditions Appropriate protection...

Page 34: ...in the table Chapter 5 0 on page 16 or the unit label Do not transport fan on the connection cables terminal box or impeller Do not stand under suspended loads 2 3 Receipt The shipment must be checked...

Page 35: ...d additional supply air fan required Series B AVD 500 1250 F300 F400 The low pressure axial smoke extraction fan is a direct driven fan where the motor is positioned in the airflow The air flow direct...

Page 36: ...via cooling air duct Inlet temperature of cooling air in the motor casing max 40 C not minimum cooling air mounting accessories centrif cooling air fan weather protection cover on site Connection of...

Page 37: ...or signals a fault then it is no longer guaranteed that the smoke extraction fan is supplied with sufficient cooling air In order to prevent damage to the smoke extraction fan it must be immediately d...

Page 38: ...allation in the fire area IB the terminal box must be dismantled from the casing and attached outside of the fire area see Fig 10 In this respect the connection line from the terminal box to the drive...

Page 39: ...data Type B KLG 500 Ref no 2798 Protection class IP44 Power 160 Watt Voltage 230 Volt max ambient temperature 40 C Frequency 50 Hz Speed 2400 1 min Current 0 7 Amp Volume flow 500 m3 h Wiring diagram...

Page 40: ...extension ducts Vertical mounting ring is not possible MRV Scope of delivery Extension ducts 2 pcs incl mounting kit hexagon head screws nuts spring washers Parallel unit mounting kit MP P Two fans c...

Page 41: ...B VAR 560 F300 3 0 B AVD 560 F300 4 6 B VAR 630 F300 3 0 B AVD 630 F300 5 2 B VAR 710 F300 3 5 B AVD 710 F300 5 7 B VAR 800 F300 4 0 B AVD 800 F300 5 8 B VAR 900 F300 4 5 B AVD 900 F300 6 9 B VAR 1000...

Page 42: ...ation of the mass to be dampened B VAR 900 4 533 kg B VAR 900 4 533 kg MP Z 900 68 kg VR 900 34 kg MK 900 18 kg Total weight 1186 kg 3 10 Centre of gravity position A motor protrusion arises depending...

Page 43: ...ransport safety device must be removed before the functional test Check for operation according to the intended purpose of the fan Permissible air flow temperature Compare power supply voltage with da...

Page 44: ...n on site the motor type plate must be observed Types F600 Relubrication device outside the casing Motors with relubrication devices must be lubricated according to the details on the motor type plate...

Page 45: ...damaged Replace casing Manufacturer Impeller not central Contact Helios customer service Incorrect air flow di rection Incorrect installation Correct installation situation Specialist according to se...

Page 46: ...Temperature class Weight up to max Type Temperature class Weight up to max B VAR 280 F300 24 kg B VAR 315 F300 26 kg B VAR 355 F300 43 kg B VAR 400 F300 76 kg B VAR 450 F300 106 kg B VAR 500 F300 191...

Page 47: ...in kW Pole changeable motor Fan size nominal diameter Fan series medium pressure axial fan B Smoke extraction version Fan type plate key Manufacturer s address CE mark Version B AVD Type designation t...

Page 48: ...01 SS 776 18 05 15 Kaltleiter Thermistor PTC PTC Kaltleiter Thermistor M L1 L2 L3 L1 L2 L3 230 400 V 230 V 400 V 400 690 V 400 V 690 V Voltage specification on motor type plate Operation at 400 V 3 Si...

Page 49: ...sa pink Farbcode nach IEC 757 BK sw schwarz black BN br braun brown RD rt rot red OG or orange orange YE ge gelb yellow GN gn gr n green BU bl blau blue VT vi violett violett GY gr grau grey WH ws wei...

Page 50: ...inzip Steuerung Principle layout Principe contr le Steuerkontakt Brandfall Alarm Control port contact emergency Contact de contr le alarme incendie Normal Betrieb Normal operation Fonctionn normal Ein...

Page 51: ...EN 21 B AVD and B VAR Smoke Extraction Fans F300 F400 F600 Installation and Operating Instructions 6 2 Basic plan for F600 Switch event in case of fire SS 1024...

Page 52: ...ORT CHAPTER 7 Installation date Remarks Installation designation Series type Production code Series number Approval number Nominal data Nominal value Actual value Unit Motor type Motor number Motor pr...

Page 53: ...crew connections checked for tight fit YES Protection grilles checked for tight fit YES System duct system installed professionally YES Inspection opening on casing freely accessible and closed YES Ai...

Page 54: ...onents for functional inte grity if needed x x x Instructed personnel Annual Check impeller for soiling corrosion damage and cor rect fastening Clean components for functional integrity if needed x x...

Page 55: ...10 years Replace motor bearings x Manufacturer or specialist company authorised by the manufacturer No time limit only after warning on status display of LZD Replace motor bearings x Manufacturer or s...