Room sensor AIR1/
KWL-CO2 0-10V
Installation and operating instructions
Any use other than the intended use is prohibited!
2.1 Technical data
AIR1/KWL-CO2 0-10 V
Dimensions (W x H x D) mm
85 x 85 x 27 mm
Power supply
24 V AC ⁄ DC (± 10 %)
Power consumption
0.6 W ⁄ 24 V DC;
1.2 VA ⁄ 24 V AC;
peak current 200 mA
Sensor
Optical NDIR sensor (non-dispersive infra-red
technology), with manual calibration (via zero
button), with automatic calibration (can be
deactivated via DIP switches)
Measuring range
0...2000 ppm or 0...5000 ppm (selectable via
DIP switches)
Output
0 -10 V with offset potentiometer (± 10 % of
the measuring range)
Relay output
potential-free changeover contact (24 V / 1 A)
Measuring accuracy
± 30 ppm ± 3 % of measured value
Temperature dependence
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄
°C (whichever is higher)
Pressure dependence
± 0.13 % ⁄ mm Hg
Long-term stability
< 2 % in 15 years
Gas exchange
by diffusion
Ambient temperature
0...+ 50 °C
Warm up time
approx. 1 hour
Response time
< 2 minutes
Electrical connection
0.14 - 1.5 mm
2
, via screw terminals
Housing
plastic, material ABS, colour pure white (simi
lar to RAL 9010)
Installation
wall mounting or on in-wall flusch box, Ø 55
mm, base with 4-hole for
mounting on vertically or horizontally installed
in-wall flush boxes for cable entry from the
back, with predetermined breaking point for
on-wall cable entry from top ⁄ bottom in
case of plain on-wall installation
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Standards
CE conformity, electromagnetic compatibili
ty according to EN 61 326, EMC Directive
2014
⁄ 30 ⁄ EU, Low Voltage Directive
2014 ⁄ 35 ⁄ EU
The recommended installation height for the room sensor AIR1/KWL-CO2 0-10 V
is between 1.4 and 1.5 m, persons who are usually standing and sitting are con-
sidered equally at this height.
The room sensor AIR1/KWL-CO2 0-10 V can also be installed at a different height
if the specific spatial conditions do not allow the recommended installation height.