32
d. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work,
to ensure the technician is aware of potentially flammable atmospheres. Ensure that the
leak detection equipment being used is suitable for use with flammable refrigerants, i.e.
non-sparking, adequately sealed or intrinsically safe.
e. Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts,
appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or
CO2 fire extinguisher adjacent to the charging area.
f. No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing
any pipe work that contains or has contained flammable refrigerant shall use any sources of
ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition
sources, including cigarette smoking, should be kept sufficiently far away from the site of
installation, repairing, removing and disposal, during which flammable refrigerant can
possibly be released to the surrounding space. Prior to work taking place, the area around
the equipment is to be surveyed to make sure that there are no flammable hazards or
ignition risks. No Smoking signs shall be displayed.
g. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into
the system or conducting any hot work. A degree of ventilation shall continue during the
period that the work is carried out. The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the atmosphere.
h. Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the
correct specification. At all times the manufacturer's maintenance and service guidelines
shall be followed. If in doubt consult the manufacturer's technical department for
assistance. The following checks shall be applied to installations using flammable
refrigerants:
The charge size is in accordance with the room size within which the refrigerant containing
parts are installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the
presence of refrigerant; Marking to the equipment continues to be visible and legible.
Markings and signs that are illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, unless the
components are constructed of materials which are inherently resistant to being corroded
or are suitably protected against being so corroded.
Summary of Contents for HDU-M20
Page 52: ...www heinner com 51 HDU M20 www heinner com 20 L...
Page 53: ...www heinner com 52 I II...
Page 54: ...www heinner com 53 III 1 2 3 4 5 6 7 8 9 10 11 12...
Page 55: ...www heinner com 54 1 2 3 4 5 6 7 8 9 10 11 12 T3 15A 250V 350V...
Page 56: ...www heinner com 55 IV R32 R290 4...
Page 57: ...www heinner com 56 R32 R290 1 2 3 4 5 6 a...
Page 58: ...www heinner com 57...
Page 59: ...www heinner com 58 1 2...
Page 60: ...www heinner com 59 25 o...
Page 61: ...www heinner com 60 80...
Page 62: ...www heinner com 61 t...
Page 63: ...www heinner com 62 V...
Page 64: ...www heinner com 63...
Page 65: ...www heinner com 64 VI 20 5 C 41 F 5 C 41 F 40 20 20 20 40...
Page 66: ...www heinner com 65 24 5 C 35 C...
Page 67: ...www heinner com 66 5 CONT 0 5 10 1 24 5 0 0 P2 35 85 5 0 24...
Page 68: ...www heinner com 67 40 50 60 TURBO 30 3 3...
Page 69: ...www heinner com 68 VII 1 8 P2 30 8 P2 2...
Page 70: ...www heinner com 69 1 2 3...
Page 71: ...www heinner com 70...
Page 72: ...www heinner com 71 1 2 3 30 A B A B VIII A B...
Page 73: ...www heinner com 72 A B C C A B B C...
Page 74: ...www heinner com 73 A B A B...