CONNECTION OF THE REFRIGERANT PIPE

Connection of the Refrigerant Pipe

When connecting the pipe to the unit or backout from the unit, use both

a spanner and a torque wrench.
When connecting, smear both inside and outside of the flare nut with

freeze motor oil, screw it by hand and then tighten with a spanner.
Refer to form 1 to check if the wrench had been tightened (too tight

would mangle the nut and lead leakage).
Examine the connection pipe to see if it had a gas leak, then take the

treatment of heat insulation. Only use a median sponge to entwine the

wiring interface of the gas pipe and heat preservation sheath of the gas

collection tube.

DRAINAGE HOSE

1. Install the drain hose.

S

The diameter of the drain hose should be equal or bigger than
the connection pipe’s. (The diameter of the polythene pipe:
Outer diameter 1 in (25 mm) Surface thickness 

 0.06 in (1.5

mm).

S

The drain hose should be short and the drooping gradient
should be less than 1/100 to prevent the formation of an air bub-

ble. If the drain hose does not has enough of a drooping

gradient, a drain raising pipe should be added.

S

To prevent a bend in the drain hose, the distance between the
hoisting stand should is 3.28 to 4.92 ft. (1 to 1.5 m) (see Fig.8).

3.28 to 4.92 ft (1 to 1.5 m)

3.28 to 4.92 ft (1 to 1.5 m)

Fig. 8

 - 

Drain Hose

S

Use the drain hose and clamp attached. Insert the drain hose into
the drain vent, and then tighten the clamp.

S

Entwine the big sponge on the clamp of drain hose to insulate
heat.

S

Heat insulation should be applied to the indoor drain hose.

Sponge(attachment)

Clamp(attachment)

Below 

1/6 in (4 mm)

Clamp

 Drain hose

Sponge (gray)

Fig. 9

 - 

Drain Hose

NOTE

:  Drain Setup pipe

S

The install height of the drain raising pipe should less than 11
in. (280 mm).

S

The drain raising pipe should form a right angle with the unit,
and distance to unit should not beyond 11.81 in. (300mm).

11 4/5 in (300 mm)

 3.2 8-4.9 2 

ft (1-1.5 m)

11 in (2 80 mm)

8 2/3 in (220 mm)

19

 2

/3 (

50

0 m

m

)

Fig. 10

 - 

Drain Setup Pipe

INSTRUCTION

The slant gradient of the attached drain hose should be within 3 in. (75

mm) so that the drain hole does not have to endure unnecessary outside

force.

 3

 in

 (

75

 mm)

19

 2

/3 (

50

0 m

m

)

Fig. 11

 - 

Slant gradient

1. Install the drain hose according to the following process if

several drain hoses join together.

Fig. 12

 - 

Slant gradient

2. Check the smoothness of the drain after the installation.
3. Check the drain state by immitting 36 3/5 in3 (600 cc) water

slowly from the outlet vent or test hole.

4. Check the drain in the state of refrigerating after installing the

electric circuit.

4 in (100 mm)

Fig. 13

 - 

Drain

Electrical wiring
NOTE

:  The power of the entire indoor unit must be connected in the

outdoor unit.

S

About the electrical wiring, see the circuit diagram attached
with the unit.

S

All electrical wiring installation must be done by professional
personnel.

S

Remove the earthing treatment.

Wiring method of connection unit and controller
Connection wiring (communication)

1. Open the electric box cover, drag the wiring (communication)

from rubber plug A, and impact them well individually with an

impact fastener.

2. Wire according to the indoor side circuit diagram.

(1.) Fix the impact fastener after the connection.
(2.) Entwine the small sponge on the electric wire (entwine

to prevent condensation).

(3.) Impact tightly with an impact fastener after connection.

Then fir on the electric box.

(4.) Connect the 3 cord rubber wire to the counter terminal

of the 3 way terminal board.

Summary of Contents for DLFBHC01K1A

Page 1: ...4 NOTE Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS INDOOR 5 CLEARANCES INDOOR 7 INS...

Page 2: ...entifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe pract...

Page 3: ...e Indoor Cassette Size Name Qty 12 18 Remote control 1 Battery 1 5V 2 Screw M4X25 2 GasketM6X 18X1 4 4 GasketM10X 30X2 5 10 Screw ST4 8X13 HC 4 Screw M6X25 4 Nut of Connector Pipe B Package 1 Pipe Con...

Page 4: ...Power and Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3 power communication wiring from the outdoor unit to the indoor unit consists of four 4 wires and...

Page 5: ...thout notice DIMENSIONS INDOOR Fig 2 Size 12 and 18 Cassette Dimensions Table 4 Dimensions Indoor SYSTEM SIZE 12 18 Height H in cm 9 1 23 1 9 1 23 1 Width W in cm 22 4 56 9 22 4 56 9 Depth D in cm 22...

Page 6: ...s subject to change without notice DIMENSIONS INDOOR CONTINUED Fig 3 Size 24 Cassette Dimensions Table 5 Dimensions SYSTEM SIZE 24 Height H In CM 9 4 23 9 Width W In CM 33 1 84 1 Depth D In CM 33 1 84...

Page 7: ...328 014525201 7 Specifications subject to change without notice CLEARANCES INDOOR Fig 4 Cassette Clearance...

Page 8: ...tioner IMPORTANT To guarantee the good performance the unit must be installed by professional personnel according with this instruction 253 5in 650mm 224 9in 570mm 153 4in 400mm m m 0 7 5 n i 9 4 2 2...

Page 9: ...6 in 4 mm Clamp Drain hose Sponge gray Fig 9 Drain Hose NOTE Drain Setup pipe S The install height of the drain raising pipe should less than 11 in 280 mm S The drain raising pipe should form a right...

Page 10: ...l by turning it toward the direction pointed by the arrow see Fig 15 so the adjust board connects well to the ceiling 5 Tighten the screws until the thickness of the sealing material between the panel...

Page 11: ...s 18 to 42 and powered by the Branch Box sizes 48 and 56 18K 0 18 1 72 24K 0 43 1 20 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS 18 42 Fig 19 Connection Diagram Outdoor Multi zone Sizes 18 42 48 56...

Page 12: ...g Align center of the pipes and or service valve Indoor unit tubing Flare nut Piping A150769 Fig 24 Align Pipe Center h Connect both the liquid and gas piping to the indoor unit i Tighten the flare nu...

Page 13: ...pushing it twice again after finishing test operation SYSTEM CHECKS 1 Conceal the tubing where possible 2 Make sure that the drain tube slopes downward along its entire length 3 Ensure all tubing and...

Page 14: ...on Viewing malfunction code through remote controller within 200s displayed directly on indoor display after 200s P8 Refrigerant lacking or blockage protection of system not available for residential...

Page 15: ...uency limit Over burden Flash 3 times Outdoor ambient sensor malfunction Flash 6 times F3 Outdoor tube sensor malfunction Flash 5 times F4 Exhaust sensor malfunction Flash 7 times F5 Attain the temper...

Page 16: ...ror Flash 20 times U1 U1 Compressor current protection Flash 21 times L9 L9 Compressor overload protection Flash 22 times H3 H3 Compressor discharge temperature protection Flash 23 times E4 E4 Lack of...

Page 17: ...B Indoor unit C Branch Box 3 Indoor unit A Indoor unit B Indoor unit C Communication error between the main board and driving board P6 Communication error between the main board and testing board CE I...

Page 18: ...18 328 014525201 Specifications subject to change without notice Copyright 2016 International Comfort Products Lewisburg Tennessee 37091 USA...

Reviews: