Functions and control
21
Domestic air conditioner
modification rate. If during the course of weak magnetic control, the modification rate is still not high
enough, enter into the control of decreasing frequency until the alarm of modification rate is relieved.
7.1.5.7 Temperature protection of the outdoor refrigerating coil
When the defrosting temperature and the sensor’s temperature are higher than 68
ć
, the frequency of
the compressor decreases 1hz/10seconds. Keep the frequency until it decreases to the lowest
frequency. When the temperatures are lower than 68
ć
and higher than 62
ć
, keep the frequency of
the compressor. When the temperatures are lower than 62
ć
, relieve the defrosting temperature
protection.
7.2 Value of Thermistor
Ambient Sensor, Defrosting Sensor, Pipe sensor
R25
ć
=10K
¡f
3% B25
ć
/50
ć
=3700K
f
3%
Temp.(
ć
)
Max.(K
ȍ
)
Normal(K
ȍ
)
Min.(K
ȍ
)
Tolerance(
ć
)
-30
165.2170
147.9497
132.3678
-1.94
1.75
-29
155.5754
139.5600
125.0806
-1.93
1.74
-28
146.5609
131.7022
118.2434
-1.91
1.73
-27
138.1285
124.3392
111.8256
-1.89
1.71
-26
130.2371
117.4366
105.7989
-1.87
1.70
-25
122.8484
110.9627
100.1367
-1.85
1.69
-24
115.9272
104.8882
94.8149
-1.83
1.67
-23
109.4410
99.1858
89.8106
-1.81
1.66
-22
103.3598
93.8305
85.1031
-1.80
1.64
-21
97.6556
88.7989
80.6728
-1.78
1.63
-20
92.3028
84.0695
76.5017
-1.76
1.62
-19
87.2775
79.6222
72.5729
-1.74
1.60
-18
82.5577
75.4384
68.8710
-1.72
1.59
-17
78.1230
71.5010
65.3815
-1.70
1.57
-16
73.9543
67.7939
62.0907
-1.68
1.55
-15
70.0342
64.3023
58.9863
-1.66
1.54
-14
66.3463
61.0123
56.0565
-1.64
1.52
-13
62.8755
57.9110
53.2905
-1.62
1.51
-12
59.6076
54.9866
50.6781
-1.60
1.49
-11
56.5296
52.2278
48.2099
-1.58
1.47
-10
53.6294
49.6244
45.8771
-1.56
1.46
-9
50.8956
47.1666
43.6714
-1.54
1.44
-8
48.3178
44.8454
41.5851
-1.51
1.42
-7
45.8860
42.6525
39.6112
-1.49
1.40
-6
43.5912
40.5800
37.7429
-1.47
1.39
-5
41.4249
38.6207
35.9739
-1.45
1.37
-4
39.3792
36.7676
34.2983
-1.43
1.35
-3
37.4465
35.0144
32.7108
-1.41
1.33
-2
35.6202
33.3552
31.2062
-1.38
1.31
Summary of Contents for JZ035-C2
Page 11: ...Piping diagrams Domestic air conditioner 4 Piping diagrams 9...
Page 12: ...Operation range 10 Domestic air conditioner 5 Operation range 10 0 21 27 35 20 40 60 43 20 40...
Page 14: ...Functions and control 13 Domestic air conditioner Wiring diagrams OUTDOOR UNIT...
Page 37: ...Service diagnosis 37 Domestic air conditioner...
Page 56: ...57 Do C omestic air ircuit Diagra conditioner ams r...
Page 58: ...Removal Procedure 1 Removal of Outdoor panel RPHVWLF LU RQGLWLR...
Page 59: ...Removal Procedure 2 Domestic Air Condition...
Page 60: ...4 Removal Procedure 3 Domestic Air Condition...
Page 61: ...Removal Procedure 2 Removal of Electrical Box RPHVWLF LU RQGLWLR...
Page 62: ...Removal Procedure 3 Removal of Fan and Fan Motor RPHVWLF LU RQGLWLR...
Page 63: ...Removal Procedure 4 Removal of fan motor brcked and partition RPHVWLF LU RQGLWLR...
Page 64: ...Removal Procedure 7 Domestic Air Condition...
Page 65: ...Removal Procedure 5 Removal of compressor and heat exchanger RPHVWLF LU RQGLWLR...