WHAT TO DO IF THINGS GO WRONG (1)
WHAT TO DO IF THINGS GO WRONG (2)
SELF HELP
If the shower is not working satisfactorily, make the following checks before calling out the installer.
Any one of these adjustments could restore the performance.
System will not operate Check that the mains electricity supply is switched on.
Pump operates but no
water is delivered
Check water is available to both ports, and that all isolating valves are open.
Check for an air-lock in the pump chamber.
Water too COLD
Turn Temperature Control Knob “B” anti-clockwise to a higher number on
the temperature scale (Diagram 10).
Check that hot water is available in the hot water cylinder. The ideal
thermostat setting for the hot water storage cylinder is 60°C (140°F).
Check that the HOT water isolating valve is open.
If possible, reposition temperature limiting device so that more movement
of knob “B” is allowed.
Water too HOT
Turn Temperature Control Knob “B” clockwise to a lower number on the
temperature scale (Diagram 10).
Check that the COLD water isolating valve is open.
Spray pattern poor
Clean the shower handset. Select an outer/inner spray pattern.
Broken parts
RING: 0117 923 5375
/
E-MAIL:
PROFESSIONAL SERVICE
If the previous “Self Help” checks fail to restore the performance, you should seek professional help.
The person who installed the shower is probably the best one to investigate and correct it and is
certainly the person to contact if you have had a problem in the guarantee period.
The following additional checklist is provided for the benefit of the qualified service person.
WARNING: SWITCH OFF THE ELECTRICITY AT THE LOCAL ISOLATOR
BEFORE REMOVING THE COVER TO MAKE CHECKS
Pump operates but no
water is delivered
Check the inlet connections to the mixing chamber are piped correctly.
Check that the shower and all pipe work are sited below the level of the
cold water tank and that it is fully primed and is therefore not air-locked.
(See commissioning procedure on page 7).
Pump operates when
motor is switched off
Check for faulty potentiometer switch, located under knob “A” inside
front cover.
Switch should be open circuit when turned fully anti-clockwise.
Water too hot
Blockage in filter causing obstruction in water supply.
Check and clean (see page 11).
Water too cold
Blockage in filter causing obstruction in water supply.
Check and clean (see page 11).
Poor temperature
adjustment
Check the hot and cold water supplies are delivered to the correct ports.
Check that water is supplied to the shower unit at balanced pressures
(ie Hot and Cold water are supplied from the same header tank).
Ensure cold water supply is not taken from mains.
Unit does not prime
Check that the shower and all pipe work are sited below the level of the
cold water tank.
Poor flow rate
Check for any restrictions in the Ø15mm supply (reduced diameters even
for short distances).
Check that pressure is not being lost to other services in the dwelling.
Check filter for obstructions in the water supply and clean if necessary.