S-15
FIGURA 12: Ventilación común de techo
HORIZONTAL COMMON VENTING
SIDE VIEW
TOP VIEW
Type "B" Vent required outdoors.
Vent Adapter Stk. #19021
At least 1/4" per foot rise or pitch
must be maintained on horizontal
runs from heater to vent.
Roof
Secure all joints with 3 (minimum) #8 x 3/8"
sheet metal screws and seal all joints.
H
Approved Vent Cap
Type "B" Vent required outdoors.
Vent Adapter Stk. #19021
Outside Wall
H
Vent Cap
Flashing
Wall Thimble
(If Applicable)
Burner Box
Burner Box
Burner Box
Burner Box
Burner Box
Burner Box
D
Burner Box
Burner Box
D
4” Aluminized steel Heat Exchange Tube
4” Aluminized steel Heat Exchange Tube
Type "B" Vent required outdoors.
Vent Adapter Stk. #
19
021
Outside Wall
Secure all join
ts with 3 (minimum) #8 x 3/8"
sheet metal screws and seal all joints.
H
Vent Cap
Wall Thimble
(If Applicable)
Burner Box
Burner Box
D
D
VENTILACIÓN COMÚN HORIZONTAL
VENTILACIÓN COMÚN VERTICAL
VISTA LATERAL
Adaptador de venteo
Part # 19021
Caja del quemador
Tapa aprobada de venteo
Lámina protectora Venteo tipo "B" necesario al exterior.
Techo
Asegure todas las uniones con 3 tornillos para metal
#8 x 3/8" como mínimo y selle todas las uniones.
Caja del quemador
Guardacabo de pared
(si es necesario)
Tapa de venteo
Pared exterior
Venteo tipo "B" necesario al exterior.
Asegure todas las uniones con 3 tornillos para metal
#8 x 3/8" como mínimo y selle todas las uniones.
Caja del quemador
Adaptador de venteo Parte # 19021
Caja del quemador