Heatrae Sadia UTC 99 Fitting Instructions And User Manual Download Page 5

5

 

When installed as a Cistern Fed water heater, the cold water supply 

must be from a feed cistern complying with Water Byelaw 30.

 

A vent pipe must be connected to the outlet of the heater. The vent 

pipe must rise continuously and be arranged to discharge into the 

cold water feed cistern. 

 

The vent pipe must have a minimum bore of 19mm.

3.1.5  National Wiring rules may contain restrictions concerning the installation 

of these units in bathrooms.

3.1.6 The installation must be carried out in accordance with the relevant 

         requirements of:      

       • The appropriate Building Regulations either The Building     

           

Regulations, The Building Regulations (Scotland) or Building

          Regulations (Northern Ireland). 

       • The Water Fittings Regulations or Water Byelaws in Scotland.

LOCATION

3.1.7  The unit should be vertically wall mounted using the wall bracket 

provided. Alternatively, it can be floor mounted on its base. The water 

connections must always be to the top of the unit.

3.1.8   Enough space should be left at the top above the unit to allow for pipe 

connections. Refer to Fig. 01 to determine a suitable position for the 

heater.

3.1.9  Ensure that the wall can support the full weight of the unit (see Technical 

Specification)  and  that  there  are  no  hidden  services  (gas,  water  or 

electricity) below the surface of the wall.

3.1.10 The unit should be fixed to the wall using No. 12 screws into suitable 

wall plugs.

3.2 PLUMBING
3.2.1  DO NOT install where the unit may freeze.
3.2.2  Refer to the section IMPORTANT INSTALLATION POINTS to determine 

which valves and accessories are required.   

3.2.3  The water connections are 15mm diameter copper tube suitable for 

compression fittings. Do not use solder joints as this will damage the 

heater. 

3.2.4  The inlet is marked BLUE and the outlet is marked RED. It is 

recommended to fit a WRAS listed isolating valve on the cold water 

inlet to simplify servicing.

OPEN OUTLET INSTALLATION
3.2.5 

When installed as an open outlet water heater, the outlet acts as 

a vent and must not be connected to any form of tap or fitting not 

Summary of Contents for UTC 99

Page 1: ...1 Fitting Instructions and User Guide UTC 99...

Page 2: ...understand these instructions prior to installing your vented water heater Particular attention should be paid to the section headed IMPORTANT INSTALLATION POINTS Following installation and commissio...

Page 3: ...lared load profile XS XS The water heating energy efficiency class of the model C D The water heating energy efficiency in 32 3 29 2 The annual electricity consumption in kWh 570 631 Daily fuel consum...

Page 4: ...or worktop 3 1 2 The UTC 99 can be installed either as an Open Outlet or Cistern Fed type unit when used with the appropriate fittings DO NOT connect directly to the mains water supply 3 1 3 OPEN OUT...

Page 5: ...ways be to the top of the unit 3 1 8 Enough space should be left at the top above the unit to allow for pipe connections Refer to Fig 01 to determine a suitable position for the heater 3 1 9 Ensure th...

Page 6: ...2 7 The cold water supply can either be taken from the cold water mains or from a cold water feed cistern complying with Water Byelaw 30 with a minimum recommended pressure of 0 04 MPa 0 4 bar 3 2 8 T...

Page 7: ...and be arranged to discharge into the cold water feed cistern The vent pipe must have a minimum bore of 19mm DO NOT connect any pressure relief device to the vent pipe of this water heater 3 2 12 The...

Page 8: ...ons Ensure the electrical supply is switched off before making any connections to the water heater 3 3 1 The unit is supplied fitted with a 0 75m 3 core 1 5mm2 flexible cable The electricity supply sh...

Page 9: ...ures in the range of 10 to 70 C To avoid any risk of freezing when the heater is not in use for long periods during the winter months do not switch off the electrical supply and set the thermostat to...

Page 10: ...nt operation 5 7 LITERATURE Hand over the Installation and user instructions 6 0 MAINTENANCE WARNING Disconnect from all electrical supplies before beginning any work on the water heater Water contain...

Page 11: ...ting pad from the terminal housing 6 3 3 Disconnect the electrical terminations to the thermostat Disconnect earth links to the earthing stud 6 3 4 Remove the element plate assembly by unscrewing the...

Page 12: ...uld a problem occur the table overleaf should enable most faults to be identified with ease Fault Finding should be carried out by a competent person and any replacement parts used should be authorise...

Page 13: ...Checkmains water turned on 1 Cold watersupply not No water flow General 2 Checkforobstructions supply 2 Blockage in cold water connections to tapset 1 Checkwater correctly installed 1 Open Outlet taps...

Page 14: ...regularly maintained Maintenance and servicing should be carried out by a competent person and any replacement parts used should be authorized Heatrae Sadia spare parts DESCRIPTION CODE No Element pl...

Page 15: ...tions 4 The unit has been used only for heating potable water The unit is not guaranteed against damage by frost and the inner container with integral immersion heater is not guaranteed against excess...

Page 16: ...67 Parts Centre Tel 0344 292 7057 www partscentre co uk Newey Eyre Unit 3 5 Wassage Way Hampton Lovett Ind Estate Droitwich Worcestershire WR9 0NX Tel 01905 791500 Fax 01905 791501 UK Spares Ltd Unit...

Reviews: