Heatrae Sadia PremierPlus Installation And User Manual Download Page 13

13

Cold water control pack

CAUTION

 

`

Flush supply pipework before 
connection to remove all flux and 
debris prior to fitting the inlet 
controls. Failure to do this may result 
in irreparable damage to the controls 
and will invalidate any warranty.

 

`

The cold water combination valve can be connected 
anywhere on the cold water cylinder supply prior to 
the expansion vessel. 

 

`

No other valves should be placed between the 
cold water combination valve and the cylinder.

 

`

The cold water combination valve is installed as a 
complete one-piece unit, the valve incorporates 
the pressure reducer, strainer, expansion valve and 
check valve.

 

`

The pressure setting is set to 3.5 bar.

 

`

The valve can be fitted in any orientation to suit 
the installation as long as the valve is installed with 
the direction of flow arrows pointing in the correct 
direction.

 

`

The expansion relief valve should be installed with 

the discharge pipework in either the horizontal 
position or facing downwards.

 

`

Where discharge pipework is difficult to attain, the 
local building control officer from the local council 
should be sought for advice as this falls under G3 
guidelines and is not down to the manufacturer of 
unvented systems

Primary circuit control

 

`

The 2 port motorised valve supplied with the 
cylinder MUST be fitted on the primary flow to the 
cylinder heat exchanger and wired such that in the 
event of the cylinder overheating it will close the 
primary circuit.         

 

`

Primary circulation to the cylinder heat exchanger 
must be pumped; gravity circulation WILL NOT 
WORK.

 

`

It is recommended that an air bleed or automatic 
air vent is incorporated in the primary return pipe 
work close to the unit.

 

`

Boiler flow temperature should be set to 82° 
(maximum flow temperature to primary heat 
exchanger 88°C).

Figure 8: 3 bar pressure reducing valve

Expansion valve

Cold mains 
connection
(22mm)

Expansion valve
outlet (15mm)

Outlet connection
(22mm)

Pressure reducing
valve cartridge
(3.5bar)

Direction of
flow

Summary of Contents for PremierPlus

Page 1: ...PremierPlus Unvented Hot Water Cylinder Installation and User Manual...

Page 2: ...ntenance operations 21 10 Troubleshooting 22 10 1 Fault finding 22 11 Decommissioning 23 11 1 Decommissioning procedure 23 12 1 Spare parts list 23 Benchmark checklist 25 Commissioning service records...

Page 3: ...appliance Faulty or insufficient maintenance of the appliance Failure to abide by the instructions on installing the product Installer s liability The installer is responsible for the installation and...

Page 4: ...and the mains water supply Do not switch on if there is a possibility that the water in the cylinder is frozen DANGER This cylinder is unvented and as such becomes pressurisedwheninoperation Thecombin...

Page 5: ...ssure 1 6MPa 16 bar Max design pressure 0 8MPa 8 bar Max operating pressure PRV 0 35MPa 3 5 bar Expansion relief valve setting 0 6MPa 6 bar T P valve setting 1 0MPa 10 bar 90 C Maximum primary pressur...

Page 6: ...199 246 295 295 355 355 Weight empty kg 23 25 28 29 36 45 45 55 55 Max supply pressure 1 6MPa 16 bar Max design pressure 0 8MPa 8 bar Max operating pressure PRV 0 35MPa 3 5 bar Max expansion vessel c...

Page 7: ...170E 210E 250E 300E B 306 306 306 306 306 306 306 C 493 616 800 925 1184 1437 1751 D 784 906 1090 1216 1474 1726 2040 Item 100B 120B 150B 170B 210B 250B 300B A 315 315 315 315 315 315 315 B 354 354 35...

Page 8: ...s with controls selected A double pole isolating switch must be installed in the mains supply All earth connections must be connected back to the mains earth supply 3 DHW OFF 2 3 L 1 N 2 3 HTG ON DHW...

Page 9: ...3 Control Housing Details Element Connections 1 5mm 3 Core HOFR sheathed cable Indirect control wiring N L 1 5mm 3 Core HOFR sheathed cable Figure 5 Direct wiring schematic Figure 4 Indirect wiring s...

Page 10: ...ions as listed below Building Regulations G3 The Building Standards Scotland The Building Regulations Northern Ireland I E E Electrical Regs UK Water Regulations 5 1 Installation regulations 5 2 Insta...

Page 11: ...r supplies that have either inadequate pressure or where the supply may be intermittent Situations where it is not possible to safely pipe away any discharge from the safety valves In areas where the...

Page 12: ...connection if required Cold water combination valve Mains water supply Isolating valve not supplied Discharge pipe Tundish Drain cock not supplied Secondary return if required use swept tee Inlet NOTE...

Page 13: ...d with the discharge pipework in either the horizontal position or facing downwards Where discharge pipework is difficult to attain the local building control officer from the local council should be...

Page 14: ...onze circulation pump will be required On large systems due to the increase in system water content it may be necessary to fit an additional expansion vessel to the secondary circuit This should be do...

Page 15: ...nd lower than the valve with no more than 600mm of pipe between the valve outlet and the tundish see fig 10 Note To comply with the Water Supply Water Fittings Regulations the tundish should incorpora...

Page 16: ...e continuously marked with a warning that no sanitary appliances should be connected to the pipe Note 1 Plastic pipes should be joined and assembled with fittings appropriate to the circumstances in w...

Page 17: ...p to 27m 1 4m 1 7m 2 3m Table 5 Sizing of copper discharge pipe D2 for common temperature relief valve outlet sizes Safety device e g Temperature relief valve Metal discharge pipe D1 from Temperature...

Page 18: ...e unit within the central heating system Other controls will be necessary to control the space heating requirements and times that the system is required to function The cylinder is compatible with mo...

Page 19: ...hermostat s and that no water has discharged from the expansion relief valve or temperature pressure relief valve during the heating cycle Indirect units Fill the indirect primary circuit following th...

Page 20: ...direct units immersion heater s All immersion heaters are fitted with a combined thermostat and thermal cut out located under the terminal cover mounted on the side of the product Access to the therm...

Page 21: ...ply and turn off boiler Attachahosepipetothedraincockhavingsufficient length to take water to a suitable discharge point below the level of the unit Open a hot tap close to the unit and open drain coc...

Page 22: ...rect thermostat Indirect motorised valve not connected correctly Check wiring and or plumbing connections to motorised valve Water discharges from expansion valve Intermittently Expansion vessel charg...

Page 23: ...Pressure reducing valve cartridge 3 5 bar 95605898 11 Temperature Pressure Relief Valve 95605810 12 Expansion vessel 12 litre 100 120 and 150 litre models not shown 95607863 13 Expansion vessel 18 lit...

Page 24: ...ure 12 Exploded view of cold water combination valve Cold Mains Connection 22mm Outlet Connection 22mm Outlet Connection 15mm 9 10 7 8 4 3 17 11 20 17 18 1 19 3 4 2 22 22 23 Figure 13 Cylinder explode...

Page 25: ...set temperature C I min Yes Type of control system if applicable Y Plan S Plan Other Is the cylinder solar or other renewable compatible Yes No What is the hot water temperature at the nearest outlet...

Page 26: ...Telephone No Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Comments Signature SERVICE 09 Date Engineer name Company name Telephone No Comments Signature SERVICE 02 Date E...

Page 27: ...subjected to frost nor has it been tampered with or been subject to misuse or neglect No factory fitted parts have been removed for un authorised repair or replacement The Benchmark commisioning chec...

Page 28: ...te responsibility and sustainability charters and reduce our printed material we encourage you to download product brochures from our website In designing these files we have taken into account the ne...

Reviews: