Heatrae Sadia 7037042 Installation, Operation And Maintenance Manual Download Page 16

16

8. Operation

8.1 General

 

`

The appliance stores water at the temperature set 

on the adjustable control knob. This can be set 

to give temperatures in the range 10°C to 70°C. 

The factory set temperature is set at 54°C and is 

indicated by aligning the arrow on the adjustment 

knob with the arrow on the cover. Turn the 

adjustment knob towards the wider red band to set 

hotter, towards the blue band to set cooler.

WARNING

 

`

If water discharges from the 

temperature/pressure relief valve on  

the appliance, turn the appliance off. 

DO NOT turn off any water supply. 

Contact a competent installer for 

unvented water heaters to check the 

system.

 

`

DO NOT tamper with any of the safety 

valves  fitted  to  the  system.  If  a  fault 

is suspected contact a competent 

installer.

 

`

DO NOT bypass the thermal cut-out in 

any circumstances.

Figure 8: Temperature control

 

`

In hard water areas it is advised that the maximum 

temperature is restricted to prevent build up of 

scale. 

 

`

Temperatures above 55

o

C can scald so 

consideration should be given to blending at the 

point of use to a safe user temperature. 

 

`

To avoid risk of freezing when the heater is not 

in use for long periods during the winter months, 

do not switch off the electrical supply and set the 

thermostat to its minimum position. N.B. This will 

not protect other system pipework.

 

`

The indicator light will be illuminated when the 

appliance is heating.

 

`

To ensure the appliance continues to operate at 

its optimum performance it should be periodically 

maintained in accordance with the instructions 

given under the section headed MAINTENANCE.

COLD

HOT

WARNING

 

`

If the appliance is to be left unused 

following installation and commissioning 

e.g. unocupied properties, the appliance 

should be drained or regularly flushed 

through with fresh mains water once a 

week.

 

`

When placing the appliance into service, 

the  procedure  for  filling  the  appliance 

and the system checks detailed above 

should be carried out.

7.4 Benchmark

The appliance is covered by the Benchmark Scheme 

which aims to improve the standards of installation 

and commissioning of domestic heating and hot water 

systems in the UK and to encourage regular servicing 

to optimise safety, efficiency and performance.

Benchmark is managed and promoted by the Heating 

and Hotwater Industry Council. For more information 

visit www.centralheating.co.uk.

Please ensure that the installer has fully completed the 

Benchmark Checklist (see page 34) of this manual and 

that you have signed it to say that you have received a 

full and clear explanation of its operation. The installer is 

legally required to complete a commissioning checklist 

as a means of complying with the appropriate Building 

Regulations (England & Wales).

All installations must be notified to Local Area Building 

Control either directly or through a Competent Persons 

Scheme. A Building Regulations Compliance Certificate 

will then be issued to the customer who should, on 

receipt, write the Notification Number on the Benchmark 

Checklist.

This product should be serviced regularly to optimise 

its  safety,  efficiency  and  performance.  The  service 

engineer should complete the relevant Service Record 

on the Benchmark Checklist after each service. The 

Benchmark Checklist may be required in the event of 

any warranty work. 

Summary of Contents for 7037042

Page 1: ...Multipoint Vertical 30 100 Litres Installation operation and maintenance manual...

Page 2: ...manufacturers and installers The purpose is to ensure that customers are provided with the correct equipment for their needs that it is installed commissioned and serviced in accordance with the manuf...

Page 3: ...ficient maintenance of the appliance Failure to abide by the instructions for installing the product Installer s liability The installer is responsible for the installation and the commissioning of th...

Page 4: ...ended minimum water pressure 0 08 MPa 0 8 bar Max water pressure1 6 MPa 16 bar see table 1 page 5 If the supply cord is damaged it must be replaced by the manufacturer its service agent or simularly q...

Page 5: ...duct Name Multipoint 30L V 3kW Multipoint 50L V 3kW Multipoint 80L V 3kW Multipoint 100L V 3kW Suppliers name or trade mark Multipoint Supplier s model identifier 30L V 3kW 50L V 3kW 80L V 3kW 100L V...

Page 6: ...43 1028 1084 1253 D 626 903 956 1134 E 100 100 100 100 F 371 371 451 451 G 95 95 105 105 H OUTLET 22mm 3 4 BSP M I INLET 22mm 3 4 BSP M J TEMPERATURE PRESSURE RELIEF VALVE DISCHARGE PIPE CONNECTION 15...

Page 7: ...TY BLACK WIRE A TERMINAL BLOCK ELEMENT EARTH IMMERSION STUD L N E OUTER CLADDING L N THERMOSTAT ADJUSTMENT SPINDLE FACTORY SET AT 54 C 2 1 B A RESET CUT OUT TO ELEMENT CUT OUT SENSOR THERMOSTAT SENSOR...

Page 8: ...pressure to the tap or shower an unvented water heater uses the incoming mains water pressure To do this the water heater is sealed and not vented However when the volume of water is heated it expands...

Page 9: ...r consistently contains a high proportion of solids e g suspended matter that could block the strainer unless adequate filtration can be ensured In areas where the water supply contains chloride level...

Page 10: ...fitted Temperature Pressure Relief valve be removed other than by a competent person To do so would invalidate any warranty claim The cold water controls supplied MUST be fitted on the mains water sup...

Page 11: ...ical installation table supplied and should be fitted A suitable draining tap should be installed in the cold water supply to the appliance between the Expansion Valve and the appliance at as low a le...

Page 12: ...ve with no more than 600mm of pipe between the valve outlet and the tundish see Fig 7 Note To comply with the Water Supply Water Fittings Regulations the tundish should incorporate a suitable air gap...

Page 13: ...able providing that a wire cage or similar guard is positioned to prevent contact whilst maintaining visibility and c discharges at high level e g into a metal hopper and metal downpipe with the end o...

Page 14: ...p to 27m 1 4m 1 7m 2 3m Table 6 Sizing of copper discharge pipe D2 for common temperature relief valve outlet sizes Safety device e g Temperature relief valve Metal discharge pipe D1 from Temperature...

Page 15: ...g heating When the set temperature is reached the indicator light will go out The set temperature can be adjusted by rotating the control knob This can be set to give temperatures in the range 10 C to...

Page 16: ...given under the section headed MAINTENANCE COLD HOT WARNING If the appliance is to be left unused followinginstallationandcommissioning e g unocupied properties the appliance should be drained or regu...

Page 17: ...pecting the water heater internally Safety valve operation CAUTION Water discharged may be very hot Manually operate the Temperature Pressure Relief Valve for a few seconds Check water is discharged a...

Page 18: ...ance interior Ensure sealing surfaces are clean and seals are undamaged if in doubt fit a new gasket Replace immersion heater ensuring correct orientation One of the bolt holes uses a larger bolt to e...

Page 19: ...Check and adjust setting if required Replace if necessary Element Failure Replace EPA Discharge of water from Expansion pressure relief valve continuously Excessive mains water pressure Check pressure...

Page 20: ...lect The appliance has not been subject to wilful or accidental damage caused by your negligence Regular maintenance has been carried out by a competent person or a Heatrae Sadia authorised engineer i...

Page 21: ...y Users in Private Households in the European Union This symbol on the product indicates that this product must not be disposed of with your other household waste Instead it is your responsibility to...

Page 22: ...22 13 Spare parts 18 9 4 15 16 5 17 3 20 21 22 1 2 19 Figure 11 Spare parts...

Page 23: ...ion relief valve 0 6 Mpa 6 bar not shown 95607986 11 Pressure reducing valve not shown 95605082 12 Tundish not shown 95605838 13 Non return valve 22mm not shown 7037720 14 Indicator light BBSC not sho...

Page 24: ...24...

Page 25: ...25...

Page 26: ...26...

Page 27: ...27...

Page 28: ...rporate responsibility and sustainability charters and reduce our printed material we encourage you to download product brochures from our website In designing these files we have taken into account t...

Reviews: