COMMUNITY BARBECUE
6
A-0060-MAN Heatlie Community Barbecue Instruction Manual V2 Updated Dec 2021
This
b
arbecue is only to be used in an above ground, open air situation
with natural ventilation
, without stagnant areas, where gas leakage and
products of combustion are rapidly dispersed by wind and natural
convection.
The
Community
B
arbecue is not for use indoors. Please refer to AS5601 for
specific installation and ventilation regulations.
If you are using the
b
arbecue within a structure, please ensure that you are
complying with at least one of the following positioning options:
• An enclosure with walls on all sides, but at least one permanent opening
at ground level and no overhead cover (Figure F1);
• Within a partial enclosure that includes an overhead cover and no more
than two walls (Figures F2 and F3);
• Within a partial enclosure that includes an overhead cover and more than
two walls, with the following also applying (Figures F4 and F5):
(i)
At least 25% of the total wall area is completely open and unrestricted
(ii)
At least 30% of the remaining wall area is open and unrestricted;
• In the case of balconies, at least 20% of the total of the side, back and
front
wall areas are to be open and unrestricted, and remain as such.
NOTE:
A door, blinds, or window, is not to be considered a permanent
opening.
POSITIONING
YOUR HEATLIE
BARBECUE IN
AN OUTDOOR
AREA
FIGURE F1 - OUTDOOR AREA - EXAMPLE 1
FIGURE F4 - OUTDOOR AREA - EXAMPLE 4
FIGURE F5 - OUTDOOR AREA - EXAMPLE 5
30 percent or more in total
of the remaining wall area is
open and unrestricted
30 percent or more in total
of the remaining wall area is
open and unrestricted
FIGURE F3 - OUTDOOR AREA - EXAMPLE 3
Both ends open
FIGURE F2 - OUTDOOR AREA - EXAMPLE 2
Open side at
least 25% of
total wall area
Open side at
least 25% of
total wall area