HEATIZON SYSTEMS Gutter Melt SR Design & Installation Manual Download Page 17

17 

 

Design and Installation 

  STEP 13         COMPLETE WARRANTY CERTIFICATE 

Mail in the warranty certificate immediately after installing the GutterMelt

® 

SR 

system.  Failure to complete the warranty card could void the manufacturer’s 
warranty. The warranty is subject to the guarantee conditions listed on the 
warranty certificate, and upon documentation that the required resistance 
readings were completed.  You may wish to keep a copy of the warranty card 
for your reference. 

  STEP 10    CONNECT POWER SUPPLY & ACTIVATION 

The connection of an acceptable ground fault protection device power supply and the activation device must be 
done in accordance with the National Electrical Code (NEC) and the Canadian Electrical Code (CEC).   
The braided shield from GutterMelt

® 

SR Cable must be wired to Ground for all primary power installations. 

Caution:  Never energize GutterMelt

®

 SR until: 

1.  The GutterMelt

®

 SR Cable has been verified to be free of damage. 

2.  All splices and all power kit and end kit connections have been inspected. 
3.  A Megohmmeter Test has been used to verify a minimum of 20 MegOhms between the 

heating element and the braided shield. 

  STEP 12     COMPLETE AND ATTACH LABELS 

  STEP 11         TROUBLESHOOTING 

Problem:  GutterMelt

®

 SR Cable fails the Megohmmeter Test 

Potential Causes:    

• 

Check field installed power/end terminations and connection splices; correct as necessary

 

• 

Inspect the GutterMelt

®

 SR Cable for damage to the insulator, exposed braided shield, and/or contact between 

the braided shield and the core wire(s).  Replace entire length of damaged GutterMelt

®

 SR Cable 

 
Call Heatizon Systems technical support @ 801-293-1232 if additional assistance is required. 

Note:  In the event the power/end termination or splices are not the cause of the failed Megohmmeter 
Test and the GutterMelt

®

 SR Cable has not been damaged in any way, remove and replace the 

entire length of GutterMelt

® 

SR.  For Warranty claims, please return the entire length of GutterMelt

® 

SR to Heatizon Systems, with the end termination and power termination connections intact, for 
evaluation prior to replacement.   

Place the included labels in the following locations: 
 

• 

Electrical Panel Label — Inside door at electrical service panel. This 
label matches the information printed on the GutterMelt

® 

SR Cable 

 

• 

Stop Sign Warning Label — on or near the area to be heated by 
GutterMelt

®

 SR Cable 

 
 

Summary of Contents for Gutter Melt SR

Page 1: ...www heatizon com 2017 Heatizon Systems HEATIZON SYSTEMS RADIANT HEATING AND SNOW MELTING SYSTEMS GutterMelt SR is a registered trademark of Heatizon Systems 07 17...

Page 2: ...2...

Page 3: ...minders 6 GutterMelt SR Cable Layout Design Guidelines 7 GutterMelt Accessories 9 GutterMelt Activation 11 Design and Installation 13 Resistance Recording Page 18 Warranty 19 Note Before proceeding wi...

Page 4: ...ach the cable to standard roof covering material The cable can also be inserted in downspouts using downspout hangers or brackets Heatizon Part HT38411 or HT386412 to support the heating cable GutterM...

Page 5: ...Electrical Code CEC part 1 and local codes and regulations Note Ground fault protection must be used when installing all GutterMelt SR products Refer to the NEC or CEC for specific requirements Note D...

Page 6: ...ed to a suitable earth ground Do not exceed the maximum circuit lengths listed in this Design and Installation Manual Always remember to test the insulation resitance using a 2500 VDC Megohmmeter veri...

Page 7: ...R are attached with a screw or nail GutterMelt cable is installed then a water sealing caulking is applied around the clips screws and nails to prevent leaks Sloped Roof with Gutter and a Valley Exten...

Page 8: ...rMelt in down spout or drain to prevent damage to cable Downspouts A continuous path for melt water can be maintained by running the Gut terMelt inside the downspout to the bottom and extend a small d...

Page 9: ...n GutterMelt is secured to angled bracket no fasteners required Includes UV resistant plastic wire ties Includes two 2 downspout hanger bracket assemblies Prevents heating cable from being damaged at...

Page 10: ...C or 300 feet 5W 120VAC GutterMelt SR Cable Contains GFCI with 30mA test and reset Power ON indicator light Requires NEMA5 20 Amp Outlet Receptacle HT393473 PT 15 Amp 120VAC Plug in Pig Tail Set Used...

Page 11: ...Mounted Sensor One 30A Contact Activates System when moisture is detected and temperature is below set point Leaves system on for up to 6 hours Requires 100 277VAC Switches up to one 30A Loads M326CD...

Page 12: ...ion device Provides two different delay features Powered by 12VDC provides 24VAC for activation device as well as up to 12 circuits of monitoring M332 Gutter Controller Gutter Controller allows Heatiz...

Page 13: ...erMelt SR is designed for snow melt applications and to provide a path for water to exit the roof gutter and downspout drain STEP 1 PLAN THE LAYOUT Note Make certain to plan for the movement of the wa...

Page 14: ...started at 40 F 0 F 20 F 505 475 420 650 560 765 765 9GM1 If started at 40 F 0 F 20 F 320 210 185 425 270 245 455 405 370 460 460 12GM1 If started at 40 F 0 F 20 F 240 155 135 315 210 180 375 310 270...

Page 15: ...tivators require human action as a result they should be placed in a location that is convenient and easily accessible STEP 6 LOCATION SELECTION STEP 3 CONTACT YOUR GUTTERMELT SR SUPPLIER Contact your...

Page 16: ...chased from your Heatizon Systems Distributor to attach GutterMelt SR to the roof covering material Use Foil Tape purchased from your Heatizon Systems Distributor to attached GutterMelt SR to the rain...

Page 17: ...of 20 MegOhms between the heating element and the braided shield STEP 12 COMPLETE AND ATTACH LABELS STEP 11 TROUBLESHOOTING Problem GutterMelt SR Cable fails the Megohmmeter Test Potential Causes Chec...

Page 18: ...00 VDC at least twice The measured value should not be less than 20 Megohms Record all test results below Prior to Installation When removed from Package After Installation of GutteMelt SR Heating Ele...

Page 19: ...urchased from Heatizon Systems integrated into or connected to them 4 Any labor costs for removal of alleged defective part s and or reinstallation of replacement part s transportation to and from Hea...

Page 20: ...20 Mail Heatizon Systems 4137 South 500 West Murray UT 84123 USA Phone 801 293 1232 Toll Free 888 239 1232 Fax 801 293 3077 Email info heatizon com Website www heatizon com...