Heatilator NDV30-IFT Installation Manual Download Page 13

13

Heatilator  • NDV30-IFT, NDV33-IFT, NDV36-IFT, NDV36-IFT-NVR, NDV42-IFT Installation Manual  •  2620-980  Rev. C  •  8/20 

Figure 3.6  Appliance Locations - Part 1, Columns A-H (For Columns I-L, See Figure 3.7)

Models

A

B

C

D

E

F

G

H

NDV30-IFT

NDV30L-IFT

in.

36

33-1/2

19-5/8

43-3/8

47

53-1/4

37

8-1/2

mm

914

851

498

1102

1194

1353

940

216

NDV33-IFT

NDV33L-IFT

in.

39

35-1/2

19-5/8

43-3/8

47

53-1/4

40

9-1/2

mm

991

902

498

1102

1194

1353

1016

241

NDV36-IFT

NDV36L-IFT

NDV36-IFT-NVR

in.

42

37-5/8

19-5/8

43-3/8

47

53-1/4

43

10-5/8

mm

1067

956

498

1102

1194

1353

1092

270

NDV42-IFT

NDV42L-IFT

in.

48

41-7/8

19-5/8

N/A

47

53-1/4

49

12-3/4

mm

1219

1064

498

N/A

1194

1353

1245

324

For optimum flame appearance in a corner installation terminating horizontally, 

configurations (1) and (6) are recommended instead of (3).  See Figure 4.23.

(3) Rear vent

One 45° elbow

Horiz Term

(6) Rear Vent

Two 90° elbows

Horiz Term

(4) Rear Vent

One 90° elbow

Vert Term

(1) Top Vent

One 90° elbow

Horiz Term

(5) No elbows

Horiz Term

A

A

A

A

A

A

C

B

B

E

F

D

1/2 in. (13 mm) min.

appliance to

combustibles

D

F

1 in. (25 mm)

min. pipe to

combustibles

E

1/2 in. (13 mm)

min. appliance

to combustibles

(2) Alcove

Installation

C

1 in. (25 mm)

min. pipe to

combustibles

G

Drywall

48 in.

(1219 mm)

maximum

NOTE: 

 Consider the mantel or cabinet system to be installed 

and comply with the necessary requirements for elevated hearth.  

Refer to instructions included with cabinet system.

In addition to these framing dimensions, also reference the 

following sections:

•  Clearances and Mantel Projections (Section 10)

•  Vent Clearances and Framing (Section 5)

H*

* As B increases, H increases accordingly.

I

L

J

K

B. 

Appliance Location and 

Clearances to 

Combustibles

When selecting a location for the appliance it is important 

to consider the required clearances to walls and allow suf-

ficient  clearance  for  heat  management  systems  venting.

See Figure 3.5.

WARNING! 

Risk  of  Fire  or  Burns! 

Provide  adequate 

clearance  around  air  openings  and  for  service  access. 

Due  to  high  temperatures,  the  appliance  should  be  lo-

cated out of traffic and away from furniture and draperies.

NOTICE: 

Illustrations reflect typical installations and are 

FOR DESIGN PURPOSES ONLY. Illustrations/diagrams 

are not drawn to scale. Actual installation may vary due to 

individual design preference.

Figure 3.5  Clearance for Heat Management System

NOTICE:  Allow 18 inches minimum clearance 

on side(s) of appliance for venting of heat 

management system.

18 IN. MIN.

Summary of Contents for NDV30-IFT

Page 1: ...ly call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a...

Page 2: ...Location and Clearances to Combustibles 13 C Constructing the Appliance Chase 16 4 Termination Location and Vent Information A Approved Pipe 17 B Vent Termination Minimum Clearances 17 C Vent Terminal...

Page 3: ...Proper appliance for fuel type ___________________________ Was a conversion performed ___________________________ Leak check performed and inlet pressure verified ___________________________ Verified...

Page 4: ...not be factored as primary heat in residential heating calculations NOTICE This installation must conform with local codes In the absence of local codes you must comply with the National Fuel Gas Code...

Page 5: ...fed or not or plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in t...

Page 6: ...rizontally vented gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection T...

Page 7: ...sure that the following tools and building supplies are available Hand Tools Tape measure Level Framing material Manometer Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety gl...

Page 8: ...r water Carefully remove the appliance and components from the packaging The vent system components and decorative barrier fronts may be shipped in separate packages If packaged separately the log set...

Page 9: ...2 32 5 8 829 38 5 8 981 F 31 1 2 800 31 1 2 800 31 1 2 800 31 1 2 800 G 35 1 4 895 35 1 4 895 35 1 4 895 35 1 4 895 H 15 3 4 400 15 3 4 400 15 3 4 400 15 3 4 400 I 1 3 4 44 1 3 4 44 1 3 4 44 1 3 4 44...

Page 10: ...9 518 835 48 171 762 803 DEMI36 B in 32 7 8 20 3 8 35 7 8 1 7 8 6 3 4 30 31 5 8 mm 835 518 911 48 171 762 803 DEMI42 B in 38 7 8 20 3 8 41 7 8 1 7 8 6 3 4 30 31 5 8 mm 987 518 1064 48 171 762 803 IMPO...

Page 11: ...9 533 835 48 171 762 803 TRES36 B in 32 7 8 21 35 7 8 1 7 8 6 3 4 30 31 5 8 mm 835 533 911 48 171 762 803 TRES42 B in 38 7 8 21 41 7 8 1 7 8 6 3 4 30 31 5 8 mm 987 533 1064 48 171 762 803 IMPORTANT Th...

Page 12: ...5 8 2 3 8 30 31 1 2 mm 873 533 911 41 60 762 800 SIM 4842 in 40 3 8 21 41 7 8 1 5 8 2 3 8 30 31 1 2 mm 1026 533 1064 41 60 762 800 Figure 3 4 Decorative Barrier Front Dimensions SIMON B IMPORTANT This...

Page 13: ...to combustibles 2 Alcove Installation C 1 in 25 mm min pipe to combustibles G Drywall 48 in 1219 mm maximum NOTE Consider the mantel or cabinet system to be installed and comply with the necessary re...

Page 14: ...z Term 6 Rear Vent Two 90 elbows Horiz Term 4 Rear Vent One 90 elbow Vert Term 1 Top Vent One 90 elbow Horiz Term 5 No elbows Horiz Term A A A A A A C B B E F D 1 2 in 13 mm min appliance to combustib...

Page 15: ...ble flooring may be installed next to the front of the appliance Drywall 1 2 in 13 mm 1 2 in 13 mm C A B Note If the inside of the framed cavity is to be finished the framing dimensions must include t...

Page 16: ...nd wall shield firestops and construction of the chase may vary with the type of building These instructions are not substitutes for the requirements of local building codes Therefore you MUST check l...

Page 17: ...n or other materials away from vent pipe could cause overheating and fire WARNING Figure 4 2 Staggered Termination Caps H minimum may vary depending on regional snowfall Refer to local codes A Approve...

Page 18: ...to building or the combustion air inlet to any other appliance termination mechanical or non mechanical 9 in 229 mm 12 in 305 mm I clearance to a mechanical powered air supply inlet All mechanical ai...

Page 19: ...Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1 2 648 DVP48 48 1219 34 864 DVP6A 3 to 6 76 to 152 2 1 8...

Page 20: ...gure 4 9 Measure to Top of Last Section of Pipe E Vent Diagrams Figure 4 7 Water Infiltration Prevention 1 4 in max 6 mm W A L L General Rules A maximum of three 90 elbows or six 45 elbows may be used...

Page 21: ...T NDV36 IFT NDV36 IFT NVR NDV42 IFT Installation Manual 2620 980 Rev C 8 20 Figure 4 10 Measure Horizontal and Vertical Termination Clearance to Trapezoid Portion of Cap OVERHANG C E WALL C and E dime...

Page 22: ...s appliances can adapt to SLP series vent pipe when venting off the top of the appliance You must use a DVP SLP24 adapter or a DVP 2SL and two feet of SLP pipe which can only be attached to the applia...

Page 23: ...T 0 0 24 in 610 mm 18 in 457 mm 4 in 102 mm 4 ft 1 22 m 4 ft 1 22 m 6 in 152 mm 6 ft 1 83 m 6 ft 1 83 m 12 in 305 mm 11 ft 3 35 m 11 ft 3 35 m 18 in 457 mm 18 ft 5 49 m 18 ft 5 49 m 24 in 610 mm 25 ft...

Page 24: ...lly H1 V1 H2 H3 Installed Horizontally Installed Vertically H2 V1 Minimum H1 H2 Maximum H1 H2 H3 Maximum 6 in 152 mm 6 ft 1 83 m 3 ft 91 m 12 in 305 mm 11 ft 3 35 m 8 ft 2 4 m 18 in 457 mm 18 ft 5 49...

Page 25: ...NDV42 IFT Installation Manual 2620 980 Rev C 8 20 Three Elbows H2 H1 V2 V1 Elbows Installed Vertically V1 min V1 V2 max H1 H2 max 12 in 305 mm 25 ft 7 62 m 19 ft 5 79 m V1 V2 H1 H2 44 ft 13 41 m Maxi...

Page 26: ...12 30 Ft Vertical Run Figure 4 19 31 60 Ft Vertical Run Install Top Vent Flue Visor No Elbow Configurations Remove screws holding flue visor to firebox top See Figure 4 17 Remove the flue visor Using...

Page 27: ...T NVR NDV42 IFT Installation Manual 2620 980 Rev C 8 20 Three Elbows Maximum horizontal run HTOTAL is 100 of vertical but cannot exceed 26 ft 7 92 m H1 H2 V1 V2 6 ft 1 83 m min 60 ft 18 29 m max V2 V1...

Page 28: ...allation Manual 2620 980 Rev C 8 20 28 Four Elbows Figure 4 21 H1 V2 V1 Elbows Installed Vertically H2 V3 Maximum horizontal run HTOTAL is 100 of vertical but cannot exceed 23 ft 7 01 m V1 V2 V3 6 ft...

Page 29: ...y Note Use DVP Series components only WARNING Risk of Fire This vent configuration is not allowed with NDV42 IFT NDV42L IFT H1 Note To achieve optimum flame appearance the vent configurations shown in...

Page 30: ...ft 610 mm 4 ft 1 2 m 6 ft 1 8 m 3 ft 914 mm 6 ft 1 8 m 9 ft 2 7 m 4 ft 1 2 m 8 ft 2 4 m 12 ft 3 7 m 5 ft 1 5 m 8 ft 2 4 m 15 ft 4 6 m 6 ft 1 8 8 ft 2 4 m 18 ft 5 5 m V1 Minimum H1 Maximum HTotal 1 ft...

Page 31: ...v C 8 20 Figure 4 26 Figure 4 27 Rear Vent Vertical Termination One Elbow Two Elbows VTotal 6 ft 1 83 m min 60 ft 18 29 m max H1 0 min 6 ft 1 83 m max H1 VTotal 6 ft 1 83 m min 60 ft 18 29 m max 0 min...

Page 32: ...lation Manual 2620 980 Rev C 8 20 32 Rear Vent Vertical Termination continued Three Elbows Figure 4 28 VTotal 6 ft 1 83 m min VTotal 60 ft 18 29 m max H1 0 min H1 6 ft 1 83 m max HTotal Maximum horizo...

Page 33: ...s 1 in 25 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm DVP heat shield designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in the...

Page 34: ...p on both sides then both wall shield firestops must have a heat shield refer to Section 12 A attached to them See Section 7 F for information for regarding the instal lation of a horizontal terminati...

Page 35: ...th nails or screws WARNING Risk of Fire DO NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Inst...

Page 36: ...ver plate by removing the two screws holding it to the top of the appliance Remove and discard the cover plate Remove the center insulation plug Cut the metal retaining band and fold the sides out Fol...

Page 37: ...tach the first vent section it will snap into place Slide the insulation gasket onto the vent section up against the appliance and over the tabs Discard the vent cap remove and discard the insulation...

Page 38: ...ces are required for heat management systems installations Provisions must be made in advance to ensure fit within the framing Heat management systems include Heat Zone Gas and Heat Out Gas Other syst...

Page 39: ...ces Lances WARNING Risk of Fire or Explosion Vent sections MUST be installed correctly Improperly installed vent sections could leak or cause appliance to overheat Attach Vent to the Firebox Assembly...

Page 40: ...All unit collar pipe slip section elbow and cap outer flues shall be sealed in this manner unless otherwise stated Assemble Vent Sections SLP Only To attach the first vent component to the starting c...

Page 41: ...ter flues of the slip section can be cut to the desired length Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and slip section with two screws no longe...

Page 42: ...pipe sections extending through the roof as shown in Figure 7 12 Use an elastomeric or silicone sealant with a minimum of 150 F temperature rating to seal the metal roof flashing NOTICE Failure to pr...

Page 43: ...the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 7 15 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shie...

Page 44: ...rom touching the hot cap NOTICE For certain exposures which require superior resistance to wind driven rain penetration a flashing kit and HRC caps are available When penetrating a brick wall a brick...

Page 45: ...tall a shroud with this fireplace See Section 12 B for a list of UL Listed shrouds Follow the instructions included with these optional components Min Base Dim Min Base Dim Min Top Dim Min Top Dim Fig...

Page 46: ...nection when servicing controls Wiring errors could cause improper and dangerous operation Verify proper operation after servicing WARNING Risk of Shock Replace damaged wire with type 105 C rated wire...

Page 47: ...Wiring Diagram This appliance is equipped with an IntelliFire control valve which operates on a 6 volt system B Wiring Requirements FLAME SENSE 2090 012 NG 2090 013 P IGNITER ADAPTER 2326 131 I S 6 P...

Page 48: ...n can be used in conjunction with a wall mounted switch See Figure 8 3 To control fan speed a BC10 Blower Control Wall Switch must be used The power supply for the appliance must be brought into a swi...

Page 49: ...t pressure 10 0 in w c 13 0 in w c Manifold pressure 3 5 in w c 10 0 in w c D High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with yo...

Page 50: ...ter See chart below for correct shutter settings The shutter measurement is taken from the bottom of the tub to the bottom of the thumbscrew See Figure 9 1 Note Adjust air shutter after flame has reac...

Page 51: ...stible Mantel Legs or Wall Projections Figure 10 1 Minimum Vertical and Maximum Horizontal Dimensions for Combustible Mantels Note Mantel Measurement is taken from top of the opening NOT the top of th...

Page 52: ...tel Leg or Wall Projections Acceptable on both sides of opening Non Combustible Mantel Legs or Wall Projections Figure 10 3 Minimum Vertical and Maximum Horizontal Dimensions for Non Combustibles Mant...

Page 53: ...proper burner operation Note It may be helpful to temporarily remove Log 5 to place the mineral wool If removed replace log according to log placement instructions Mineral wool is shipped with this g...

Page 54: ...h care Inspect the gasket to ensure it is undamaged and inspect the glass for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken o...

Page 55: ...left end of Log 4 into the flat spot on Log 2 and then resting the right end or nose of Log 4 on the flat spot on Log 1 Figure 3 shows locations of flat spots Figure 4 shows Log 4 installed 4 4 SIZE 3...

Page 56: ...of Log 5 is positioned toward the front of the appliance with the two slots on the back side resting on the bent lip of the hearth pan See Figure 6 Slide Log 5 toward the right until it contacts the...

Page 57: ...in 187 mm 11 3 8 in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart E...

Page 58: ...ld is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than...

Page 59: ...S 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm...

Page 60: ...ation Cap 7 1 4 in 12 in 305 mm 184 mm 5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41...

Page 61: ...87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm DVP HRC ZC SS NOT APPROVED FOR ALL UNITS Not approved for NDV42 IFT Figure 12 5 PVI SLP B Vent Components DECORATIVE...

Page 62: ...SLEEVE 48 A Vent Components Diagrams continued PVV SLP Vertical Power Vent Note A wire harness is required to power the PVV SLP and connect it to the appliance It is ordered separately from the PVV S...

Page 63: ...mm 13 5 8 IN 346 mm EFFECTIVE LENGTH 32 IN 813 mm MIN 35 IN 889 mm MAX Figure 12 7 PVI SLP B Vent Components PVI SLP B Power Vent Inline SLP LPC SLP Low Profile Cap Approved for use with PVI SLP B on...

Page 64: ...21 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 4 IN 159 mm Front View Top View Side View PVLP BEK Brick Kit Note Wire harnesses required to power the PVLP SLP connect to the appliance and are ordered separat...

Page 65: ...Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter 6 1 2 in 165 mm 25 3 16 in 640 mm 8 1 16 in 205 mm 10 7 8 in 276...

Page 66: ...kness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 13...

Page 67: ...n 356 mm 12 1 2 in 318 mm 12 in 305 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TVHW Vertical Termination Cap DVP FBHT Hori...

Page 68: ...20 in 508 mm 17 in 432 mm 9 3 8 in 238 mm TCG375 Terra Cotta Cap LDSCP M Shroud Leg Multipack not shown See your Heatilator dealer for a complete listing of optional components B Optional Components C...

Page 69: ...may be added Contact your dealer to order the correct refractory kit Detailed installa tion instructions are included with the refractory kit Remote Controls Wall Controls and Wall Switches After a q...

Reviews: