background image

 

Heatilator • CNXT Series • 4000-011 Rev N • 11/05 

45

With proper installation, operation and maintenance your gas appliance will provide years of trouble-free service. If you do 
experience a problem, this troubleshooting guide will assist a qualifi ed service person in the diagnosis of a problem and the 
corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed service technician.

A. Intellifi re Ignition System

14

14  

Troubleshooting 

Symptom

Possible Causes

Corrective Actions

1.

The ignitor/module makes 
noise, but no spark.

A.

Incorrect wiring.

Verify “S” wire (white) for sensor and “I” wire (orange) for ignitor are 
connected to the correct terminals on the module and the pilot assembly. 
Reversed wires at the module may cause the system to make a sparking 
noise, but the spark may not be present at pilot hood.

B.

Loose connections or 
electrical shorts in the wiring.

Verify there are no loose connections or electrical shorts in wiring from 
module to pilot assembly. The rod closest to the pilot hood should be ignitor. 
Verify connections underneath pilot assembly are tight; also verify the 
connections are not grounding out to the metal chassis, pilot burner, pilot 
enclosure, mesh screen if present, or any other metal object.

C.

Ignitor gap is too large.

Verify gap of ignitor to pilot hood. The gap should be approximately .17 in. or 
1/8 in.

D.

Faulty module.

Turn ON/OFF rocker switch or wall switch to OFF position. Remove ignitor 
wire “I” from module. Place ON/OFF rocker switch or wall switch in ON 
position. Hold ground wire about 3/16 in. away from “I” terminal on module. If 
there is no spark at “I” terminal, module must be replaced. If there is a spark 
at “I” terminal, module is fi ne. Inspect pilot assembly for shorted sparker wire 
or cracked insulator around electrode.

2.

Pilots won’t light, there is no 
noise or spark.

A.

Transformer installed 
correctly.

Verify that transformer is installed and plugged into module. Check voltage of 
transformer under load at space connection on module with ON/OFF switch in 

B.

A shorted or loose 
connection in wiring 
confi guration or wiring 
harness.

Remove and reinstall the wiring harness that plugs into module. Verify there is 
a tight fi t. Verify pilot assembly wiring to module. Remove and verify continuity 
of each wire in wiring harness.

C.

Improper wall switch wiring. Verify wall switch is wired correctly.

D.

Module not grounded.

Verify black ground wire from module wire harness is grounded to metal 
chassis of appliance.

E.

Faulty module.

Turn ON/OFF rocker switch or wall switch to OFF position. Remove ignitor 
wire “I” from module. Place ON/OFF rocker switch or wall switch in ON 
position. Hold ground wire about 3/16  in. away from “I” terminal on module. If 
there is no spark at “I” terminal module must be replaced. If there is a spark at 
“I” terminal, module is fi ne. Inspect pilot assembly for shorted sparker wire or 
cracked insulator around electrode.

Summary of Contents for CNXT70IH

Page 1: ...ighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the re department Installation and service must be performed by a quali ed installer service agency or...

Page 2: ...ation on appliance Dealership purchased from Dealer phone Notes We recommend that you record the following pertinent information about your appliance Listing Label Information Location The model infor...

Page 3: ...ion Cap 31 E Assemble and Install Storm Collar 31 9 Gas Information 32 A Fuel Conversion 32 B Gas Pressure 32 C Gas Connection 32 D High Altitude Installations 33 10 Electrical Information 34 A Recomm...

Page 4: ...equirements which refers to 15 U S Code USC 2063 stating Such certi cate shall accompany the product or shall otherwise be furnished to any distributor or retailer to whom the product is delivered Som...

Page 5: ...anometer Voltmeter Tape measure Non corrosive leak check solution 1 2 3 4 in length 6 or 8 Self drilling screws One 1 4 in female connection for optional fan Keep appliance dry Mold or rust may cause...

Page 6: ...re ect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Fire Risk Provide adequate...

Page 7: ...erature caulk to seal gaps Gas line holes and other openings should be caulked with high temp caulk or stuffed with unfaced insulation If the appliance is being installed on a cement slab we recommend...

Page 8: ...wall 0 in 36 in 914 mm Combustible Object 1 2 in 13 mm 1 2 in 13 mm D 0 in to level of standoffs Figure 3 4 Clearances to Combustibles Model A Rough Opening Width B Rough Opening Height C Rough Openin...

Page 9: ...nt Termination Minimum Clearances Fire Risk Explosion Risk Do not pack air space with insulation or other materials Maintain vent clearance to combustibles as speci ed WARNING Failure to keep insulati...

Page 10: ...nly permitted if veranda porch deck or balcony is fully open on a minimum of 2 sides beneath the oor N Vertical clearance between two horizontal termination caps 12 in 30 cm minimum O Horizontal clear...

Page 11: ...l to 8 1 2 in horizontal run and 8 1 2 in vertical run A length of straight pipe is allowed between two 45 elbows see Figure 5 1 ALL vent configuration specifications MUST be followed This product is...

Page 12: ...l H measurement for each 45 elbow installed horizontally A maximum of three 90 elbows or six 45 elbows may be used in any vent con guration Some elbows may be installed horizontally See Figure 5 6 Elb...

Page 13: ...t max 7 62 m Figure 5 4 Minimum Installation Requirements for Two 45 Elbows Top Vent Horizontal Termination Top Vent Horizontal Termination Three Vertical Elbows See Figure 5 6 for information about i...

Page 14: ...6 Two or Three Elbows some Horizontal Note Subtract 3 ft 914 mm from the total horizontal measurement for each 90 elbow installed horizontally Subtract 1 1 2 ft 457 mm from the total horizontal measur...

Page 15: ...max Top Vent Vertical Termination No Elbows Top Vent Vertical Termination Two Elbows Figure 5 7 Vertical Termination No Elbows 12 ft 3 66 m min 60 ft 18 29 m max Maximum horizontal run is 100 of verti...

Page 16: ...6 m min 60 ft 18 29 m max Maximum horizontal run is 100 of vertical but cannot exceed 26 ft 7 92 m Figure 5 9 Vertical Termination Three Elbows some horizontal Note Subtract 3 ft 914 mm from the total...

Page 17: ...Table 5 4 H1 Max Total Vert V Min Total Horiz H1 H2 0 1ft 0 31 m 1 ft 31 m 4 ft 1 22 m 2 ft 61 m 1 ft 31 m 4 ft 1 22 m 3 ft 91 m 1 ft 31 m 6 ft 1 83 m 0 1ft 0 31 m 2 ft 61 m 6 ft 1 83 m 2 ft 61 m 2 ft...

Page 18: ...457 mm from the total horizontal measurement for each 45 elbow installed horizontally Table 5 5 H1 Max Total Vert V Min Total Horiz H1 H2 H3 0 1 ft 31 m 4 ft 1 22 m 1ft 31 m 1 ft 31 m 4 ft 1 22 m 2 f...

Page 19: ...n Two Elbows Figure 5 15 Vertical Termination Two Elbows Rear Vent Vertical Termination One Elbow 12 ft 3 66 m min 60 ft 18 29 m max 0 min 6 ft 1 83 m max Figure 5 14 Vertical Termination One Elbow No...

Page 20: ...05 12 ft 3 66 m min 60 ft 18 29 m max 0 min 6 ft 1 83 m max Maximum horizontal run is 100 of vertical but can not exceed 26 ft 7 92 m Figure 5 16 Vertical Termination Three Vertical Elbows Rear Vent...

Page 21: ...rances to Combustibles Fire Risk Explosion Risk Maintain vent clearance to combustibles as speci ed Do not pack air space with insulation or other materials Failure to keep insulation or other materia...

Page 22: ...eiling Firestop 3 fasteners per side Attic insulation shield installed below ceiling Attic insulation shield installed above ceiling Bend tabs in around pipe Figure 6 5 Installing the Attic Insulation...

Page 23: ...r Figure 7 4 Remove Inner Cover Plate Remove four screws holding the outer collar to the appliance top See Figure 7 4 Remove the outer collar Note Once the vent cap has been removed it CANNOT be reatt...

Page 24: ...r Cover Plate Figure 7 8 Remove Inner Cover Plate Remove four screws holding the inner cover plate to the appliance back See Figure 7 8 Remove the inner cover plate and white gasket Place the inner co...

Page 25: ...7 7 on the appliance top Use four screws to hold the outer cover plate in place See Figure 7 13 Figure 7 14 Cover Plate Locate the cover plate removed in the rst step and place on top of top pan heat...

Page 26: ...es and Framing Section 6 for hole location Place the appliance into position Level the appliance from side to side and front to back Shim the appliance as necessary It is acceptable to use wood shims...

Page 27: ...e section to con rm it has completely locked into place Assemble Pipe Sections Insert the inner ue of section A into the ared inner ue of section B Start the outer ue of section A over the outer ue of...

Page 28: ...attached by tting another pipe section to it and snapping it together as normal Assemble Slip Sections The outer ue of the slip section should slide over the outer ue of the pipe section and into inne...

Page 29: ...rotate either section see Figure 8 10 so that the seams on both pipe sections are aligned see Figure 8 11 They can then be carefully pulled apart Figure 8 8 Securing Vertical Pipe Sections Figure 8 9...

Page 30: ...will need to be cut to the thickness of the wall and be attached to the wall shield restop The small leg on the extended heat shield should rest on the top of the vent pipe section to properly space i...

Page 31: ...ake sure the collar is tight against the pipe section See Figure 8 16 Slide the assembled storm collar down the pipe section until it rests on the roof ashing see Figure 8 13 Caulk around the top of t...

Page 32: ...nwealth of Massachusetts approved 1 2 in 13 mm T handle manual shut off valve and exible gas connector are connected to the 1 2 in 13 mm control valve inlet If substituting for these components please...

Page 33: ...is complete all connections must be tightened and checked for leaks with a commercially available non corrosive leak check solution Be sure to rinse off all leak check solution following testing Fitt...

Page 34: ...e by removing any excess wire length Low voltage and 110 VAC voltage cannot be shared within the same wall box C Intelli re Ignition System Wiring This appliance requires a 110 VAC supply to the appli...

Page 35: ...eed control Connect the white wire from the junction box to the white wire from the variable speed control Label all wires prior to disconnection when servicing controls Wiring errors can cause improp...

Page 36: ...e junction box receptacle to the outer shell rotate the junction box inward to disengage it from the outer shell see Figure 10 2 Pull the electrical wires from outside the appliance through this openi...

Page 37: ...rom fireplace opening to perpendicular wall B 48 in 1219 mm max Mantel Leg or Perpendicular Wall Top of Appliance Drywall A B Figure 11 2 Mantel Leg or Wall Projections Acceptable on both sides of ope...

Page 38: ...Install approved accessories per instructions included with accessories Refer to Section 16 D Clean the Appliance Clean vacuum any sawdust that may have accumulated in side the rebox or underneath in...

Page 39: ...og Assembly Set the Logs CNXT70I 36 in Place LEFT FRONT LOG on the far left grate bar so the notch on the log sits on the horizontal portion of the grate bar and the body of the log is on the grate bu...

Page 40: ...own Place LEFT TOP LOG so that the burnt tip of the log sits against the left center grate bar The body of the log should rest on the white groove on the left center log and the groove in the back log...

Page 41: ...th attachment clips and press rmly in place I Grilles and Trim Install optional marble and brass trim surround kits using the installation instructions included with them Marble brass brick tile or ot...

Page 42: ...en supplied with an integral barrier to prevent direct contact with the fixed glass panel Do NOT operate the appliance with the protective barrier removed Contact your dealer or Hearth Home Technologi...

Page 43: ...appliance WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life FOR YOUR SAFETY READ BEFORE LIGHTING 33631D C U...

Page 44: ...quids clear of appliance Do NOT store ammable materials in the vicinity of the appliance Do NOT use gasoline lantern fuel kerosene charcoal lighter uid or similar liquids in this appliance Combustible...

Page 45: ...in or 1 8 in D Faulty module Turn ON OFF rocker switch or wall switch to OFF position Remove ignitor wire I from module Place ON OFF rocker switch or wall switch in ON position Hold ground wire about...

Page 46: ...s rmly connected to module D Damaged pilot assembly or dirty sensor rod Verify that ceramic insulator around the sensor rod is not cracked damaged or loose Verify connection from sensor rod to white s...

Page 47: ...ompartment Burner burner ports Risk of Fire Delayed ignition or explosion Exposure to combustion fumes Odors WARNING Handle glass assembly with care Note Clean glass after initial 3 4 hours operation...

Page 48: ...rpage corrosion or perforation Sand and repaint as necessary 2 Replace appliance if rebox has been perforated Burner ignition and operation 1 Verify burner is properly secured and aligned with pilot o...

Page 49: ...ppliance Dimensions 16 16 Reference Materials B 38 in 965 mm 1 1 2 in 38 mm 26 1 2 in 673 mm 2 1 2 in 64 mm 6 in 152 mm 14 3 8 in 365 mm Electric Access 3 5 8 in 92 mm 6 3 8 in 162mm Gas Line Access 9...

Page 50: ...S Ceiling Firestop DVP WS Wall Shield Firestop 12 in 14 in 1 in 8 in 6 in 10 in 1 1 2 in 5 in 12 in DVP HVS Vent Support UP DVP AS Attic Shield 10 in 24 in 4 in 5 in DVP AD1 Adapter DVP AD2 Adapter 4...

Page 51: ...ap 15 1 8 in 14 in 8 in Max Effective Length Minimum Maximum Term Cap Effective Length Effective Length TRAP1 4 1 8 in 5 5 8 in TRAP2 6 3 4 in 10 5 8 in DVP TRAP1 Horizontal Termination Cap Kit DVP TR...

Page 52: ...13 1 4 in 24 5 8 in 27 1 2 in RF6M Roof Flashing Multi pak 31 in 24 5 8 in 13 1 4 in RF12M Roof Flashing Multi pak 7 1 4 in 5 1 4 in 12 1 2 in DVP TVHW Vertical Termination Cap High wind BEK Trap Cap...

Page 53: ...Heatilator CNXT Series 4000 011 Rev N 11 05 53 This page intentionally left blank...

Page 54: ...inadequate ventilation or drafting caused by tight sealing construction of the structure air handling devices such as exhaust fans or forced air furnaces or other causes 5 use of fuels other than thos...

Page 55: ...D O N O T D I S C A R D This product may be covered by one or more of the following patents United States 4593510 4686807 4766876 4793322 4811534 5000162 5016609 5076254 5113843 5191877 5218953 52634...

Reviews: