Heatiator IDV4833IH Owner'S Manual Download Page 12

Heatilator  •  ICON DV-IDV Series  •  4042-575  •  Rev. S  •  5/11

12

Initial Break-in Procedure

•  The fireplace should be run three to four hours 

continuously on high.

• Turn 

the 

fi replace off and allow it to completely cool.

• Remove 

fi xed glass assembly. See Section 15.J.

• Clean 

fi xed glass assembly. See Section 3.

• Replace 

the 

fi xed glass assembly and run continuously 

on high an additional 12 hours.

This cures the materials used to manufacture the fi re-
place.

NOTICE! 

Open windows for air circulation during fi replace 

break-in.

 

•  Some people may be sensitive to smoke and 

odors.

 

•  Smoke detectors may activate.

I.  After Fireplace is Lit

K. Frequently Asked Questions

ISSUE

SOLUTIONS

Condensation on the glass

This is a result of gas combustion and temperature variations. As the appliance warms, this 
condensation will disappear.

Blue fl ames

This is a result of normal operation and the fl ames will begin to yellow as the appliance is allowed 
to burn for 20 to 40 minutes.

Odor from appliance

When fi rst operated, this appliance may release an odor for the fi rst several hours. This is caused 
by the curing of materials from manufacturing. Odor may also be released from fi nishing materials 
and adhesives used near the appliance. These circumstances may require additional curing 
related to the installation environment.

Film on the glass

This is a normal result of the curing process of the paint and logs. Glass should be cleaned within 
3 to 4 hours of initial burning. A non-abrasive cleaner such as gas appliance glass cleaner may be 
necessary. See your dealer.

Metallic noise

Noise is caused by metal expanding and contracting as it heats up and cools down, similar to the 
sound produced by a furnace or heating duct. This noise does not affect the operation or longevity 
of the appliance.

Is it normal to see the pilot 
fl ame burn continually?

In an IntelliFire ignition system (IPI), the pilot fl ame should turn off when appliance is turned off. 
Some optional control systems available with IPI models may allow pilot fl ame to remain lit.  In a 
standing pilot system the pilot will always stay on. 

J. Flame Adjustment Control

Some appliances come equipped with a high/low fl ame 
adjustment control.

•  Open control access panel
•  Compare your valve to Figures 2.4 & 2.5.
• Adjust 

the 

fl ame by turning knob as indicated in the photo 

matching your valve.

HI

LO

Indicator

Indicator

HI

LO

Figure 2.4 

DEXEN Valve - IntelliFire Ignition System

Figure 2.5 

SIT Valve - Standing Pilot Ignition System

Summary of Contents for IDV4833IH

Page 1: ...instructions and the manufactured home construction and safety standard Title 24 CFR Part 3280 or Standard for Installation in Mobile Homes CAN CSA Z240MH This appliance is only for use with the type s of gas indicated on the rating plate DO NOT DISCARD THIS MANUAL CAUTION Important operating and maintenance instructions included Leave this manual with party responsible for use and operation Read ...

Page 2: ...place Model Number Not Not for for use use with with solid solid fuel fuel Ne Ne doit doit pas pas entre entre utilise utilise avec avec un un combustible combustible solide solide This This appliance appliance must must be be installed installed in in accordance accordance with with local local codes codes if if any any if if not not follow follow ANSI ANSI Z223 1 Z223 1 in in the the USA USA or ...

Page 3: ...ies Needed 16 D Inspect Appliance and Components 16 5 Framing and Clearances A Select Appliance Location 17 B Construct the Appliance Chase 18 C Clearances 18 D Mantel and Wall Projections 19 6 Termination Locations A Vent Termination Minimum Clearances 20 7 Vent Information and Diagrams A Approved Pipe 22 B Vent Table Key 22 C Use of Elbows 22 D Measuring Standards 22 E Vent Diagrams 23 8 Vent Cl...

Page 4: ...J Glass Panel Assembly 48 K Decorative Firescreen Refractory Shields and Lower Decorative Front Face 49 L Installing External Refractories 50 M Air Shutter Setting 51 16 Troubleshooting A Intellifire Ignition System 52 17 Reference Materials A Appliance Dimension Diagram 54 B Vent Components Diagrams 55 C Service Parts 60 D Optional Components 67 E Contact Information 68 ...

Page 5: ...new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier The warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupancy date The warranty period for parts and la...

Page 6: ... RI QRUPDO XVH V D KHDWLQJ DSSOLDQFH VRPH FKDQJHV LQ FRORU RI LQWHULRU DQG H WHULRU VXUIDFH ILQLVKHV PD RFFXU 7KLV LV QRW D IODZ DQG LV QRW FRYHUHG XQGHU ZDUUDQW DPDJH WR SULQWHG SODWHG RU HQDPHOHG VXUIDFHV FDXVHG E ILQJHUSULQWV DFFLGHQWV PLVXVH VFUDWFKHV PHOWHG LWHPV RU RWKHU H WHUQDO VRXUFHV DQG UHVLGXHV OHIW RQ WKH SODWHG VXUIDFHV IURP WKH XVH RI DEUDVLYH FOHDQHUV RU SROLVKHV 5HSDLU RU UHSODFHP...

Page 7: ...E AS A PRIMARY HEAT SOURCE This appliance is tested and approved as either supplemental room heat or as a decorative appliance It should not be fac tored as primary heat in residential heating calculations D High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or authorities having jurisdiction When installin...

Page 8: ...eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage installed in ac...

Page 9: ...tion To prevent unintended operation when not using your fireplace for an extended period of time summer months vacations trips etc Remove batteries from remote controls Turn off wall controls Unplug 3 volt adapter plug and remove batteries on IPI models Turn off gas controls valve on standing pilot models 2 2 Operating Instructions User Guide HOT SURFACES Glass and other surfaces are hot during o...

Page 10: ...not present or help is needed to properly install one For more information refer to the instructions supplied with your decorative door or front F Remote Controls Wall Controls and Wall Switches Follow the instructions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protection lockout feature Keep remote controls ou...

Page 11: ... by hand B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT LINE VOLT AGE 110 120 VAC OR 220 240 VAC TO THE CONTROL VALVE Improper installat...

Page 12: ...so be released from finishing materials and adhesives used near the appliance These circumstances may require additional curing related to the installation environment Film on the glass This is a normal result of the curing process of the paint and logs Glass should be cleaned within 3 to 4 hours of initial burning A non abrasive cleaner such as gas appliance glass cleaner may be necessary See you...

Page 13: ...roperly maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surrounds Fronts Frequency Annually By Homeowner Tools needed Protective gloves stable work surface Assess condition of screen and replace as necessary Inspect for scratches dents or other damage and repair as necessary Check that louvers are not b...

Page 14: ...e when exposed to heat Confirm there is no damage to glass or glass frame Replace as necessary Verify that fixed glass assembly is properly retained and attachment components are intact and not damaged Replace as necessary Burner Ignition and Operation Frequency Annually By Qualified Service Technician Tools needed Protective gloves vacuum cleaner whisk broom flashlight voltmeter indexed drill bit...

Page 15: ...ed Optional Wall Switch Vertical Termination Cap SECTION 10 Storm Collar SECTION 10 Attic insulation shield not shown must be used here to keep insulation away from vent pipe if attic is insulated SECTION 8 Vent pipe penetrates roof preferably without affecting roof rafters SECTION 8 A Typical Appliance System NOTICE Illustrations and photos reflect typical installations and are for design purpose...

Page 16: ...eeded Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Non corrosive leak check solution Hammer Phillips screwdriver Gloves Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Level Reciprocating saw Manometer Flat blade screwdriver 1 2 3 4 in length 6 or 8 Self drilling screws ...

Page 17: ...and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Top Vent One 90 Elbow Horiz Term Top Vent One 90 Elbow Horiz Term A A D C E B B 1 1 2 in 38 mm min appliance to combustibles Alcove Installation F A Drywall A B C D E ...

Page 18: ...filtration barriers should be installed in the chase as per regional codes for the rest of the home Additionally in regions where cold air infiltration may be an issue the inside surfaces may be sheetrocked and taped for maximum air tightness Figure 5 2 Clearances to Combustibles C Clearances NOTICE Install appliance on hard metal or wood surfaces extending full width and depth DO NOT install dire...

Page 19: ...nimum clear ances to combustibles as specified Framing or finishing material closer than the minimums listed must be construct ed entirely of non combustible materials i e steel studs concrete board etc Figure 5 3 Minimum Vertical and Maximum Horizontal Dimensions 1 in 25 mm min to perpendicular wall A 7 75 in 159 mm min from fireplace opening to perpendicular wall B Mantel Leg or Perpendicular Wa...

Page 20: ...3 25 Over 20 12 to 21 12 8 0 3 ft minimum in snow regions Storm Collar Roof Flashing 6 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire WARNING Gas Wood or Fuel Oil Termination Cap B Gas Termination Cap A If ...

Page 21: ... N Vertical clearance between two horizontal termination caps 12 in 30 cm minimum O Horizontal clearance between two horizontal termination caps 12 in 30 cm minimum P 6 Non vinyl sidewalls 12 Vinyl sidewalls Q 18 Non vinyl soffit and overhang 42 Vinyl soffit and overhang R 8 ft D E B L C V V B F V B V V B X A J Fixed Closed M V K X RESTRICTION ZONE TERMINATION NOT ALLOWED AIR SUPPLY INLET X GAS ME...

Page 22: ... diagonal is equal to 8 1 2 in 216 mm horizontal run and 8 1 2 in 216 mm vertical run A length of straight pipe is allowed between two 45º elbows see Figure 7 1 Figure 7 1 Using Two 45 Elbows 7 7 Vent Information and Diagrams B Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams D Measuring Standards Vertical and horizontal measurements listed in the vent d...

Page 23: ...re 7 9 E Vent Diagrams Figure 7 3 One Elbow 1 Top Vent Horizontal Termination V1 min V1 max H1 max ft m ft m ft m 1 0 30 25 in 635 mm 1 5 0 46 18 5 49 2 0 61 25 7 62 25 7 62 25 7 62 Elbows may be placed back to back anywhere in the system as long as the first 90 elbow is a starter elbow except as shown in Figure 7 4 When penetrating a combustible wall a wall shield firestop must be installed When ...

Page 24: ... installations A 6 in 152 mm section of straight pipe may need to be attached to the appliance before a 90º elbow to allow the vent pipe to clear the top standoffs 1 Top Vent Horizontal Termination continued Figure 7 4 Two 45 Elbows replacing One 90 Elbow V1 min V1 max H1 H2 max H1 H2 H3 max ft m ft m ft m ft m 1 5 0 46 18 5 49 18 5 49 2 0 61 25 7 62 25 7 62 25 7 62 25 7 62 25 7 62 ...

Page 25: ...or ICON DV IDV Series 4042 575 Rev S 5 11 25 Figure 7 6 1 Top Vent Horizontal Termination continued Three Elbows H1 V1 V2 H2 Installed Vertically V1 min V1 V2 max H1 H2 max ft m ft m ft m 1 0 30 24 7 32 19 5 79 ...

Page 26: ...ctor should be used 12 ft 3 66 m min 60 ft 18 29 m max 12 ft 3 66 m min 60 ft 18 29 m max Maximum horizontal run is 100 of vertical but cannot exceed 26 ft 7 92 m Figure 7 7a 12 ft to 30 ft Vertical Run Figure 7 7b 31 ft to 60 ft Vertical Run Install Flue Restrictor Remove screws from flue firebox top Using the screws removed install flue restrictor according to your installation requirements See ...

Page 27: ...CON DV IDV Series 4042 575 Rev S 5 11 27 Figure 7 9 2 Top Vent Vertical Termination continued Three Elbows 12 ft 3 66 m min 60 ft 18 29 m max Maximum horizontal run is 100 of vertical but cannot exceed 26 ft 7 92 m ...

Page 28: ...construction SLP pipe A wall shield firestop must be placed on each side of an interior wall A minimum 1 1 2 in 38 mm overlap of attached heat shields must be maintained DVP pipe A wall shield firestop is required on one side only on interior walls If your local inspector requires a wall shield firestop on both sides then both wall shield firestops must have a heat shield attached to them See Sect...

Page 29: ...s Frame an opening 10 in by 10 in 254 mm by 254 mm whenever the vent penetrates a ceiling floor see Figure 8 3 Frame the area with the same sized lumber as used in ceiling floor joist The ceiling firestop may be installed above or below the ceiling joists when installed with a attic insulation shield It must be under joists between floors that are not insulated Refer to Figure 8 4 Secure with thre...

Page 30: ...ain the air space between the pipe and the shield Set the shield on the ceiling firestop and attach to the firestop Bend all tabs inward 90 around the top of the shield These tabs must be used to prevent blown insulation from getting between the shield and vent pipe and to maintain air space clearance Figure 8 5 Attic Insulation Shield Vaulted Ceiling Installation Remove one shield from box NOTICE...

Page 31: ...e The diagram shows how to properly position and secure the appliance see Figure 9 1 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing Level the appliance from side to side and front to back Shim the appliance as necessary It is acceptable to use wood shims underneat...

Page 32: ...rate inner pipe For 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe Commercial Multi family Multi level exceeding two stories or High Rise Applications All o...

Page 33: ...d cap outer flues shall be sealed Continue adding pipe as necessary following instructions in Assemble Pipe Sections NOTICE If slip section is too long the inner and outer flues of the slip section can be cut to the desired length Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and slip section with two screws no longer than 1 2 in 13 mm using the pi...

Page 34: ...inimum height from roof to lowest discharge opening 24 in min 610 mm Roof Pitch H Min Ft Roof Pitch H Min Ft Flat to 6 12 1 0 Over 11 12 to 12 12 4 0 Over 6 12 to 7 12 1 25 Over 12 12 to 14 12 5 0 Over 7 12 to 8 12 1 5 Over 14 12 to 16 12 6 0 Over 8 12 to 9 12 2 0 Over 16 12 to 18 12 7 0 Over 9 12 to 10 12 2 5 Over 18 12 to 20 12 7 5 Over 10 12 to 11 12 3 25 Over 20 12 to 21 12 8 0 3 ft minimum in...

Page 35: ...es 10 13 10 14 Wrap the storm collar around the exposed pipe section closest to the roof and align brackets Insert a bolt provided through the brackets and tighten the nut to complete the storm collar assembly Make sure the collar is tight against the pipe section Slide the assembled storm collar down the pipe section until it rests on the roof flashing Caulk around the top of the storm collar Fig...

Page 36: ...trimmed A minimum 1 1 2 in 38 mm overlap MUST be maintained Use an extended heat shield if the finished wall thickness is greater than 7 1 4 in 184 mm The extended heat shield may need to be cut to length maintaining sufficient length for a 1 1 2 in 38 mm overlap between heat shields Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended ...

Page 37: ...ing material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Burns Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For certain exposures which requir...

Page 38: ...ologies fireplace systems and termination caps The shrouds must be constructed from a minimum 018 in 26 ga thick aluminized steel The wire mesh is optional but recommended and must be 018 in thick minimum 1 2 in mesh A HHT Shrouds You may install a shroud with this fireplace See Section 17 D for a list of UL Listed shrouds Follow the instructions included with these optional components Min Base Di...

Page 39: ...Width Min Base Dimension Minimum Height Figure 11 2 Roofed Style Shroud Dimensions Roofed Style Shroud may be used with DVP TV DVP TVHW SLP TVHW Mailbox Style Shroud may be used with DVP TV DVP TVHW SLP TVHW Min Base Dims in 20 x 20 mm 508 x 508 Min Height in 18 mm 457 Min Base Dims in 20 x 20 mm 508 x 508 Min Height in 18 mm 458 Min Opening Width in 14 mm 356 Min Opening Height in 10 mm 254 ...

Page 40: ...nformation Gas Pressure Natural Gas Propane Minimum inlet pressure 5 0 in w c 11 0 in w c Maximum inlet pressure 10 0 in w c 13 0 in w c Manifold pressure 3 5 in w c 10 0 in w c Note Have the gas supply line installed in accordance with local codes if any If not follow ANSI 223 1 Installation should be done by a qualified installer approved and or licensed as required by the locality In the Common...

Page 41: ...emove batteries before using the transformer and unplug the transformer before installing the batteries Battery polarity must be correct or module damage will occur C Optional Accessories Requirements This appliance may be used with a wall switch wall mounted thermostat and or a remote control Wiring for optional Hearth Home Technologies ap proved accessories should be done now to avoid re constru...

Page 42: ...n box and bracket to appliance with two screws Figure 13 2 Remove Two Screws From Bracket If the junction box is being wired from the INSIDE of the appliance Remove one screw that attaches access panel to column See Figure 13 3 Remove two screws that attach junction box to junction box bracket See Figure 13 4 Feed an appropriate length of romex through plastic romex connector Reattach junction box...

Page 43: ...antel Legs or Wall Projections 0 in 0 in 0 in Finish wall material may be combustible Top and Sides High Temperature Sealant 300 F 149 C min Top and Side Seal Joint A B Shaded area noncombustible materials only A B inches 44 3 8 46 1 2 mm 1127 1181 inches 48 7 8 60 1 2 mm 1241 1537 IDV4833 IDV6247 Model B Facing Material Metal front faces may be covered with non combustible materials only Facing a...

Page 44: ...ishing Material Finishing Material Finished Opening Width X Finished Opening Width Finished Opening Height X Y inches 33 34 1 2 mm 838 876 inches 47 39 mm 1194 991 IDV4833 IDV6247 Model C Non combustible Finishing Material Figure 14 4 Finished Fireplace Opening ...

Page 45: ...om the kit Use the three screws removed from the cover plate Return to Heat Zone Gas instructions G Refractory All refractory internal to the firebox comes pre installed See Section 15 L for installation of bottom front and side refractories B Remove Fixed Glass Assembly See Section 15 J C Remove Materials Shipped Inside Firebox Three top logs are shipped inside the firebox D Clean the Appliance C...

Page 46: ...g with white notched area in top of base log Repeat for each top log See Figures 15 1 through 15 6 Figure 15 1 Placing First Top Log 4042 356 IDV4833 Figure 15 2 Placing Second Top Log 4042 355 IDV4833 Figure 15 3 Placing Third Top Log 4042 354 IDV4833 Figure 15 4 Placing First Top Log 4042 362 IDV6247 Figure 15 5 Placing Second Top Log 4042 355 IDV6247 Figure 15 6 Placing Third Top Log 4042 356 I...

Page 47: ...nd lava rock are shipped with this gas appli ance Place rockwool on burner in front of front base log Place lava rock on hearth refractory not burner as desired See Figure 15 7 WARNING Risk of Explosion Follow rockwool placement instructions DO NOT place rockwool directly over burner ports Replace rockwool material annually Improperly placed rockwool interferes with proper burner operation ...

Page 48: ... Remove three outer refractory pieces as per instructions in Section 15 L Remove the lower decorative front face by removing the four screws attaching the face See Figure 15 16 Remove the left and right refractory shields by removing the three screws holding each shield See Figure 15 15 Remove the decorative firescreen mesh Release the screen rod from the center screen support Remove the right sid...

Page 49: ... the left and right screen rod supports to ensure the screen is locked closed See Figure 15 13 Figure 15 11 Place Left End of Screen Rod Figure 15 12 Place Right End of Screen Rod Eyelet Rod Support Figure 15 13 Ensure Eyelets are Outside the Rod Support Figure 15 14 Place Center of Screen Rod Figure 15 15 Install Refractory Shields Figure 15 16 Install Lower Decorative Front Face Place the center...

Page 50: ...op See Figure 15 18 Insert Pin Notch Figure 15 18 Insert Pin into Top Frame Insert Pin Swedge Figure 15 20 Insert Pin into Bottom Frame Install rod with swedge Figure 15 19 in hole in glass frame bottom See Figure 15 20 Repeat for the left side refractory panel Swedge Figure 15 19 Swedge Bottom Front Hearth Refractory The firescreen must be pulled up to install the hearth refractory Figure 15 21 S...

Page 51: ...e time of installation The air shutter is set at the factory for minimum vertical vent run Adjust air shut ter for longer vertical runs See Figure 15 24 Pull the air shutter knob up to close Push the air shutter knob down to open NOTICE If sooting occurs provide more air by opening the air shutter Open Closed Figure 15 24 Air Shutter Adjustment ...

Page 52: ... shorted or loose connection in wiring configuration or wiring harness Remove and reinstall the wiring harness that plugs into module Verify there is a tight fit Verify pilot assembly wiring to module Remove and verify continuity of each wire in wiring harness Replace any damaged components C Improper wall switch wiring Verify that 110 VAC power is ON to junction box D Module not grounded Verify b...

Page 53: ...nsing rod should glow shortly after ignition Verify correct pilot orifice is installed and gas inlet is set to pressure specifications C Module is not grounded Verify module is securely grounded to metal chassis of appliance Verify that wire harness is firmly connected to the module D Damaged pilot assembly or contaminated flame sensing rod Verify that ceramic insulator around the flame sensing ro...

Page 54: ... in 57 mm F 21 1 2 in 546 mm A B C D E F in 46 1 2 33 27 5 8 34 1 2 45 1 4 44 3 8 mm 1181 838 702 876 1149 1127 in 60 1 2 47 41 5 8 39 49 3 4 48 7 8 mm 1537 1194 1057 991 1264 1241 Model IDV4833I IDV6247I A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For framing dimensions and clearances refer to Section 5 Figure 17 1 Appliance Dimensions ...

Page 55: ... Effective Height Length 10 1 2 in 267 mm 10 7 8 in 276 mm DVP45 45 Elbow 45 4 7 8 in 124 mm Assembled Height 24 in 610 mm Diameter 10 in 254 mm DVP AS2 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop 7 3 8 in 187 mm 11 3 8 in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in 13 mm TYP DVP90ST 90 Elbow 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm DVP HVS Vent Support UP DVP WS ...

Page 56: ...25 mm 13 1 4 in 367 mm RF12M Roof Flashing Multi pak BEK Trap Cap Brick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm COOL ADD Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DRC RADIUS Cap Shield 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm DVP TRAPFL Flashing 26 in 660 mm DV...

Page 57: ...5 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT Fire Brick Termination Cap 7 1 4 in 184 mm 5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW Vertical Termination Cap High wind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap PVK 80 For use with IPI and DSI appliances o...

Page 58: ... Length Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length ...

Page 59: ...rams continued Figure 17 6 DVP Vent Components 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm DVP HRC SS 10 7 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm DVP HRC ZC SS Fillers DVP TRAP to DVP HPC Side Filler Kit ...

Page 60: ...____ ________________________________________________________________________________ Printed in U S A Copyright 2011 DO NOT DISCARD THIS MANUAL NOTICE Leave this manual with party responsible for use and operation Important operating and maintenance instructions included Read understand and follow these instructions for safe installation and operation Heatilator a brand of Hearth Home Technologie...

Reviews: