HeatFab Saf-T Vent CI Plus Installation Instructions Download Page 4

PI-CCGUY   112602

APPLICATION 4.

 

Support Above a Floor

(

Figure 7

)

The guy support may be set on lengths of
metal bracing that are secured to the floor.
Make sure that the guy brackets are
positioned over the metal bracing.  Drill
through the metal bracing and secure with
appropriate nuts and bolts.  Do not
completely tighten, to allow for expansion
and contraction of the system.

APPLICATION 5. 

Support Horizontally

 

(Figure 8)

Support horizontally by attaching guy wires,
chains or threaded rod to the guy support bracket
holes.  Anchor the guy lines to the building
infrastructure on the underside of the floor or roof.

Floor / Roof

Anchor to Bottom
of Floor / Roof

Guy Support,
 Preferred Option

Guy Support,
Option Two

Figure 6

www.heat-fab.com 800.772.0739

Figure 7

Floor

Metal Cross Brace

Fasten
Brackets
to Bracing

Guy Support

Guy Line

Floor or
Roof

1/4" Pitch
per Foot

Guy Support

Figure 8

Guy Line
Typical of 4

APPLICATION 3. 

Support Below a Floor or Roof

(Figure 6).

Attach guy wires, chains, or threaded rod with a
minimum rated capacity of 500 lbs. to the four hole
locations on the support brackets.  Anchor the guy
lines to the building infrastructure on the underside
of the floor or roof.  Continue to attach vent lengths
above and below the guy support.

Preferred Option

: Install the Guy Support above

the Boot Tee.

Option Two

: Install the Guy Support below the

Boot Tee.

Reviews: