DEVICE SETUP
Parameter
Description
Min
Max
Default
St
Set point
-30
30
-10
r1
Minimum set point value
-50
303
-30
r2
Maximum set point value
-30
150
30
c2
Minimum compressor off time
0
100
4
do
Type of Defrost
0
4
0
dI
Interval between defrost
0
199
6
dt
End defrost temperature set point
-50
127
65
dP
Maximum defrost duration ALARM_ED
1
199
60
d4
Defrost on power-up
0
1
1
dd
Dripping time
0
15
2
F0
Enable evaporator fan control
0
1
0
F2
Stop evaporator fan if compressor off
0
1
0
F3
Evaporator fan status during defrost
0
1
1
Fd
Post-dripping time
0
15
2
Parameter
Description
Min
Max
Default
St
Set point
0
50
34
r1
Minimum set point value
-50
50
0
r2
Maximum set point value
0
150
50
c2
Minimum compressor off time
0
100
4
do
Type of Defrost
0
4
0
dI
Interval between defrost
0
199
6
dt
End defrost temperature set point
-50
127
65
dP
Maximum defrost duration ALARM_ED
1
199
60
d4
Defrost on power-up
0
1
1
dd
Dripping time
0
15
2
F0
Enable evaporator fan control
0
1
0
F2
Stop evaporator fan if compressor off
0
1
0
F3
Evaporator fan status during defrost
0
1
1
Fd
Post-dripping time
0
15
0
St
Set point
0
50
38
r1
Minimum set point value
-50
50
0
r2
Maximum set point value
0
150
50
c2
Minimum compressor off time
0
100
4
do
Type of Defrost
0
4
2
dI
Interval between defrost
0
199
6
dt
End defrost temperature set point
-50
127
40
dP
Maximum defrost duration ALARM_ED
1
199
40
d4
Defrost on power-up
0
1
0
dd
Dripping time
0
15
0
F0
Enable evaporator fan control
0
1
0
F2
Stop evaporator fan if compressor off
0
1
0
F3
Evaporator fan status during defrost
0
1
0
Fd
Post-dripping time
0
15
0
Set o
Set o
Set o
Set 1
Set 1
Set 1
Set 2
Set 2
Set 2
Set 3
Set 3
Set 3
Set 4
Set 4
Set 4
Set 1 - Low Temperature Models - Electric Defrost w/ -10° F Set Point
Set 2 - Medium Temperature Models - Electric Defrost w/ 34° F Set Point
Set 3 - Medium Temperature Models - Air Defrost w/ 38° F Set Point