6
Thermostat setup options / Menu windows
Sensor Setting
Set the type of regular used system. There are 3 options:
Floor reg. : The thermostat regulates floor temperature only. A floor sensor must be connected.
Room reg. : The thermostat regulates room temperature only.
Room/limit: The thermostat regulates room temperature with min. and max. limits for floor temperature. A floor
sensor must be connected.
Press OK and select the required heating system.
Note: If the thermostat is in the room to be heated, select Room/limit. If the thermostat is outside of the room to be
heated, select Floor. Once you have chosen the required setting, press OK. You now need to select the actual sensor
setting so that the thermostat can take this into account during operation.
Auto
Press OK to activate Auto mode. Then enter hour, minute, weekday and load(if load is known).
Note: If load setting is not correct, only energy consumption readout in the “Energy Monitor” Menu will not work.
All other functions will work correct and unaffected no matter the load value.
Power Regulator (this is a Man only menu)
Press OK to activate Power Regulator.
The Power Regulator run in 12-minute cycles.
Fatory Setting
Options
50%
0
– 100%
Examples:
0% = Heating on 0 of 12 min.
25% = Heating on 3 of 12 min.
50% = Heating on 6 of 12 min.
75% = Heating on 9 of 12 min.
100% = Heating on 12 of 12 min.