background image

Heat & Glo  •  8000TR-OAK, 8000TR-OAK-IPI, 8000TRLP-OAKIPI  •  2057-900  Rev. Q  •  6/09

22

A.  Vent Termination Minimum Clearances

Roof Pitch 

H (Min.) Ft.

Flat to 6/12...........................................................1.0*

Over 6/12 to 7/12 .................................................1.25*

Over 7/12 to 8/12 .................................................1.5*

Over 8/12 to 9/12 .................................................2.0*

Over 9/12 to 10/12 ...............................................2.5

Over 10/12 to 11/12 .............................................3.25

Over 11/12 to 12/12 .............................................4.0

Over 12/12 to 14/12 .............................................5.0

Over 14/12 to 16/12 .............................................6.0

Over 16/12 to 18/12 .............................................7.0

Over 18/12 to 20/12 .............................................7.5

Over 20/12 to 21/12 .............................................8.0

Figure 6.1  Minimum Height From Roof To Lowest Discharge  

 

Opening

* 3 foot minimum in snow regions

HORIZONTAL

OVERHANG

VERTICAL

WALL

GAS DIRECT VENT 

TERMINATION CAP

12

X

ROOF PITCH

IS  X/ 12

LOWEST

DISCHARGE

OPENING

2 FT.

MIN.

20 INCHES MIN.

H (MIN.) - MINIMUM HEIGHT FROM ROOF

TO LOWEST DISCHARGE OPENING

6

Termination Locations 

 

Fire Risk.
Maintain  vent  clearance  to  combustibles  as 

specifi ed.

DO NOT

 pack air space with insulation or other 

materials.

Failure to keep insulation or other materials away 

from vent pipe may cause overheating and fi re.

WARNING

Figure 6.2  Staggered Termination Caps

Gas, Wood or Fuel Oil

Termination Cap

B

Gas

Termination

Cap **

A*

*

If using decorative cap cover(s), this distance may need to be

increased. Refer to the installation instructions supplied with the

decorative cap cover.

**

In a staggered installation with both gas and wood terminations, the

wood termination cap must be higher than the gas termination cap.

A

B

6 in. (minimum) up to 20 in.

152 mm/508 mm

18 in. minimum

457 mm

20 in. and over

0 in. minimum

Î

Summary of Contents for 8000TR-OAK

Page 1: ... should be performed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or technicians supervised by an NFI certified professional Leave this manual with party responsible for use and operation DO NOT DISCARD WARNING Important operating and maintenance instructions included Read understand and follow these instructions for safe installation and ope...

Page 2: ...ence Information Model Number Heat Glo a of Hearth Home Technologies Inc 20802 Kensington Boulevard Lakeville MN 55044 brand Not for use with solid fuel Ne doit pas entre utilise avec un combustible solide This appliance must be installed in accordance with local codes if any if not follow ANSI Z223 1 in the USA or CAN CGA B149 installation codes Installer l appareil selon les codes ou reglements ...

Page 3: ...d A Typical Appliance System 17 B Design and Installation Considerations 18 C Tools and Supplies Needed 18 D Inspect Appliance and Components 18 5 Framing and Clearances A Selecting Appliance Location 19 B Constructing the Appliance Chase 20 C Clearances 20 D Mantel and Wall Projections 21 6 Termination Locations A Vent Termination Minimum Clearances 22 7 Vent Information and Diagrams A Approved P...

Page 4: ...C Clean the Appliance 52 D Accessories 52 E Install the Refractory 52 F Ember Placement 52 G Install the Log Assembly 53 H Fixed Glass Assembly 55 I Install the Mesh 55 J Hood 55 K Install Trim and or Surround 55 L Air Shutter Setting 55 15 Troubleshooting A Standing Pilot Ignition System 56 B Intellifire Ignition System 58 16 Reference Materials A Appliance Dimension Diagram 60 B Vent Components D...

Page 5: ...Heat Glo 8000TR OAK 8000TR OAK IPI 8000TRLP OAKIPI 2057 900 Rev Q 6 09 5 B Limited Lifetime Warranty Î ...

Page 6: ...Heat Glo 8000TR OAK 8000TR OAK IPI 8000TRLP OAKIPI 2057 900 Rev Q 6 09 6 B Limited Lifetime Warranty continued ...

Page 7: ...hat can ignite and burn whether flame proofed or not or plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C22 1 A 110 120 VAC circuit for this produc...

Page 8: ...as fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage installe...

Page 9: ...ass and other surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other flammable materials Keep clothing furniture draperies and ot...

Page 10: ...e Controls Wall Controls and Wall Switches Follow the instructions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protection lockout feature Keep remote controls out of reach of children See your dealer if you have questions CLEAR SPACE 3 FT IN FRONT OF FIREPLACE H Before Lighting Fireplace Before operating this fire...

Page 11: ...cause some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT 110 VAC TO THE CONTROL VALVE Improper installation adjustment al teration service or maintenance can cause injury or property damage Re fer to the owner s information manual provided with t...

Page 12: ...ogies fireplace please refer to www fireplaces com A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these in structions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT tou...

Page 13: ...40 minutes Odor from appliance When first operated this appliance may release an odor for the first several hours This is caused by the curing of the paint and the burning off of any oils remaining from manufacturing Odor may also be released from finishing materials and adhesives used around the appliance Film on the glass This is a normal result of the curing process of the paint and logs Glass sho...

Page 14: ...g may be required due to lint from carpeting or other factors Control compartment burner and circulating air passageway of the fireplace must be kept clean CAUTION Risk of Burns The fireplace should be turned off and cooled before servicing When properly maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surro...

Page 15: ...ment and Firebox Top Frequency Annually By Qualified Service Technician Tools needed Protective gloves vacuum cleaner dust cloths Vacuum and wipe out dust cobwebs debris or pet hair Use caution when cleaning these areas Screw tips that have penetrated the sheet metal are sharp and should be avoided Remove all foreign objects Verify unobstructed air circulation Burner Ignition and Operation Frequenc...

Page 16: ...Heat Glo 8000TR OAK 8000TR OAK IPI 8000TRLP OAKIPI 2057 900 Rev Q 6 09 16 Either cobrahead or SIT PRODUCT SPECIFIC Figure 3 1 IPI Pilot Flame Patterns Figure 3 2 Standing Pilot Flame Patterns ...

Page 17: ...ntally CEILING FIRESTOP ON FLOOR OF ATTIC SECTION 8 C VERTICAL TERMINATION CAP SECTION 10 G VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS SECTION 8 C FRAMING HEADED OFF IN CEILING JOISTS SECTION 8 C GAS LINE SECTION 11 MANTEL AND MANTEL LEG SECTION 5 D SURROUND HEARTH EXTENSION VENT PIPE SECTIONS 7 and 8 OPTIONAL WALL SWITCH STORM COLLAR SECTION 10 F NON COMBUSTIBLE ROOF FLAS...

Page 18: ... Risk of Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry C Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers High temperature caulking material Hammer Phillips screwdriver Gloves Framing square...

Page 19: ... traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 5 1 Appliance Locations A B C D E F G H I J K L Inches 55 7 8 49 79 61 1 2 87 22 1 2 38 7 8 3 3 8 10 13 19 3 4 Millimeters 1419 1245 2007 1562 2210 559 1...

Page 20: ...ces NOTICE Install appliance on hard metal or wood surfaces extending full width and depth DO NOT install directly on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to appliance and vent pipe Insulation and other materials must be secured to prevent accidental contact The chase must be properly blocked to prevent blown i...

Page 21: ...pecified Framing or finishing material closer than the minimums listed must be constructed entirely of noncom bustible materials i e steel studs concrete board etc Figure 5 3 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles Note All measurements in inches Figure 5 4 Combustible Mantel Leg or Wall Projections Acceptable on both sides of opening Combustible Mantels Combustible Mantel...

Page 22: ...OPENING 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire WARNING Figure 6 2 Staggered Termination Caps Gas Wood or Fuel Oil Term...

Page 23: ...tted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap 3 All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap See Note 1 See Note 2 Note 3 Local ...

Page 24: ...ght pipe is allowed between two 45º elbows see Figure 7 1 Figure 7 1 7 Vent Information and Diagrams B Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams D Measuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards Pipe measurements are shown using the effective length of pipe see Figure 7 2...

Page 25: ...2 mm 5 1 2 ft 1 7 m 1 ft 305 mm 8 ft 2 4 m 2 ft 610 mm 13 ft 4 0 m 3 ft 914 mm 18 ft 5 5 m V1 H1 40 ft 12 2 m Maximum H1 20 ft 6 1 m Maximum V1 Minimum H1 H2 Maximum Two 90º Elbows back to back Not approved 6 in 152 mm 2 1 2 ft 762 mm 1 ft 305 mm 5 ft 1 5 m 2 ft 610 mm 10 ft 3 1 m 3 ft 914 mm 15 ft 4 6 m V1 H1 H2 50 ft 15 2 m Maximum H1 H2 17 ft 5 2 m Maximum Top Vent Horizontal Termination Note F...

Page 26: ...H1 Maximum V2 Minimum H2 Maximum V1 V2 Minimum H1 H2 Maximum Elbow only 3 ft 914 mm 1 1 2 ft 457 mm 6 1 2 ft 2 m 2 ft 607 mm 9 1 2 ft 2 9 m 1 ft 305 mm 5 ft 1 5 m 2 ft 610 mm 10 ft 3 1 mm 3 ft 914 mm 15 ft 4 6 m 2 ft 610 mm 10 ft 3 1 m 1 ft 305 mm 5 ft 1 5 m 3 ft 914 mm 20 ft 6 1 m H1 H2 20 ft 6 1 m Maximum V1 V2 H1 H2 50 ft 15 2 m Maximum H2 H1 V2 V1 ...

Page 27: ...bending the part back and forth until it breaks see Figure 7 8 3 Match the amount of vertical in the system with the chart to find the appropriate position to set the Flue Restrictor see Figure 7 9 CHART Vertical Top Vent NG Top Vent LP Rear Vent NG Rear Vent LP 4 1 1 No Restrictor No Restrictor No Restrictor 8 2 2 1 2 1 1 No Restrictor 15 3 3 3 2 2 2 1 2 20 3 4 3 3 3 3 2 3 25 3 4 3 3 3 3 2 3 30 4 ...

Page 28: ...ecific restrictions on this value EXCEPT V1 V2 H1 cannot exceed 50 ft 15 2 m V1 H1 H2 V2 V1 V2 Minimum H1 H2 Maximum ELBOW ONLY 3 ft 914 mm 3 ft 914 mm 2 ft 610 mm 7 ft 2 1 m 7 ft 2 1 m 4 ft 1 2 m 17 ft 5 2 m 17 ft 5 2 m H1 H2 17 ft 5 2 m Maximum V1 V2 H1 H2 50 ft 15 2 m Maximum Figure 7 11 Two Elbows H1 V1 V2 Three Elbows INSTALLED HORIZONTALLY H1 H2 V1 V2 Top Vent Vertical Termination continued F...

Page 29: ...on Figure 7 13 Figure 7 14 No Elbow One 45º Elbow H1 1 1 2 ft 457 mm Maximum H1 9 in 229 mm Maximum H1 H1 This model is tested and approved to use 45º elbows in corner installations However 90º elbows will result in better performance Note LP units cannot be used with a 45º elbow A 90º elbow must be used ...

Page 30: ... 2 m 1 1 2 ft 457 mm 4 ft 1 2 m 8 ft 2 4 m 6 ft 1 8 m 2 1 2 ft 762 mm 6 ft 1 8 m 12 ft 3 6 m 8 ft 2 4 m 4 1 2 ft 1 4 m 12 ft 3 6 m 20 ft 6 1 m V1 H1 H2 50 ft 15 2 m Maximum H1 8 ft 2 4 m Maximum H1 H2 20 ft 6 1 m Maximum H1 Maximum V1 Minimum H2 H3 H1 H2 H3 Maximum 2 1 2 ft 762 mm 1 ft 305 mm 6 in 152 mm 2 1 2 ft 762 mm 4 ft 1 2 m 1 1 2 ft 457 mm 1 ft 305 mm 5 ft 1 5 m 6 ft 1 8 m 2 1 2 ft 762 mm 6...

Page 31: ...ows Figure 7 18 V1 Minimum H1 Maximum 6 in 152 mm 2 ft 607 mm 1 1 2 ft 457 mm 4 ft 1 2 m 2 1 2 ft 762 mm 6 ft 1 8 m 3 1 2 ft 1 0 m 8 ft 2 4 m V1 H1 50 ft 15 2 m Maximum V1 H1 8 ft 2 4 m Maximum H1 H2 Maximum V1 Minimum Two 90º Elbows back to back 1 12 ft 457 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 3 ft 914 mm 5 ft 1 5 m 3 1 2 ft 1 0 m V1 H1 50 ft 15 2 m Maximum H1 V1 ...

Page 32: ...ed Three Elbows Figure 7 19 H1 Maximum V1 Minimum H2 H1 H2 Maximum 2 ft 610 mm 1 ft 305 mm 3 1 2 ft 1 0 m 5 1 2 ft 1 7 m 4 ft 1 4 m 1 1 2 ft 457 mm 4 ft 1 4 m 8 ft 2 4 m 8 ft 2 4 m 3 1 2 ft 1 0 m 8 ft 2 4 m 16 ft 4 9 m 8 ft 2 4 m 4 1 2 ft 1 4 m 12 ft 3 6 m 20 ft 6 1 m V1 V2 H1 H2 50 ft 15 2 m Maximum V2 V1 H2 H1 ...

Page 33: ... the part Position the shield so the longest dimension 13 1 2 inch is placed in same direction the elbow is pointing Center the shield directly above the elbow with a 1 2 inch air space between shield and combustible surface see Figure 8 3 Heat shield required if vertical distance between top of horizontal elbow and any combustible surface above elbow is less than 4 inches Heat shield not required...

Page 34: ...ith diameter one inch greater than the pipe is acceptable Whenever a non combustible wall is penetrated the wall shield firestop is only required on one side and no heat shield is necessary Shows center of 10 in x 12 in vent framing hole for top venting The center of the hole is 1 inch above the center of the horizontal vent pipe With minimum vertical or 12 inch and 90º elbow A B C D Inches 44 3 4 ...

Page 35: ...he ceiling joists when installed with a attic insulation shield It must be under joists between floors that are not insulated Refer to Figure 8 8 Secure with three fasteners on each side WARNING Risk of Fire DO NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating Figure 8 7 Installing Ceiling Firestop Figure 8 8 Installing the Attic Shield 3 FASTENE...

Page 36: ...ese tabs must be used to prevent blown insulation from getting between the shield and vent pipe and to maintain air space clearance Figure 8 9 Attic Insulation Shield BEND ALL TABS INWARD 90 TO MAINTAIN CLEARANCE AND PREVENT INSULATION FROM FALLING INSIDE INSERT 3 SCREWS BEND 3 TABS OUTWARD TO FASTEN TO CEILING FIRESTOP BEND REMAINING TABS INWARD 90 DEGREES TO MAINTAIN CLEARANCE Vaulted Ceiling In...

Page 37: ...t 9 Appliance Preparation Figure 9 2 Remove the center insulation plug Figure 9 3 Cut the metal retaining band and fold the sides out Figure 9 4 Fold the center parts of the retaining band up and use to remove the seal cap Figure 9 5 Discard the seal cap remove and discard the insulation basket Note Once the vent cap has been removed it cannot be reattached Proceed to Section 10 Figure 9 1 Remove ...

Page 38: ...lation gasket Figure 9 7 Cut the metal retaining band and fold the sides out Figure 9 8 Fold the center parts of the retaining band out and use to remove the seal cap Figure 9 9 Discard the vent cap remove and discard the insulation basket Figure 9 10 Attach the first vent section it will snap into place Slide the insulation gasket onto the vent section up against the appliance and over the tabs NO...

Page 39: ...he diagram shows how to properly position and secure the appliance see Figure 9 11 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing Level the appliance from side to side and front to back Shim the appliance as necessary It is acceptable to use wood shims underneath t...

Page 40: ...te Set up 1 Straighten the tabs on the grate bracket see Figure 9 12 and remove grate from unit 2 Remove grate bracket see Figure 9 12 by bending it back and forth until it breaks Discard grate bracket 3 Remove 4 tabs holding base refractory see Figure 9 12 by bending tabs back and forth until they break 4 Reinstall grate into unit see Figure 9 13 Figure 9 12 Removing Grate REMOVE GRATE REMOVE GRA...

Page 41: ...lling holes DO NOT penetrate inner pipe For 90º and 45º elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe Commercial Multi family Multi level exceeding two sto ries or Hi...

Page 42: ...pipe section Secure the pipe and slip section with two screws no longer than 1 2 in 13 mm using the pilot holes in the slip section See Figure 10 6 120º Figure 10 7 Securing Vertical Pipe Sections 120º Figure 10 8 Securing Horizontal Pipe Sections C Secure the Vent Sections Vertical runs must be supported every 8 ft 2 44 m after the 25 ft 7 62 m maximum unsupported rise Horizontal sections must be...

Page 43: ... D Disassemble Vent Sections Rotate either section see Figure 10 9 so the seams on both pipe sections are aligned as shown in Figure 10 10 Pull carefully to separate the pieces of pipe Figure 10 10 Align and Disassemble Vent Sections Figure 10 9 Rotate Seams for Disassembly ...

Page 44: ...IMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING CAULK NOTICE Failure to properly caulk the roof flashing could cause water entry Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing where it contacts the roof surface See Figure 10 12 F Assemble and Install Storm Collar CAUTION Risk of Cuts Abrasions or Flying Debris Wear protective gloves ...

Page 45: ...Figure 10 16 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 10 16 If the wall thickness does not allow the required 1 1 2 in 38 mm heat shield overlap when installed an extended heat shield must be used If the wall thickness is less tha...

Page 46: ...ing may be brought to the edge of the cap base Flash and seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent a...

Page 47: ...on DO NOT use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure may cause explosion Verify inlet pressures Verify minimum pressures when other household gas appliances are operating Install regu...

Page 48: ... voltage and 110 VAC voltage cannot be shared within the same wall box WARNING Risk of Shock or Explosion DO NOT wire 110V to the valve or to the appliance wall switch Incorrect wiring will damage controls Determine if the appliance uses an Intellifire ignition sys tem or standing pilot ignition system Open the control access panel or remove the decorative front A red or black ignitor button as sho...

Page 49: ...anding Pilot Ignition Wiring Diagram WARNING Risk of Shock Replace damaged wire with type 105º C rated wire Wire must have high temperature insulation Note Appliance will not operate unless properly grounded IGNITION MODULE 3 VAC TRANSFORMER 3 VAC GRN ORG INTERMITTENT PILOT IGNITOR IGNITION MODULE 3V ON OFF WALL SWITCH LOW VOLTAGE PLUG IN 3V TRANSFORMER NEUTRAL HOT GROUND FLAME SPARKER SENSOR REMO...

Page 50: ...male as shown W H T W HT B L K BLK GRN wire inside box Copper ground attached to GRN screw with GRN wire 14 2WG Cover Plate outside firebox Romex Connector Figure 12 4 Junction Box Detail NOTICE DO NOT wire 110 VAC to wall switch Red Switch Switch Box Red Black Black Green Green White Power Supply Wires White Red Black Green White Minimum 14 3 AWG with Ground Junction Box Knockout Figure 12 5 Junc...

Page 51: ...2 11 10 9 8 7 6 TOP OF HOOD 4 12 13 11 32 CEILING 1 2 B Facing Material Metal front faces may be covered with non combustible materials only Facing and or finishing materials must not interfere with air flow through louvers operation of louvers or doors or access for service Facing and or finishing materials must never overhang into the glass opening Observe all clearances when applying combustible m...

Page 52: ...ons in manual DO NOT place embers directly over burner ports Replace ember material annually Improperly placed embers interfere with proper burner operation Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over ports Care should be taken not to cover the lighting trail of ports from back to front Place dime size pieces of Glowing Embers...

Page 53: ...est on the base refractory STEP 2 Log 1 SRV2057 720 Place log 1 so that the bottom right notch on log rests on far right grate tine The bottom left notch on log 1 must mate over the log tab on the burner face 1 STEP 3 SRV2057 721 Place log 2 nose to nose with log 1 The bottom notch on log 2 must mate over the log tab on the burner face STEP 4 SRV2057 722 Place log 3 so that the bottom notches mate...

Page 54: ... as shown The left end of log 6 should touch the upper knot of log 2 The right end of log 6 should rest on the grate bar centered between tine 4 and 5 NOTE The front faces C of log 6 and 2 should be on the same plane This is key in avoiding flame impingement 1 C C NOTE Finished top view 2 3 1 5 4 6 STEP 6 SRV2057 724 Notch in left end of Log 5 will interlock with front left corner of grate Rest rig...

Page 55: ...removed cracked broken or scratched Replace as a complete assembly Removing Fixed Glass Assembly Pull the four glass assembly latches out of the groove on the glass frame Remove glass door from the appliance see Figure 14 2 Replacing Fixed Glass Assembly Replace the glass door on the appliance Pull out and latch the four glass assembly latches into the groove on the glass frame I Install the Mesh ...

Page 56: ...rmocouple connection at the gas valve is fully in serted and tight hand tighten plus 1 4 turn Verify proper voltage output from the thermocouple to the valve Place one millivolt meter lead wire on the thermocouple copper lead Place the second lead wire on the solder button on the back of the valve blue wire Start the pilot and hold the valve knob in The mil livolt reading should read 8 16 millivol...

Page 57: ...fill the fuel tank B Improper gas inlet pressure Natural gas should be 5 14 in w c LP should be 11 14 in w c Verify pressure with manometer C Inner vent pipe leaking exhaust gases back into the system Check venting system for damage Replace repair im properly assembled pipe sections D Glass installed improperly Check to ensure glass is installed properly Replace fixed glass panel assembly E Thermopi...

Page 58: ...rmer is installed and plugged into module Check voltage of transformer under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good transformer are between 3 2 and 2 8 volts AC B A shorted or loose connection in wiring configuration or wiring har ness Remove and reinstall the wiring harness that plugs into module Verify there is a tight fit Verify pilot as...

Page 59: ...rify cor rect pilot orifice is installed and gas inlet is set to pressure specifications Clean flame sensing rod with emery cloth to remove any contaminants that may have accumulated on flame sensing rod C Module is not grounded Verify module is securely grounded to metal chassis of ap pliance Verify that wire harness is firmly connected to the module D Damaged pilot assembly or contami nated flame sens...

Page 60: ...fer to Section 5 Figure 16 1 Appliance Dimensions D S P M L N F J K Ø E C B A H G Q R T O I GAS LINE ACCESS ELECTRICAL ACCESS Ø U C L C L Location Inches Millimeters L 43 1091 M 48 1221 N 7 177 O 1 1 8 28 P 38 3 4 983 Q 2 1 4 58 R 5 1 4 134 S 28 7 8 733 T 44 1 4 1124 U 8 203 Location Inches Millimeters A 35 1 2 900 B 17 3 4 450 C 21 1 2 548 D 11 5 8 297 E 8 203 F 40 1019 G 9 1 8 232 H 2 1 4 56 I 3...

Page 61: ...05 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP 10 in 254 mm 24 in 610 mm DVP HVS Vent Support DVP AS Attic Shield DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45º Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 276 mm 13 mm Pipe Effective Length Inches Millimeters DVP4 4 102 DVP6 6 152 DVP12 12 305 DVP24 24 610 D...

Page 62: ... 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield B Vent Components Diagrams continued Figure 16 3 DVP vent components Term Cap Minimum Effective Length Maximum Effect...

Page 63: ...ap Cap Brick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADD Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield B Vent Components Diagrams con...

Page 64: ... in 98 mm DVP TV VerticalTermination Cap 7 1 4 in 12 in 305 mm 184 mm 5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind PVK 80 For use with IPI and DSI appliances only 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap B Vent Components Diagrams continued Figure 16 5 DVP vent components ...

Page 65: ...____________________________________________________________ ________________________________________________________________________________ This product may be covered by one or more of the following patents United States 4593510 4686807 4766876 4793322 4811534 5000162 5016609 5076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452708 5542407 5601073 5613487 5647340 5688568 ...

Reviews: